OREGENCY
Owners &
Regency HorizonTM HZ4OE Installation Manual
Gas Fireplace MODELS: 14Z40E•NG1 Natural Gas
I4Z40E•LP1 Propane
WARNING: FOR YOUR SAFETY
If the information in these instructions are not followed exactly, What to do if you smell gas:
a fire or explosion may result causing property damage, • Do not try to light any appliance
personal injury or loss of life. • Do not touch any electrical switch:
do not use any phone in your
FOR YOUR SAFETY building.
Do not store or use gasoline or other flammable vapors and • Immediately call your gas supplier
liquids in the vicinity of this or any other appliance. from a neighbour's phone. Follow
Installation and service must be performed by a qualified the gas supplier's instructions.
installer, service agency or the gas supplier. • If you cannot reach your gas
supplier, call the fire department.
It,ted by.
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
EDI
Homeowner: Please keep these instructions for future reference.
Intertek
919 165 FM FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1144 05/29/12
EFTA00301420
MANUFACTURED MOBILE HOME REQUIREMENTS
INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
This Regencr product has been tested and listed by Warnock Hersey/Intertek as a Direct Vent Wall Furnace to the following
standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88-2009/ CSA 2.33-2009 and GAS-FIRED APPLIANCES FOR
USE AT HIGH ALTITUDES CAN / CGA 2.17-M91.
This appliance may only be installed in an aftermarket permanently located, manufactured (U.S.A only) or mobile home,
where not prohibited by local codes.
This Direct Vent System Appliance must be installed in accordance with the manufacturers installation instructions and the
Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria
for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home
Standard in Canada.
This appliance installation must comply with the manufacturers installation instructions and local codes, it any. In the absence
of local codes follow the current National Fuel Gas Code, ANSI 2223.1 and the current National Electrical Code ANSI/NFPA
70 in the U.S.A., and the current CAN/CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1
in Canada.
This appliance comes equipped with a dedicated #8 Ground Lug for attachment of the ground wire to the steel chassis as
applicable to local codes.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the
National Electrical Code, ANSI/NFPA 70. or the Canadian Electrical Code, CSA C22.1.
This appliance can only be used with the type of gas indicated on the rating plate.
This appliance is not convertible for use with other gases.
Ensure that structural members are not cut or weakened during installation.
This appliance may be installed as an OEM installation in a manufactured home (USA only) or mobile home and must be
installed in accordance with the manufacturer's instruction and the Manufactured Home Construction and Safety Standard,
Title 24 CFR. Part 3280, in the Untied States, or the Standard for Installation in Mobile Homes, CAN/CSA Z240 Mkt, in
Canada.
W ilkA WARNING! lir
HOT GLASS WILL
CAUSE BURNS
DO NOT TOUCH GLASS
UNTIL COOLED
NEVER ALLOW CHILDREN
TO TOUCH GLASS
Regency HorlzonTM HZ40E Gas Fireplace
EFTA00301421
To the New Owner:
Congratulations!
You are the owner of a state-of-the-art Gas Fireplace by REGENCY°. The HZ40E has been
designed to provide you with all the warmth and charm of a fireplace at the flick of a switch.
The model HZ4OE has been approved by Warnock Hersey/Intertek for both safety and efficiency.
As it also bears our own mark, it promises to provide you with economy, comfort and security for
many trouble free years to follow. Please take a moment now to acquaint yourself with these
instructions and the many features of your Regency Fireplace.
ONE REGENCY
marmoithu. We recommend that our products be
FIREPLACE
IRSTRLITC installed and serviced by professionals
NFI who are certified in the U.S. by the
National Fireplace Institute° (NFI)
or in Canada by Wood
Energy Technical WoodEmmy
Wakeleateleg
CERTIFIED., Training (WETT).
ONE TREE TM
Regency HorlzonTM HZ40E Gas Fireplace
EFTA00301422
TABLE OF CONTENTS
SAFETY DECAL 4" x 6-5/8" venting 35
High Elevation Gas Line Installation 36
Copy of Safety Decal 5 Pilot Adjustment 36
Gas Pipe Pressure Testing 36
880 S.I.T. Valve Description 36
REQUIREMENTS Aeration Adjustment 36
AC power adaptor installation (for surefire systems) 37
MA Code - CO Detector 6 Wiring Diagram 38
(for the State of Massachusetts only) 6 proflame system GT 38
proflame system GTM 38
INSTALLATION proflame system GTMF with optional fan 39
optional fan Wiring Diagram 40
Without ProFlame GTMF system 40
Important Message 8 Optional Remote Control 41
Before You Start 8 Receiver Wall Switch 41
General Safety Information 8 wall mount On / Off Switch and battery compartment
Installation Checklist 9 installation and/or receiver installation 42
Locating Your Gas Fireplace 9 GTMF remote installation 43
Heatwave Duct System 9 Optional fan Installation 46
Heat Release kit 9
Optional fan Installation - into existing installations 47
Clearances 10 Inner Panel Installation 49
Mantel Clearances 11
Glass Crystals or optional ceramic stones 50
Mantel Leg Clearances 11
Optional Pebble / Crystal Installation 51
Unit Assembly Prior To Installation 12
Glass door Installation 52
Nailing Strips 12
Optional mesh glass guard 53
Installation Access panel 12 54
4 piece faceplate installation
Front face Nailing strip installation 12
Inner and outer door frame installation 55
Framing Dimensions 13
Non-Combustible Requirements 14
Non-combustible facing installation 14 OPERATING INSTRUCTIONS
Framing & Finishing 15
Framing & Finishing 16 Operating Instructions 56
Non-Combustible Requirements 16 First Fire 56
Exterior Vent Termination Requirements 17 Lighting Procedure 56
4" x 6-5/8" Rigid Pipe 18 Shutdown Procedure 56
Cross Reference Chart only 18 Normal Operating Sounds of Gas Appliances 56
Vent Restrictor Position 20 Copy of Lighting Plate Instructions 57
Venting Introduction 21 Maintenance Instructions 58
Venting Arrangement for Horizontal Terminations 21 Glass Gasket 58
Horizontal Terminations 22 Glass Door 58
Flex Vent 4" x 6-7/8" 22 Glass Replacement 58
Horizontal terminations 23 General Vent Maintenance 58
Rigid Pipe 4" x 6-5/8" 23 Valve assembly Replacement 59
Horizontal Terminations 24
Rigid Pipe 4" x 6-5/8" 24 PARTS LIST
Vertical terminations 27
Rigid Pipe 4" x 6-5/8" 27
Venting Arrangement for Vertical Terminations 28 Main Assembly 60
Vertical Termination with Co-Linear Flex System 29 Accessories 61
Vertical Terminations 30
Rigid Pipe 4" x 6-5/8" 30 WARRANTY
Venting Arrangements - Vertical Terminations 32
Unit Installation with Horizontal Termination 33
4" x 6-5/8" venting 33 The Warranty: Limited Lifetime 63
Unit Installation with Horizontal Termination 34
Unit installation with Vertical Termination 35
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301423
SAFETY LABEL
This is a copy of the label that accompanies
each HZ40E-NG1 and HZ40E-LP1 Direct Vent
Gas Fireplace. We have printed a copy of the
contents here for your review.
NOTE: Regency, units are constantly being
improved. Check the label on the unit and if
there is a difference, the label on the unit is the
correct one.
COPY OF SAFETY DECAL
Lined: VENTED GAS FIREPLACE HEATER! FOYER AU GAZ A EVACUATION DO NOT REMOVE THIS LABEL r NE PAS ENLEVER CETTE ETIQUETTE
Certified for/Leith& pour: CANADA and U.S A.
Tested to: CAN/CGA-2.17-M91(R2009)
Intertek
ANSI 221.88-2009/CSA 2.33-2009
MAY BE INSTALLED IN MANUFACTURED (MOBILE' HOMES AFTER FIRST SALE.
litREPN.cT
Serial No/ No de aerie
412
4001172
O NATURAL GAS: Model H240E-NG1 APPAREIL FONCTIONNANT AU NATURAL GAS Minimum Clearances to Combustibles I
Degagement Minimum De Materisux Combustibles
CONCU POUR ETRE POELE: Mode* HZ40E-NG1
Minimum supply pressure 5if WC/C.E. (125IPa) Preston mnimurn Side Walls
Manifold pressure 34 WCIC.E. f327IPa) Preston a la aibulum dechappement Neves A Er (203mm)
Orifice sue IMO CA1S Grandeur de nnecteur Ceiling
Maximum input 26.000 Mufti (7.61 kW) Debt Calonligue maximum salon 8 22' (559mm)
Minimum input 18,000 Mufti (5 28 kW) Yaltitude Min. Mantel Height
Altitude 04500 Dpi (0-1372m) C 1r (432mm)
Max. Mantel Depth
O PROPANE GAS: Model HZ40E-LPI EQUIPE A CUISINE POUR GAZ PROPANE 13" (330mm)
CONCU POUR ETRE POELE: ModeleHT.40E-LP1 Alcove Width
Mnimum supply pressure 11' WC (2.73 kpa) Preston Minimum E 84" (1524mm)
Manifold pressure 10' WC1C.E. (2491Pa) Presslon a b turauNre dolchapperneM elevee Alcove Depth
Orifice sae #53 CMS Grandeur de I1Mecteur F 36- (2134mm)
MaxmLon Input 25.500 Btuiti (7.47kW) DeWI Calorilque maxenum scion DOOR SEAL: Please
Minimum Input 21.000 Bbih (6.15 kW) raktude check that the door is lawsuitsction Munui let
Altitude 04500 fipl (0-1372m) properly sealed minute:ens)
This appliance must be inslallad n aconlance *Mb local codes. if any: if nom. Sow the National Fool Gas Code. ANSI 2223.1. cr Natural Gas and Propane Install on Code. GSA0169.1.
This MpliaMe muslin :Walled ine000rdance wen me StandiedCAN:CSAZ2401M. M0bleHousino.in Canada. Or wsb me HanulachgedHolneCcoseucbonandSalgYSlandard. tee 24 CFRP(0 3280.in
the Veiled SOWS. C. wails, SW) StaMarO PS Mt apoicams.ANSUKSBCS A225 liNFPASOI A. Mantoactured Horne IntlellatiCOS Standard C•ANSI All 9.20u NFPA SOIC standard reeRecreed4no Wades
This appliamo is only forum ailh the type dips irdicalcdrolls recap plate and may be mimed n an aftermarkel. permanently lomat manufactuogrnobilaThomewhere nc4pohlaited bylocal cedes. See
vanes manual fordetals. This applance d notoomembie torus, enhothareases.wiless a certifed iutisused.
Installer reooenFlselonles codes ourealementsOcata. ou.en rabeence de MK Nolemerts. INICOIOS 01:la 2223.1. National FuelGasCode ouCSA43149.1 en vIgueur
Installer repoereil salon le norms CAN'CSA-Z240. Sane WM. MilltiOn MOON, Ou CANCSA-Z240 VC. VOIColOS 00 CaMOIn0. Ou la tonne 24 CFR Pert 3280. ManulaCtunid HOMO Consau(ton and Safety
Standard. Si ces norm*,ne pampas acclimates. utilsez le normeANSUNCSBCSA225.1/NFPA 501A. Manufactured Home Installations Standard. ouANSI AI 19 2 ou NFPASOIC Standardfor Recreational
Vehicles.
Cal apparel don etre dela.unouemem avec to tyDedepa2 ndiove suns plaque signeXHIgue.Cecamaret.o errs ru"s"e O&M. unBmiton preeabnqueeou moDhe le -V. SeuleclaliV)InSIfille daMtoule Si
les retflaMenISIOG3us le DaMeltenl Writ WOG Cla IVIIMSSor pets pluSde fenSeirecnertS CSISCOOMII=[OS COnAutible DOurunS ulllexIbOnaveCilliti$2.aSurS. on.IfCuSSOCONDS *SI Vella
Thls vented gas fireplace heater is not forme wither Altars. Ne pas utikserde Niro a air avec ce foyerau pas itevacuatIon.
FORUSEWITHGLASSDOORSCERTIFIEDWITH THEAPPLIANCEONLY POUR UMISATIONUMOUEMENT AVEC LESPORTESENVERRECERTIFIEESAVEC L'APPAREIL
Fan (1Pala 258-911) vase," canals. Fdroon au Canals
Ela-tical supply l Electrique 115VAC. 1.13A 6011t
NOT FOR USE WITH SOLID FUELS.! NE PAS UTILISER AVEC DU COMEIUSTBLE SOLIDE. FPI Fireplace Products International Ltd. Delta. BC. Canada 9i#166
For the State of Massachusetts, installation
and repair must be done by a plumber or
gasfitter licensed in the Commonwealth of
Massachusetts.
For theStateof Massachusetts. flexible con-
nectors shall not exceed 36inches in length.
For the State of Massachusetts, the appli-
ances individual manual shut-off must be a
t-handle type valve.
The State of Massachusetts requires the
installation of a carbon monoxide alarm in
accordance with NFPA 720 and a CO alarm
with battery back up in the same room where
the gas appliance is installed.
Regency HorizonTM HZ40E Gas Fireplace
EFTA00301424
REQUIREMENTS
MA Code - CO Detector
(for the State of Massachusetts only)
5.08: flodlfleatIons to NFPA-54. Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in pan for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or guiltier shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic. the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements: provided, however. that during said thirty (30) day period. a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSUUL 2034 listed and IAS certified.
3. SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled healing appliance or. equipment. The
sign shall read in print size no less than one-half(1f2) inch in size. "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signagc installed in accordance with the provisions of 248 CMR
5.08(2X2)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(8)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by
the Board: and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment. the
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components: and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases. but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation alit:Will:MS: and
2. The "special venting systems" shall be Product Approved by the Board. and the instructions for that system shall include a pans list and
detailed installation instructions.
(c) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment. all seating instructions.
all pans lists for venting instructions. and'or all venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301425
DIMENSIONS
45 5/8"
PEW 39-13/16'
1
— 1. —
. 364- —
—Iv
:2
a , —
43X1 (1092mm
341,4- (972mm)
48. (1238mrn)
4
(902m1
36" (gum.)
mew
El
Regency I-Icemen' 14240E Gas Fireplace
EFTA00301426
INSTALLATION
11)Under no circumstance should this
IMPORTANT MESSAGE YOUNG CHILDREN SHOULD BE CARE- appliance be modified. Parts that have
SAVE THESE FULLY SUPERVISED WHEN THEY ARE to be removed for servicing should be
replaced prior to operating this appliance.
IN THE SAME AREA AS THE APPLI-
INSTRUCTIONS ANCE. TODDLERS.YOUNG CHILDREN
12) Installation and any repairs to this appliance
AND OTHERS MAY BE SUSCEPTIBLE
The Gas Fireplace must be installed in accordance should be done by a qualified service person.
with these instructions. Carefully read all the TO ACCIDENTAL CONTACT BURNS. A A professional service person should be called
instructionsin thismanual first. Consult the'authority PHYSICAL BARRIERS IS RECOMMEND- to inspect this appliance annually. Make it a
having jurisdiction"todeterminetheneed for aperrnit ED IF THERE ARE AT RISK INDIVIDUAL practice to have all of your gas appliances
prior tostarting theinstallation.It is the responsibility IN THE HOUSE. TO RESTRICT ACCESS checked annually.
of the installer to ensure this fireplace is installed TO A FIREPLACE OR STOVE. INSTALL
in compliance with manufacturers instructions and AN ADJUSTABLE SAFETY GATE TO 13) Do not slam shut or strike the glass door.
all applicable codes. KEEP TODDLERS, YOUNG CHILDREN
AND OTHER AT RISK INDIVIDUALS OUT 14) Under no circumstances should any solid fuels
OF THE ROOM AND AWAY FROM HOT (wood. paper, cardboard, coal. etc.) be used in
BEFORE YOU START SURFACES. this appliance.
Safe installation and operation of this appliance 15) The appliance area must be kept clear and free
requires common sense, however, we are required CLOTHING OR OTHER FLAMMABLE of combustible materials. (gases andotherflam•
by the Canadian Safety Standards and ANSI MATERIAL SHOULD NOT BE PLACED made vapours and liquids).
Standards to make you aware of the following:
ON OR NEAR THE APPLIANCE.
INSTALLATION AND REPAIR SHOULD Emissions from burning wood or gas could
BE DONE BY AN AUTHORIZED contain chemicals known to the State of
SERVICE PERSON. THE APPLIANCE
GENERAL SAFETY Califomia to cause cancer, birth defects or
SHOULD BE INSPECTED BEFORE INFORMATION other reproductive harm.
USE AND AT LEAST ANNUALLY BY A
PROFESSIONAL SERVICE PERSON. 1) The appliance installation must conform with
MORE FREQUENT CLEANING MAY local codesor,in theabsenceof localcodes, with
the current Canadian or National Gas Codes.
BE REQUIRED DUE TO EXCESSIVE
CANI -B149orANSI Z223.1 Installation Codes.
LINT FROM CARPETING. BEDDING
MATERIAL,ETC.IT IS IMPERATIVETHAT 2) The appliance when installed, must be
CONTROL COMPARTMENTS.BURNERS electrically grounded in accordance with local
AND CIRCULATING AIR PASSAGEWAYS codes, or in the absence of local codes with the
OF THE APPLIANCE BE KEPT CLEAN. current National Electrical Code. ANSI/NFPA 70
or CSA C22.1 Canadian Electrical Code.
DUE TO HIGH TEMPERATURES, THE 3) See general construction and assembly
APPLIANCE SHOULD BE LOCATED instructions. The appliance and vent should be
enclosed.
OUT OF TRAFFIC AND AWAY FROM
FURNITURE AND DRAPERIES. 4) This appliance must be connected to the
specified vent and terminationcaptotheoutside
of the building envelope. Never vent to another
WARNING: FAILURE TO INSTALL THIS room or inside a building. Make sure that the
APPLIANCE CORRECTLY WILL VOID vent is fitted as per Venting instructions.
YOUR WARRANTY AND MAY CAUSE A
SERIOUS HOUSE FIRE. 5) Inspecttheventingsystem annually forblockage
and any signs of deterioration.
CHILDREN AND ADULTS SHOULD BE 6) Venting terminals shall not be recessed into a
ALERTED TO THE HAZARDS OF HIGH wall or siding.
SURFACE TEMPERATURES. ESPE-
CIALLY THE FIREPLACE GLASS. AND 7) Any safety glass removed for servicing must be
SHOULD STAY AWAY TO AVOID BURNS replaced prior to operating the appliance.
OR CLOTHING IGNITION.
8) To prevent injury, do not allow anyone who is
unfamiliarwiththeoperation to usethefireplace.
9) Wear gloves and safety glasses for protection
while doing required maintenance.
10) Be aware of electrical wiring locations in walls
and ceilings when cutting holes for termination.
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301427
INSTALLATION
This includes: 4) This appliance is Listed for bedroom
INSTALLATION installations using the standard Remote
CHECKLIST 1) Clocking the appliance to ensure the correct
firing rate (rate noted on label 26.000 Equal
(thermostat system). Some areas may have
funher requirements. check local codes before
1) Locate appliance (NG).25.500 Btum (LP)after burning appliance installation.
a) Room location (Refer to' ocating Your Gas for 15 minutes.
fireplace section) 5) The HZ40E Direct Vent Gas Fireplace
b) Clearances to Combustibles (Refer to 2) If required. adjusting the primary air to ensure is approved for alcove installations, see
'Clearances" section) that the flame does not carbon. First allow the "Clearances" section for details.
c) Mantle Clearances (Refer to "Mantel unit to bum for 15.20 min. to stabilize.
Clearances' section) 6) We recommend that you plan your installation
d) Framing 8 Finishing Requirements (Refer CAUTION: Any alteration to the product that on paper using exact measurements for
to "Framing 8 Finishing" section) causes sooting orcarbonIng that resultsIn dam- clearances and floor protection before actually
e) Venting Requirements (Refer to "Venting' age Is not the responsibility of the manufacturer. installing this appliance. Have an authorized
section) inspector. dealer. orinstaller reviewyour plans
before installation.
2) Position nailing strips (Refer to 'Unit Assembly
Prior to Installation). Note: For vent terminations refer to "Exterior
Vent Termination Locations" section.
3) Slide unit into place.
4) Remove installation access panel. LOCATING YOUR
Heat Wave
5) Install vent (Refer to 'Venting Arrangement' GAS FIREPLACE asvarr---er
sections).
1) When selecting a location for your fireplace.
ensure that the clearances are met.
HEATWAVE
6) Make gas connections (Refer to "Gas Line
Installation section). DUCT SYSTEM
2) The appliance must be installed on a flat. solid.
7) Make electrical connections to receptacle continuous surface For example a wood. metal OPTIONAL KIT #946-556
supplied with unit (recommended). or concrete floor or in a raised (on the wall) ap-
plication. The appliance must be installed on The HeatWave Air Duct Kit increases the
8) Install 4 AA batteries into receiver/switch box a metal or wood panel extending the full width effectiveness of your fireplace by dispersing warm
or use optional AC power adaptor. and depth of the appliance. air from the ireplace to remote locations in the same
room or other rooms in your home.
9)Testthe pilot (Refer to 'PilotAdjustmenrsection). 3) The HZ40E Direct Vent Gas Fireplace can be
installed in a recessed position or framed out Up to two kits may be installed on the fireplace.
10) TestGas Pressure (Referto"Gas Pipe Pressure into the room as in A. B. C and D.
Testing" section). See Diagram 1. Please Note: Only 1 HeatWave kit may be oper-
ated at one lime. This includes the internal blower
11) Install standard and optional features. Refer to option as well.
the following sections:
a) Glass Crystals/ Optional Ceramic
TET A
alltur>"•=1.0
Wave
,"
Stones Heat
b) Optional Firebox Base Pebbles
c) Optional Reflective Panels
d) Optional Fan The HeatWave Duct Kit has different
e) Faceplate clearance andframingrequirements.cbeck
f) Remote Control or Wall Thermostat the HeatWave manual for details.
and 10ft. wire harness.
12) Reinstall installation access panel.
OPTIONAL
13) Final check.
Diagram HEAT RELEASE KIT
Before leaving this unit with the customer, the
installer must ensure that the appliance is firing
A) Flat on Wall
#946-570
correctly and operation fully explained to
customer. B) Flat on Wall Comer
The Heat Release Kit expels warm air from the
C) Recessed into Wall/Alcove
Comer fireplace to the outside of the building. allowing
D)
the fireplace to be operated with less heat entering
the room. The kit may be used on either the left
or right side.
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301428
INSTALLATION
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires Is failure to maintain required clearances (air space)to combustible materials. It is of the greatest importance
that this fireplace and vent system be Installed only in accordance with these Instructions.
Caution Requirements WARNING
The top. back and sides of the fireplace are defined by Fire hazard Is an extreme risk
standoffs. The metal ends of the standoff may NOT be if these clearances (air space) to combustible materials are not
recessed into combustible construction. adhered to. It is of greatest importance that this fireplace and vent
system be installed only in accordance with these instructions.
iwites.•
r The HeatWave Duct Kit and the Heat
ife Release Kit have different clearance
Clearance: Dimension Measured From: S and framing requirements. check the
HeetWaveand Heat Release manual
A: Mantel Height (min.)
B: Sidewall (on one side)
1T (330mm) Top of Fireplace Opening
lint Release MI for details.
8' :203mm: Side of Fireplace Opening
Flue Clearances to Combustibles
C: Ceiling
(room and/or alcove) Horizontal Top 3"
22" (559mm) Top of Fireplace Opening
Horiztonal . Side 2"
D: Mantel Depth (max.) 1r (330mm) 22" Above Fireplace Opening Horiztonal • Bottom
E: Alcove Width 844 (2134mm) Sidewall to Sidewall (Minimum) Vertical
F: Alcove Depth 36' (914mm) Front to Back Wall (Maximum) Passing through wall.
G: From Floor 27' (686mm) Top of Fireplace Opening floor/ceiling when F 1 2"
Note: 0" No hearth required firestop is used.
Installed close
to ceiling.
E
Alcove
r Regency Horizon"' HZ40E Gas Fireplace
EFTA00301429
INSTALLATION
MANTEL CLEARANCES
Due to the extreme heat this fireplace emits, the 14 12 10 8 6 4 2 0
mantel clearances are critical. Combustible mantel
clearances from top of front facing are shown in the ll l l l l l t l l t l l l
diagram on the right. 26-
Note: Ensure the paintthat Is used on the mantel Combustible Material
and the facing is"high quality" orthe paint
may discolour. 20 -
Metal Stud
(On Edge)
1" (25mm)
Facing
22"(559mm) Non-combustible
10-
-
17 Standoff
4
0
To Unit
Base 2T
Top of
Fireplace
Opening
MANTEL LEG CLEARANCES
Combustible mantel leg clearances as per diagram:
5-11/16"(144mm
Non-Combustible
Allowable mantel
legp rojection
Regency Norizonm 14240E Gas Fireplace
EFTA00301430
INSTALLATION
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The nailing Strips must be correctly positioned and attached before unit is
slid into position.
NAILING STRIPS
The nailing strips come attached to the unit. There is 1 plate on each side.
on the top. There also two on the bottom.
The top and side nailing strips are secured to the framing. The bottom
nailing strips are
IMPORTANT NOTE
Framing depth measurement is noted with the nailing strips
set as far forward on the firebox as possible. The nailing
strips can be adjusted back up to 1-1/24 to allow for varying
thicknesses in noncombustible material & wall finishes.
INSTALLATION ACCESS PANEL
The unit is equipped vMh a removable access panel for pre-finish installation
of optional components this panel is located on the lower front face.
1) Remove lower front face nailing strips (2 screws per nailing strip).
2) Remove 8 screws to remove access panel.
3) Easier access to gas connection with panel removed.
4) Install any optional components with access panel removed.
5) Reinstall access panel with B screws and lower front face nailing strips
(2 screws per strip) - prior to installing any facing material
Note: Access panel is no longer usable once fadng material installed.
Installation Access Panel
FRONT FACE NAILING STRIP Lower front nailing strips
INSTALLATION
Required when the combined facingilinishing material is 112'.
If using material which is thicker than 1/2'. the nailing strips are not
required and should be removed and discarded.
1) The 5 front nailing strips are only used if the facing/finishing material
is a combined 1/2' in thickness. This enables the fadng and finishing
materials to be securely fastened to a solid surface.
2) Follow instructions on non-combustible facing installation for pre-
drilling holes prior to attaching the noncombustible material supplied
with this unit.
3) The sidettop nailing strips which are attached to this unit will also need
to be adjusted. See Framing and finishing in this manual.
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301431
INSTALLATION
FRAMING DIMENSIONS
Framing
Description HZ40E IME
DimensiOnS
Framing Height 42' (1067mm)
B EMMIIML_ taa
C1 Horizontal Vent 19-7116' (495mm)
Framing Depth* C2 Vertical Vent 23-7/16" (596mm)
Vertical rise -terminating horizontal
1) Minim
Coiner Wall Depth 57-18" (1457mm)
Comer
G Vent Centerline Height 36 - (921mm)
Nona 1r (432m01)
Gas Connection Opening Height 2" 151mm)
J Gas CSE 4 - 3/16" (106mm) -- al
K Gas Connection Inset 8. 5116' (211mm)
L Gas Connection Opening Width a2" (89mm)
* Framing depth measu Omani is noted with the nailing strips set as far forward on the firebox as possible.
The nailing ships can be adjusted back up to 1- to allow for varying thicknesses in non-combustible
material & wall finishes.
Note: Al other framing may
be of wood construction.
Regency Hodzonm FiZ40E Gas Fireplace
EFTA00301432
INSTALLATION
NON-COMBUSTIBLE REQUIREMENTS
AI three pieces (top. 2 sides) are now supplied to meet the non combustible requirements. Previously only the top was supplied
Metal Stud (header)
51.5116' (1303mm) on edge
Calcium silicate board is a high • grade material Metal Stud g ►, Metal Stud
• • A
with cement. quartz. natural and selected
•
minerals as the main raw materials. It is widely
used for partitions and ceilings in buildings.
It is fire proof and earthquake proof.
II finishing the wall above the unit with materials
such as tile, brick, marble. etc. non-combustible •
board available from the building supply store g
can be used. nE
;TA
Note: Calcium Silicate is 1/2' thick
•
10'
(252=1)
el In
5-11/16-
(144mm)
NON-COMBUSTIBLE FACING INSTALLATION
Caution: The noncombustible board supplied with this unit can
be damaged if dropped or struck. Handle with care.
1'
1) Using drywall screws • secure non combustible material
around unit, framing and top nailing strip every 6 inches.
Important Note: To avoid cracking the board • pre-drill holes prior to
securing to unit/ framing.
2) Wipe any debris/dust from the non combustible
material and drywall.
3) Prior to taping and mudding it is highly recommended
to prime the facing using a quality primer. This will gen.'s...Ana bawd
seised vein um.
ensure proper adhesion of both the tape and mud.
The supplied board is very porous.
Non combusIblie board
4) Tape the seams using a mesh type tape. Apnea v41b unt
5) Mud seams as normal. We recommend using a
product called Durabond high strength compound • for the first coat.
This product can be found at any hardware store.
Mud must be cured as per manufacturers recommendations.
6) Prime wall for a second time for proper adhesion of paint
7) Paint walls using a high quality paint which will withstand
the high temperatures being emitted from this appliance.
14:0 combust/So loud
MUS1 BE PRIMED.
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301433
INSTALLATION
FRAMING & FINISHING
1) Frame in the enclosure for the unit with framing material. 5) If material such as brick, stone. etc extends past the faceplate depth (1.112-).
when finishing around the faceplate, the minimum opening dimensions noted
IMPORTANT: The framed opening must be of non-combustible below must be adhered to ensuring for the removal of the faceplate and for
material. the safe operation of this appliance.
Note: When constructing the framed opening, please ensure there
NOTE: Spacing of 1" around the completed surround must be adhered to.
Is access to Install the gas lines when the unit is Installed.
2) For exterior walls, insulate the enclosure to the same degree as the
rest of the house, apply vapour barrier and drywall. as per local instal- 52.31C I
lation codes. (Do not Insulate the fireplace Itself.)
WARNING: Failure to insulate and add vapor barriers to the inside
of the exterior wall will result in operational and performance
problems including, but not limited to: excessive condensation
on glass doors, poor flame package, carbon, blue flames etc. if
These are not product related issues.
3) The unit does not have to be completely enclosed in a chase. You
must maintain clearances from the vent to combustible materials: See is.
"Clearances" section. Combustible materials can be laid against the
side and back standoffs and the stove base.
Unit shown with 4 piece faceplate
4) Noncombustible material (ie. tile, slate. etc) may be brought upto and
overlap the unit (top and bottom) ensuring that the maximum thickness
does not go beyond the 1.112" as shown in the diagram below. The
faceplate will not be able to be mounted if finished material is beyond 47- .1115-
1-1/Y.
1-'4" (38mm)
Nailing Strip
Edge of __
flange on
fireplace Unit shown with inner and outer door frame
E LTT i_
I
I .
39-13/16" IL
1/2" required
between faceplate • to
+ finished wall eb
1:W (38mm)
IMPORTANT: 112" gap required between faceplate and finished wall when
Unit shown with inner door frame only
using 4 pee. Faceplate (Part # 256.924, 256.926, 256.927)
Regency Norlzonm 14240E Gas Fireplace
EFTA00301434
INSTALLATION
FRAMING & FINISHING
1/2" 1"
Nailing Strip
1' Forward
Unit
Nailing Strip
/12 " Forward
Note:
Depending on the material used for finishing, the nailing
strips must be set accordingly so that the finished material
Unit is always at the 1.1/2' edge of the flange.
3" (flush)
` —Nailing Strip
Flush w/unit
Factory Set
NON-COMBUSTIBLE REQUIREMENTS
Metal Stud (header)
51-5/15' (1303mm) on edge
I 1 4 ► Metal Stud
A •
•
E
33.13416• (859mni)
V
ZO?
E
CAn
10'
(252mm) May be combustible (ie. 1/2"dryw
5-11/16"
(144mm)
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301435
INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
BITI0RINO110
Vent Termination Q Air Suppry Owlet E Area whet* terminal a nol perrritted
Minimum Clearance Requirements Canada' USA2
A Clearance above grade. veranda. porch. deck. or balcony 12130cm) 12130cm)
8 Clearance to window or door that may be opened 12130cm) cr (23crn)
C Clearance to permanently closed window '
0 Vertical clearance to ventdated soffit located above the ternwial within a horizontal distance of 2 feet (6Icm) 19148cm) 19148cm)
from the center Ike of the terminal (check with the local code)
E Clearance to unventiLated soffit 19148cm) 19 '(48cm)
F Clearance to outside corner: with AstroCap Termination Cap. 7118cm) 7118cm)
Clearance to outside corner: with all other approved Termination Caps. 13133cm) 13133cm)
G Clearance to inside corner: with AstroCap Termination Cap 7118cm) 71113cm)
Clearance to inside corner: with all other approved Termination Caps. 13133cm) 13133cm)
H Clearance to each side of center line extended above metedregulator assembly 36190cmr
J Clearance to service regulator vent outlet 36'(90cm) '
K Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance 12130cm) r (23cm)
L Clearance to a mechanical air supply inlet #3' (91cm) above if withal 10' (3rn) horizontally. 7211.8m) 36•(90cn)e
fA Clearance above paved sidewalk or a paved drweway located on public property 84 12.1m)! '
N Clearance under veranda, porch. deck. or balcony 12130cm), '
' In accordance with current CSA 8149.1. Natural Gas and Propane Installation Code
2 In accordance with the current ANSI Z223. liNFPA 54. Nat,onal Fuel Gas Code
+A vent shall not terrneste directly above a sklewak or paved driveway which is located between two single family dwellings and serves both dwellings
$ Permitted only if veranda. porch, deck. or balcony S fully open on a minimum of two sides beneath the floor
• Clearance in accordance with local installation codes and the requirements of the gas supplier
a 3 feet (91cm) within a height of 15 feet (4.5m) above the meter 1regulator assembly
b 3 feet (91cm) above - it within 10 feet (3m) horizontally
Regency Hertz:mini I4Z40E Gas Fireplace
EFTA00301436
INSTALLATION
4" X 6-5/8" RIGID PIPE
CROSS REFERENCE CHART ONLY
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
Oescriptien Simpson SeIldrk American Metal Meial-Fabm SecurRy ICC Excel
Owed Wm pia Direst Terrr ProductsID Sure Seel Secure-Vent Med
AmOtIvial Died
8 Pipe Length-Galvanized 460VA-06 401-6 WA 406 SV4L6 TC-4DL6
8 Pipe Length-Black 460VA-069 40T-65 WA 4065 SV4L86 TC-40L6B
7- Pipe Length-Galvanized N/A WA 407 WA WA WA
7- Pipe Length-Week WA WA 4075 WA WA N/A
9" Pipe Length-Galvanized 46DVA-09 40T-9 WA WA WA WA
9" Pipe Length-Week 460VA-095 4DT.95 WA WA WA N/A
12' Plpe Length-Galvanized 46DVA-12 40T-12 4012 4012 SV4L12 TC-40L1
I2- Pipe Lengui-Black 460VA-125 40T-125 40125 40125 SV4L812 TC-II)Liti
18' Pipe Length-Galvanized 46DVA-18 407-18 4018 4018 SV4LA TC-40L18
1W Pipe Length-Black 46DVA-18B 40T-185 40185 40185 SV4LA TC-4DL 18B
24' Pipe Length-Galvanized 48WA-24 401-24 4024 4020 SV4L24 TC-40L2
24' Pipe Length-Black 460VA.245 401.245 40245 40245 SV4L524 TC-40L2B
36' Pipe Length-Galvanized 480VA-36 40T-36 4036 4036 5V4138 TC-40L3
36' Pipe Length-Black 46DVA-365 401-366 40366 40365 SV4L536 TC-40L36
48' Pipe Length-Galvanized 480VA-48 40T-48 0048 4048 SV4L48 TC-40L4
4W Pipe Length-Black 46DVA-486 401-48B 40486 40485 SV4L548 TC-40L46
60' Pipe Length-Galvanized 48WA-60 40T-60 WA N/A WA N/A
EC Pipe Length-Black 460VA-606 401-60B N/A WA WA WA
Adjustable Length 7 -IT-Galvanized WA WA N/A 4DAL WA TC-ODLT
Adustabte Length T.I 0' -Black WA WA WA 4DAL5 WA TC.4DLTB
Adjustable Length T -Galvanized WA WA 4D7A WA WA N/A
Adusiable Length T'-Black WA WA 407AB WA WA NA
Extension PO 8-1/t-Galvanized 460VA-08A WA N/A WA WA N/A
Extension Pipe El-VT -Black 46DVA-OBAB WA N/A WA WA NA
Adjustable Length It -Galvanized WA WA 4012A WA SVOLA12 N/A
Ackosiable Length 12'-Slack WA WA 4012A WA SV4L5Al2 NA
Extensko Pipe 16*-GaNailzed 460VA-16A WA N/A WA WA NIA
Extension Pipe 16'-Black 46DVA-I6AB WA WA WA WA WA
45' El3ow-Galvantzed 46DVA-E45 407-EL45 4045L WA N/A TE-40E45
45' Wbow-5lack 460VA.E456 401-EL455 40T-EL45B VA WA TE-40E458
45' Elbow Swivel-Galvanized See 460VA-E45 N/A WA 41345L SV4E45 WA
45' Ebow Swwel.Black See 46DVA.E45B WA WA 4045L5 SV4EB45 WA
90' Elbow-Galvanized 460VA-E90 401-EL9OS 40TEL9OS N/A N/A TE-40E90
90' Ebow-Black 460VA.E936 40T-EL90S5 40T-EL90S5 WA SV4EBR90.1 TE-40E90B
90' Elbow. SwIvel.Galvantzed See 460VA-E90 N/A WA 40901. SV4E90-1 WA
90' Elbow. Swivel.Black See 46DVA.E9OB WA WA 4090L5 SV4E690-1 WA
90' Starter Elbow. Swivel-Gab/awed N/A N/A WA 4090A N/A WA
Adaptor' WA WA WA 4090L WA WA
Ceiling Support WA 407-CS 4DFSP 40SP SV4SD 7E-4DE45
Cathedtal Support Box 46DVA-CS 40T-CSS 401156 40RS SV4CSB TE-41)E4515
Wal Support/Band 46DVA-WS 407-WS1B 4DWS 4DWS SV4BM WA
Ofiset Support 46CP/A.ES (MA . FPI) 40T-OS NSA WA SV4SU WA
Wal Thanble-Black 46DVA-WT 407-WT 40W7 40W1 SV4FISM 7E-4DE90
Wal Trimble Suppcit/Ceiling Supped., 460VA•DC WA NSA NA SV4PF TE-40E90B
Areal* Spacer 46DVA-FS 407-FS 4DFSP 4DFS SV4BF _ WA —
Trim Pate-Back WA 4DT-TP 4DEPB 40CP SV4LA WA
C Regency Horizon"' HZ40E Gas Fireplace
EFTA00301437
INSTALLATION
Description Simpson Selldrk American Metal Metal-Fatd" Security ICC Excel
Deceived Pro* Direct Temp" Products:ID suet Sod Secure-Were Circa
Arnehwer Oita
Attc NtolatKin She 2' 46CNA.IS MAO FPI NrA 4DAIS12 WA SV4RSA TA
Attic Insulation Shield - Cold °khakis 36" N/A N/A ODAIS12 N/A N/A TM-4AS
Basic Horizontal Termination Kit (A) Disc. 4DT.HKA 4DHTK2 4W-1'MA SV-SHK NA
Horizontal Termination Kit (B) 46DVA-KMA 401-ZIKB 4DHTK1 4DHTI(B SV-HK HA
tOwind mai:fent;
Vencal Terminatim Kil Ds. 4C.T.oKC 4DHTK fo:r7K SlbFK NA
High Wind Verlical Cap 46DVA-VCH WA WA Ni'. WA TM-4VT
nigh Wird Horizontal Cap 46DVA.HC NA TA TVACHT
Horizontal Square Termination Cap See 46DVA-HC 4DT-HiSC 4DHC 4DHT SV4CHC-I TA-4MT
Vented Termination Cap 461YVA.vC 4DT.FP/C 4DVC 4DVT SV4CGV.I TM-4V7
Storm Collar 46DVA-08A 4DT-SC 4DSC 4DSC SV4FC TA-SC
Adjustable Flashing OM 24212 460VA-F6 4DT-ST t4 40125 405114 SV4STCI4 TF-4FA
Adjustable Mashing 6/12-12/12 46DVA-FLA 4DT-ST36 4D355 4DST36 SV4STC38 TF-4F0
Vinyl &ding Standen 46DVA.VSS 4DT-VS NrA 4DVS SV4VS PA-VSS
Vinyl Siding Shield Plate N/A 4DT-VSP N/A WA SV4VS N/A
Snorkel Termination 14' 46DVA.SNKL TA WA IFA NIA T.4-43714
Snorkel Termination 36- N/A NIA WA WA WA 114-4S138
Redick!' Disk NA NA NR WA TA TM-4DS
Extended Vertical Termination Cap WA WA N/A NM WA N/A
Chimney Corweision Kt A (USA only) 46DVA.KCA Ni WA NrA TA TM-4CA6
Chimney Conversion Ki B (USA only) 46DVA-KCB WA N/A NIA WA T.4-4CA7
Chimney Corrmesion 10 C (USA only) 46DVA.KCC Na NrA WA NIA PARCAE,
Chimney Conversion Kt Masonry 46DVA10.4C WA WA NIA WA N/A
(USA only)
Wal Fireslop 46DVA.V/FS Na NrA WA NIA TM-SIR
Cando Flex Connectors 46DVARDF WA NfA N/A WA WA
FPI
946-506P Vary Guard (Optimal) for AstroCap 948-206 Vinyl Siding Shield for Riser VeM Terminal
510.994 Rigid Pipe Adaptor (Must use with all rig° piping) 946-200P Vent Guard (Opting Ice Riser Vent Terminal
640-530:P Mae( Vent Terminal 948-523V AstroCap Horizontal Cap
946-605 Starter Calm Increaser C x 8-6/V to 5' x 8' 946.206 Vinyl Siding Standoff for AstroCap
Note: When using Metal-Fab Site Seal Rigid Piping - please note that the Adaptor (400A) must be used in ccojundko wkh FPI Rigid Pipe Adaptor (510-994).
Offset Pipe Selection: Use this table to determine offset pipe lengths.
Pipe Length V x 6.5TVenting For SpOCille insItuctions on venting °deponents - visit the
0-) manulaclurers ivebsite ISIS below.
RLYI (X) Kee CY)
0- (0mm) 4-718- (124mm) 13-7/8' (340mm) .L / Simpson Direct Vent Pro:
6" (152tivn) V (933mm) 16-1/2- (419twn) Selkirk Direct-Temp:
/ Y
9' (229mre) 10-L8- (257mm) 18-5/8" (473mm) / / I American Metal Predicts
12- (3116mm) 12-1/C (3l 1mm) 20-3/4- (527mm) I ' I I Metal-Fab Sure Seal:
24' (610mm) 20-5V (524mm) 29-1/8" (74Ornm) I Se:Andy Secure Vent.
— '
36- (914mm) 29- (737mm) 37-112- (953mm) I i Industrial Chimney Company:
48' ( I 21ginvn) 37-7/16' (951mm) 45-15116' i1167mm) X
Note: Horizontal Leis DI vent must be love. or have a VC rise or every 1 fool of tort towards the letmimtlo
Never anew the vent to MIdCwaws d - this could CALM high temperatures and may present a posstl fire hazard.
Regency Horizon"' 14240E Gas Fireplace
EFTA00301438
INSTALLATION
VENT RESTRICTOR POSITION
Vent restriction is required for certain venting installations. see the diagrams in the "Venting
Arrangements' section to determine if they are required for your installation.
The Vent Restrictor plate is located on the inside top of the firebox.
To set the vent restriction as indicated in the venting arrangements diagrams, refer to the following instructions:
1) Remove the glass door - see instructions in this manual.
2) Remove the screws that hold the vent restrictor plate in place.
3) Adjust the vent restrictor plate to the required vent restrictor position as per the diagrams shown.
4) Once the vent restrictor plate is in the required position, secure with screws.
3.000 2000 1500 1.000
u—kria-u
I
Set 0 Set 1 Set 2 Set 3
(Factory set) VENT RESTRICTOR VENT RESTRICTOR VENT RESTRICTOR
VENT RESTRICTOR AT 2' AT 1.1/2' AT 1"
AT 3'
C
Regency HorlzonTM HZ40E Gas Fireplace
EFTA00301439
INSTALLATION
VENTING INTRODUCTION
The HZ40E uses the "balanced flue' technology Co-Axial system. The inner liner vents products of combustion to the outside while the outer liner draws
outside combustion air into the combustion chamber thereby eliminating theneed louse heatedroom air for combustion and losing warm room air upthechimney.
Note: These flue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel
or gas burning appliance. Each direct vent gas appliance must use its own separate vent system. Common vent systems are prohibited.
VENTING ARRANGEMENT FOR HORIZONTAL TERMINATIONS
The diagram shows all allowable combinations of vertical runs with horizontal terminations. using one 90° (two 45°elbows equal one 90° elbow). (Not including
the starting 45 elbow at the flue collar when using rigid venting.)
Note: Must use optional rigid pipe adapter (Part# 510-994) when using Rigid Pipe Venting Systems.
Horizontal (Feet)
0 2 4 6 0 10 12 14 16 18 20
Is I I I ! I I
16
• 14I
Vent Restrictor
on Set 1
a.
0 12
E
0
10
u_
a—
0
.0 6
stu
2— 36.114' (921mm)
Ainimum Height
Recpinnent
>
0 •
VENT RESTRICTOR SETTING:
Vent restrictor lac ory se at Se 0.
Refer to the 'Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 0 to Set 1 if required.
Note: For horizontal terminations the Regency Direct Vent Flex System may be used for installations with a maximum continuous vent
length of up to 10 feet. If longer runs are required, rigid pipe must be used.
• Maintain clearances to combustibles as listed in "Clearances" section
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each floor level and whenever passing through a wall.
• A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
• Flex system can only be used up to 10 feet - otherwise rigid venting must be used.
Regency Horizonw HZ40E Gas Fireplace
EFTA00301440
INSTALLATION
HORIZONTAL TERMINATIONS
FLEX VENT 4" X 6-7/8"
These venting systems. in combination with the HZ40E Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by Warnock
Hersey/ Intertek. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in 'Exterior Vent Termination
Locations" section.
Regency. Direct Vent (Flex) System Termination Kits includes all the parts needed to install the 14240E using a flexible vent.
FPI Kit # Length Contains:
#946-513 2 Feet 1) 6.7/8" flexible outer liner (Kit length)
2) 4' flexible inner liner (Kit length)
3) spring spacers
4) thimble
#946-515 4 Feel 5) AstroCap termination cap
6) screws
7) tube of Mill Pac
8) plated screws
#946-516 10 Feet
9) S.S. screws #8 x 1.1/2' drill point
Notes:
1) Liner sections should be continuous without any
Joints or seams.
2) Only Flex pipe purchased from Regency" may be
used for Flex installations
3) Horizontal vent must be supported every 3 feet.
4) Regency"Direct Vent System (Flex)Isonlyapproved
for horizontal terminations.
5) Flex system can only be used up to a maximum
continuous vent length of up to 10 feet. If longer
runs are required, rigid pipe must be used.
Vent Guard
(Part #946-506/P)
Wall Thimble
AstroCar
4" dia. flue pipe Termination Cap
6-7/8" (Part# 946-523/P)
173mm) .5,
dia. Flue pipe spring spacer
22
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301441
INSTALLATION
HORIZONTAL TERMINATIONS
RIGID PIPE 4" X 6-5/8"
The minimum components required for a basic horizontal
termination are:
1 Horizontal Termination Cap
1 45° Elbow
1 Rigid Pipe Adaptor (510-994)
1 Wall Thimble
1 Length of pipe to suit wall thickness
(see chart)
Wall thickness is measured from the back standoffs to the inside
mounting surface of termination cap. For siting other than vinyl
furring strips may be used. instead of the vinyl siding standoff, to
create a level surface to mount the vent terminal. The Terminal
must not be recessed into siding. Measure the wall thickness
including furring strips. Horizontal
Termination Cap
If a Vinyl Siding Standoff is required (it must be used with vin I
siding), measure to outside surface of wall without siding and Vinyl Siding Vent Guard
Standoff (Optional (Part #946-506/
add 2 inches.
r i,",,i i:I I I inhi l ETii .n li
Wall Thickness Vent Length Required
(inches) (inches) all Thimble
4" • 5.1/2' 6'
• Adj.Pipe Length
7" • 8-1/2' 9'
10" - 11.1/2' 12" 4T Elbow
9" - 14-1/2" 11" - 14-5/8' Adj. Pipe Rigid Pipe Adapter
1T - 23-1/2' 1r - 24' Adj. Pipe
WARNING-
Do not combine venting components from
different venting systems.
However use of the the AstroCar and FPI
Riser is acceptable with all systems.
This product has been evaluated by Intertek
for using a Rigid Pipe Adaptor in conjunction
withDuravenl Direct-Vent. Selkirk Direct-Temp.
Ameri Vent Direct Venting, ICC Excel Direct
and Security Secure Vent systems. Use of
these systems with the Rigid Pipe adaptor is
deemed acceptable and does not affect the
Intertek WHI listing of components. When using Rigid Vent other than
Simpson 0ura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
The FPI AstroCapw and FPI Riser Vent terminal are certified for installations using FPI venting systems as well as Simpson Dura-Vent• Direct Vent.
American Metal Products Ameri Vent Direct Vent. Security Secure Venr. ICC Excel. Selkirk Direct-Temp. AstroCari is a proprietary trademark of FPI
Fireplace Products International Ltd. Dura-Vent® and Direct Vent are registered andfor proprietary trademarks of Simpson Dura-Vent Co. Inc.
Regency Horizon"' 14240E Gas Fireplace
EFTA00301442
INSTALLATION
HORIZONTAL TERMINATIONS
RIGID PIPE 4" X 6-5/8"
The diagrams below shows examples of horizontal termination arrangements using one, two. or three 90, ebows (two 45° elbows equal one 90° elbow)
1) A maximum of three 90° elbows are permitted (not Including the starting 45°elbow at the flue collar when using rigid venting).
2) Minimum distance between elbows is 1 ft. (305mm).
• Maintain clearances to combustibles as listed in the "Clearances" section.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each floor level and whenever passing through a wall.
• Must use optional rigid pipe adaptor (Part# 510-994) when using rigid pipe vent systems.
• A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
• Flex system can only be used up to 10 feet - otherwise rigid venting must be used.
Straight Out Horizontal Venting
Diagram 1
center
of hole
•
Please note the minimum centerline for
basic install shown above.
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301443
INSTALLATION
Horizontal Venting with Two (2) 90° Elbows Horizontal Venting with Three (3) 90° Elbows
One elbow = Two 45° elbows. One 90° elbow = Two 45° elbows.
Option V H + H1 Withtheseoptions. maximum Option H V Hatt+H2 With these options.
total pipe length is 28 feet maximum total pipe
A) 1' Min. 3' Max. with minimum of 6 teel total A) 1' Max. 1' Min. 3' Max. length is 28 feet with
minimum of 11 teat
B) 2' Min. 4' Max. vertical and maximum 8 feet B) 2' Max. 3' Min. 5' Max. total vertical and
total horizontal. maximum 9 foet total
C) 3' Min. 5' Max. C) 3' Max. 5' Min. 6' Max. horizontal.
D) 4' Min. 6' Max. Pleese note minimum 1 D) 4' Max. 7' Min. 7' Max.
loot between 90° elbows is Plees, note
E) 5' Min. 7 Max. E) 5' Max. 9' Min. 8' Max. minimum 1 loot
required. between90°elbows
F) 6' Min. 8' Max. F) 6' Max. 11' Min. 9' Max. Is required.
Restrictor Position Set 0 (factor)/ sening) Restrictor Position Set 0 (lactory setting)
H2
Horizontal Venting with Two (2) 90° Elbows
One elbow = Two 45° elbows.
Option H V H4411 With these options,
maximum total pipe
A) 1' Max. 1' Min. 3' Max. Iength Is 28 feet with
minimum of 8 feet total
B) 2' Max. 2' Min. 5' Max. and maximum
8 feet total horizontal.
C) 3' Max. 4' Min. 6' Max.
D) 4' Max. 6' Min. 7' Max. P
pielaosoetnotmin
betwnimg
E) 5' Max. 8' Min. 8' Max. elbows is required.
Restnctor Position - Set 0 (factory setting)
25
Regency Horizon*" HZ40E Gas %oplas°
EFTA00301444
INSTALLATION
Horizontal Venting with Three (3) 90° Elbows
One 90' elbow= Tvo 450 elbows.
Option V H V+V1 H+H1 With !hase options,
maximum total pipe
A) 2' Min. 1' Max. 3' Min. 4' Max. lenath is 28 feet with
B) 3' Min. 2' Max. 4' Min. 5' Max. totalnuvritertlitcatr atenectl
C) 4' Min. 3' Max. 6' Min. 6' Max. mnilail.9 feet total
lriloVizio
D) 5' Min. 4' Max. 8' Min. 7' Max.
Please note
E) 6' Min. 5' Max. 10' Min. 8' Max. minimum I kun
between 90' elbows
F) 7' Min. 6' Max. 12' Min. 9' Max. Is requIred.
Restnctor Position Set 0 (tadog setting)
Regency Horizonn, HZ40E Gas Flreplace
EFTA00301445
INSTALLATION
VERTICAL TERMINATIONS
RIGID PIPE 4" X 6-5/8"
The minimum components required for a basic vertical
termination are:
Vertical Termination Cap
45° Elbow Vertical Terminal
Rigid Pipe Adaptor (510.994)
Ceiling Firestop
Flashing
Storm Collar Storm Collar
Length of pipe to suit wall thickness
(see chart)
Flashing
Galvanized pipe is desirable above the roofline due to its higher
corrosion resistance. Continue to add pipe sections through the
flashing until the height of the vent cap meets the minimum height
requirements specified in Dia.4 or local codes. Note that for steep Ceiling Firestop
roof pitches. thevertical height must be increased. A poor draft, or
down drafting can result from high wind conditions near big trees
or adjoining roof lines. in these cases, increasing the vent height
may solve the problem.
Pipe Length
Roof Pitch Minimum Vent Heigh
Feet Meters Rigid Pipe Adapter
flat to 7112 2 0.61
over 7/12 to 8/12 2 0.61
over 8112 to 9/12 2 0.61
over 9/12 to 10/12 2.5 0.76
over 10/12 to 11/12 3.25 0.99
over 11/12 to 12/12 4 1.22
over 12/12 to 14112 5 1.52
over 14/12 to 16/12 6 1.83
over 16,12 to 18/12 7 2.13
over 18,12 to 20/12 7.5 2.29
over 20/12 to 21/12 8 2.44
WARNING.
Do not combine venting components from different venting systems.
However use of the the AstroCapw and FPI Riser is acceptable with all systems.
This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction
with Duravent Direct-Vent. Selkirk Direct-Temp.Ameri Vent Direct Venting.ICC ExcelDirect
and Security Secure Vent systems. Use of these systems with the Rigid Pipe adaptor is When using Rigid Vent other than
deemed acceptable and does not affect the Intenek WHI listing of components. Simpson Dura-Vent. 3 screws must be
used to secure rigid pipe to adaptor.
The FPI AstroCar and FPI Riser Vent terminal are certified for installations using FPI venting systems as well as Simpson Dura•VenP Direct Vent.
American Metal Products Amen Vent Direct Vent. Security Secure Ventt. ICC Excel. Selkirk Direct-Temp. AstroCap1° is a proprietary trademark of FPI
Fireplace Products International Ltd. Oura-Vent and Direct Venl are registered and/or proprietary trademarks of Simpson Oura.Vent Co. Inc.
Regency Horizon,'" HZ40E Gas Fireplace
EFTA00301446
INSTALLATION H
VENTING ARRANGEMENT FOR VERTICAL TERMINATIONS
Vertical Venting with One(1) 90° Elbows (1 - 90° 2 - 45°)
Horizontal (Feet)
Theshadedareainthediagramshowsallallowablecombinations
a a a el 11
of straight vertical and offset to vertical terminations, using one
90° elbow, with Rigid Pipe Venting Systems.
I I I I i t
Two 45° elbows equal to one 90° elbow. not including the a- A
starting 45° elbow at the flue collar.
33
Vent must be supported at offsets.
Minimum distance between elbows is 1 ft. (305mm).
Maintain clearances to combustibles as listed In the
"Clearances" section. E
Horizontal vent must be supported every 3 feet. m—
Firestops are required at each floor level and whenever
passing through a wall.
Vert Rosinaor on
Must use optional rigid pipe adaptor (Part# 510.994)
when using rigid pipe vent systems.
Refer to the "Vent Restrictor Position" section for
details on how to change the vent restrictor from the
factory setting of Set 0 to Set 1 or Set 2 if required.
Vett Rostrictor on Sot 2
ff
14
a—
Vent Rosinclor on Set I
a—
iazt,_
I —
4—I
I—
2—
a
M.
M. IC tat (cialerine lo conk**
Maim." @Nad ppe
between elbass 12'(306m n(
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301447
INSTALLATION
VERTICAL TERMINATION
WITH CO-LINEAR FLEX SYSTEM
THE APPLIANCE MUST NOT BE Masonrychimneys may takevariouscontourswhichthe flexiblelinerwill accommodate. However.
CONNECTED TO A CHIMNEY FLUE SERV- keep the flexible liner as straight as possible. avoid unnecessary bending.
ING A SEPARATE SOLID FUEL
BURNING APPLIANCE. The Air Intake pipe must be attached to the inlet air collar of the termination cap.
This appliance is designed to be attached to
two 3" (76mm) co-linear aluminium flex running Co-linear DV
the full length of the chimney. See the 'Venting Vertical Termination
Arrangements Vertical Terminations' Section for Cap # 946-529
minimum and maximum heights.
A maximum
Required Parts: of two certified
Part # Description joiner kits
946.529 Co-linear DV Vertical may be used
Termination Cap
948.305 3" Flex 35 ft. per length. Flex Liner
946.563 Co-Axial to Co-LinearAdaptet Kit #948-305
which contains the following: 35ft (11m)
Co-linear Flex Adapter
Outer Pipe
Inner Pipe Adapter
510.994 Rigid Pipe Adaptor
46DVA-E45 450 Elbow
Alternate Approved Caps Exhaust
46DVA-VC Vertical Termination Cap Flue
46DVA-VCH High Wind Cap
46DVA-GK r Co-linear Adapter with flashing
Outer
Pipe
with Kit#
946-563
Air Intake
Pipe Length
N4 Co-Linear
Flex
Rigid Pipe Adapter Adapter
# 510-994 with Kit#
946-563
45° Elbow
Inner Pipe
Adapter
with Kit#
946-563
29
Regency Horizon" HZ40E Gas Fireplace
EFTA00301448
INSTALLATION
VERTICAL TERMINATIONS
RIGID PIPE 4" X 6-5/8"
• Two 450 elbows equal to one 90° elbow. Maximum of four 45° elbows allowed, not including the starting 45°elbow al the flue collar.
• Vent must be supported at offsets.
• Minimum distance between elbows is 1 ft. (305mm).
• Maintain clearances to combustibles as listed in the "Clearances" section.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each floor level and whenever passing through a wall.
• Must use optional rigid pipe adaptor (Part./ 510-994) when using rigid pipe vent systems.
Vertical Venting with Two (2) 90° Elbows Vertical Venting with Two (2) 90° Elbows
One 90' elbow = Two 45° elbows. One 90° elbow = Two 45° elbows.
Option V H V+V1 With these options. Option H + Ht V With theseoptions. maximum
maximum total pipe total pipe length is 30 feet
A) i• min. 4' Max. 2' Min. length is 30 feet with A) 2' Max. Z Min. with minimum of 6 feet total
nl tal vertical and maximum 6 feet
B) 2' Min. 5' Max. 3' Min. vmelil
ii ieaulm 6armtuto
anodfrn m B) 3' Max. a Min- total horizontal.
feel total horizontal.
C) 3' Min. 6' Max. 4' Min. C) 4' Max. 4' Min. Please note minimum I
D) 4' Min. 7' Max. 5' Min. Please note minimum foot between 90° elbows is
I loot between 90° D) 5' Max. 5' Min.
required
E) 5' Min. 8' Max. 6' Min. elbows is required. E) 6' Max. 6' Min.
Restrictor Position Set 0 (factory setting) Restrictor Position Set 0 (factory setting)
For additional vertical venting with
2 x 90° elbows. refer to 'Rigid Pipe
Venting Arrangements" Section.
30
Regency Horizon*" HZ40E Gas Fireplace
EFTA00301449
INSTALLATION
Vertical Venting with Three (3) 90° Elbows
One 90° elbow = Two 45° elbows.
Option H V H + H1 V + V1 With these options. max. total
A) t• Max. t• Mm. .5 Max. I .5 min. pipe length is 30 feet with min.
B) 2' Max. 2' Min. 4' Max. I 5' Min. of 11 feet total vertical and
C) 3' Max. 3' Min.' 5' Max. 7' Min. max. 7 feet total horizontal.
Please note min. 1 loot
D) 4' Max 4' Min. 61 Max. 9' Min.
b 90, elbows is
E) 5' Max 5' Min. 7 Max. ' 11' Min. required.
etween
Restrictor Position Set 0 (factory setting)
Vertical Venting with Three (3) 90° Elbows
One 90, elbow= Two 45, elbows.
Option V H + H1 V + V1 withthese options, max. total
A) Z Min. 3' Max. 4' Min. pipe length is 30feet with min.
B) 3' Min. 4' Max. 6' Min. of 10 feet total vertical and
max. 8 feet total horizontal.
-- CF. 4. Mm. 5' Max. 7' Min. Please note min. 1 loot
D) 5' Min. 6' Max. 8' Min. between 90° elbows Is
E) 6' Min. 7' Max. 9' Min. required.
F) 7' MunriMax. 10' Min
Resuictor Position - Set 0 (factory setting)
Regency Horlzonm 11240E Gas Fireplace
EFTA00301450
INSTALLATION
VENTING ARRANGEMENTS - VERTICAL TERMINATIONS
with Co-linear Flex System for both
Residential & Manufactured Homes
into Masonry Fireplaces
35—
35
CV
1
O
Ven Restrictor
Vent Restrictor Set 2
Set 2
•
•
Vent Restrictor Set 1
35' (10.7m) Max.
Vertical Height (feet)
2
Vertical Height (fe
0
x
8
Combined max. of 16' M
2
Vent Resbictof Set 1
E
Cl
r to
0
C •
E E
•
E E
IF ao
• lV
• •
A
--EE
7OS g
I 1 1 II I I I I I I I
Horizontal Distance (Feet) Horizontal Distance (Feet)
Horizontal Distance (Feet)
The shaded area in the diagrams show
the allowable vertical terminations when
using two- 3" co-linear aluminium flex
and 4 x 6-5)8" rigid pipe.
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301451
INSTALLATION
5) Assemble the desired combination of pipe and
UNIT INSTALLATION elbows to the appliance adaptor and twist-lock
7) Ensurethat the pipe clearances to combustible
materials are maintained (Diagram 5). Install
WITH HORIZONTAL for a solid connection. the termination cap.
TERMINATION Note: if installing termination on a vinyl siding
4" X 6-5/8" Note: Forbestresultsandoptimumperfonnance covered wall, a vinyl siding standoff or
VENTING with each approved venting system, it is furring strips must be used to ensure
highly recommended to apply "Mill-Pac•" that the termination is not recessed into
(Rigid Vent Systems) the siding.
sealant (supplied) to every Inner pipe
Minimum Vent Clearances connection. Failure to do so may result
to Combustibles in drafting or performance issues not Siding
covered under warranty. Silicone (red apply sealant
' Clearances noted below must be maintained: RTV) is optional. to all four sides
except when passing through a wall. ceiling of al the bolt Horizontal
termination where the use of a firestop or wall thimble — 4— Top to Vinyl Standoff
reduces clearance to 1 -112' (38mm). Horizontal runs of vent must be supported every
Horizontal Top' 3" (76mm)' 3 feet (0.9meter). Wall straps are available for
this purpose.
Horizontal Side 2 " (51mm)
Horizontal Bottom 2" (51mm) 6) Mark thevanforasquare hole.-see chart to left
for size. The center of the square hole should
Vertical Vent 2" (51mm) line upwith the center•lineof the horizontal pipe.
Below are the recommended framing dimensions Cut and frame the square hole in the exterior screws
(inside measurements) for the 4" x 6-5/8' wall where the vent will be terminated. See Vinyl siding standoff
rigid vent terminations - for use with a firestop or diagram 2 for center line requirements. Wall Thimble
wall thimble. (required)
If the wall being penetrated is constructed of
Recommended Framed Opening non-combustible material, i.e. masonry block Diagram 5
or concrete, an 8" (203mm) diameter hole is
Size
acceptable. The four wood screws provided should be
Vent Size Framing Size replaced with appropriate fasteners for stucco.
Note: brick, concrete, or other types of sidings.
ri" z 6 - 5/8' 10' x 10'
a) The horizontal run of vent must be level, or
have a 1/4 inch rise for every 1 foot of run 8) Beforeconnectingthehorizontal runof vent pipe
Install the vent system according to the
towards the termination. Never allow the to the vent termination, slide the Wall Thimble
manufacturers instructions included with the
vent to run downward. This could cause over the vent pipe. The wall thimble is required
components.
high temperatures and may present the for all horizontal terminations.
1) Set the unit in its desired location. Check to possibility of a fire.
determine if wall studs or roof rafters are in 9) Slide the appliance and vent assembly towards
the way when the venting system is attached. b) The location of the horizontal vent the wall carefully inserting the vent pipe into the
If this is the case, you may want to adjust the termination on an exterior wall must meet vent cap assembly. It is important that the vent
locationof theunit. Rough in the gas preferably all local and national building codes, pipe extends into the vent cap sufficient6stance
on the right side of the unit and the electrical so as to result in a minimum pipe overlap of
(junction block is on the left side) on the left. 1-1/4 inches (32mm). Secure the connection
2) Direct Vent pipe and fittings are designed with between the vent pipe and the vent cap.
special twist-lock connections to connect the
venting system to the appliance flue outlet. A 10) install wall thimble in the center of the framed
twist•lock appliance adaptor is required. hole and attach with wood screws (Diagram 7).
3) In conjunction with theApproved Vent system.
install the adaptor after the unit is set in its
desired location. Put abeadof high temperature
silicone inside the outer section of the adapter
and a bead of Mill Pack on the inner collar. Slip
the adapter over the existing inner and outer
flue collar. Fasten to the outer collar only with
the 3 supplied screws (drilling pilot holes will
make this easier).
4) Level the fireplace and fasten it to the framing Diagram 2
using nails or screws through the top and side
nailing strips. Diagram 7
Female
SE Locking
• Lugs
Pease>
Male
Lugs
Diagram I
Regency Horizon" HZ40E Gas Fireplace a
EFTA00301452
INSTALLATION
UNIT INSTALLATION NOTE: Horizontal sections must be supported ASTROCAP
at Intervals not exceeding 3 feet (0.9 DIMENSIONS (91W5231P)
WITH HORIZONTAL meter).(Flame picture and performance
will be affected by sags In the liner).
TERMINATION
4" X 6-518" 4) Separate the 2 halves of the wall thimble and
VENTING securely fasten the one with the tabs to the
outside wall making sure that the labs are on
(Flex Vent Systems) top and bottom. Fasten the other thimble half
Minimum Vent Clearances to the inside wall. The thimble halves slip inside
each other and can be &gusted for 2 x 4 or 2
to Combustibles x 6 walls.
• Clearances noted below must be maintained:
except when passing through a wall. ceiling or at the 5) Slip the assembled liner and termination
termination where the use of a frestop or wall thimble assembly through the thimble making sure the
reduces clearance to v. (25mm). termination cap faces up (there are markings
on the cap indicating which way is up). This
Horizontal Tor 3" (76mm)" will position the termination cap with proper
Horizontal Side 2 " (51mm) down slope for draining water. Fasten the cap
to the outer wall with the 4 supplied screws.
Horizontal Bottom 2" (51mm)
Vertical Vent 2" (51mm) 6) Pull the centre inner and outer Ilex liner out
enough to slip over the flue collars of the
Below are the recommended framing dimensions fireplace. (You may wish tocutthe liner shorter
(inside measurements) or the 4" x 6.5/8" rigid to make it more workable.) Do not bend liner
vent terminations - for use with a firestop or wall more than 90'. The liners must slip over the
thimble. collars a minimum of 14/8".
Recommended Framed Opening
Size 7) Apply Mill Pac over the fireplace inner flue
collar and slip the inner flex liner down over it
Vent Size Framing Size and attach with 3 supplied screws.
e x 6 - 5/8' 10" x 10'
8) Do the same with the outer flue collar and outer
flex liner.
1) Locate the unit in the framing, rough in the gas
(preferably on the right side of the unit). Locate 9) Apply a bead of silicone between the thimble
the centerline of the termination and mark wall and termination and around the outer edge of
accordingly. Cut an square hole in the wall - see the terminal al the wall in order to keep the
chart (inside dimension). water out.
Note: If Installing termination on a airline coy- IMPORTANT:Donotlocate terminationhood
gyed wall. a vinyl sidina standoff or vinyl where excessive snow or ice buildup may
1111011811llizamustlausgsltoensure that occur. Be sure to check vent termination
the termination is not recessed into the
area after snow falls. and cleat to prevent
siding.
accidentalblockage of ventingsystem. When
using snow blowers, make sure snow is not
directed towards vent termination area.
Termination
Screws 4" (102mm) dia. flue pipe
Cap
(3 per ly with spring spacer
connection) N 4. r
2) Level the fireplace and fasten it to the framing
using nails or screws through the nailing strips. 1 II
3) Assemble the vent assembly by applying Mill
Pacto the inner flue collarof thelermination and 6-7/8" (173mm) Screws
slipping the inner flex liner over it at least 1.3/8" dia. air intake
(4 per
(35mm). Fasten with the 3 screws (drilling pilot
connection)
holes will make this easier). Apply Mill Pac or Wall Thimble 2 pieces
high temperature silicone to the outer flex pipe (10" (254mm
and slip it over the outer flue collar of the vent Outer Diameter)
terminal at least 1.3/8"(35mm) and fasten with
the 3 screws.
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301453
INSTALLATION
UNIT INSTALLATION 4) Assemble the desired lengths of pipe and
elbows. Ensure that all pipes and elbow con-
WITH VERTICAL nections are in the fully twist-locked position
and sealed.
TERMINATION Female
4" X 6-518" VENTING Locking
Lugs
(Rigid Vent Systems)
cgke.coll
s
Male Diagram 4
Locking
Lugs
1) Maintain the 1.172" clearances (air spaces) to Roof Pitch Minimum Vent Height
combustibles when passing through ceilings,
walls, roofs, enclosures, attic rafter, or other Feet Meters
NOTE: For best results and optimum perform-
nearby combustible surfaces. Do not pack ance with each approved venting system, It is flat to 7/12 2 0.61
air spaces with insulation. 4IFF highly recommended to apply"Mill-Pac" sealant
Check 'Venting' Sections for TI (supplied) toevery Inner pipeconnectlon. Failure
over 7/12 to 8/12 2 0.61
the maximum vertical rise of the to do so may result In drafting or performance over 8/12 to 9/12 2 0.61
venting system and themaximum Issues not covered under warranty.Silicone(red
horizontal offset limitations. over 9/12 to 10112 2.5 0.76
RTV) is optional.
over 10/12 to 11/12 3.25 0.99
2) Set the gas appliance in its
desired location. Drop a plumb 5) Cut a hole in the roof centered on the small over 11/12 to 12/12 4 1.22
bob down from the ceiling to the drilled hole placed in the roof in Step 2. The hole over 12/12 to 14/12 5 1.52
position of the appliance flue should be of sufficient size to meet theminimum
exit, and mark thelocation where requirements for clearance to combustibles over 14/12 to 16/12 6 1.83
the vent will penetrate the of 1.1/2'. Slip the flashing under the shingles over 16/12 to 18/12 7 2.13
ceiling. Drill a small hole (shingles should overlap half the flashing) as
at this point. Next, drop a per Diagram 3. over 18/12 to 20/12 7.5 2.29
plumb bob from the roof to over 2(1/12 to 21/12 8 2.44
the hole previously drilled
in the ceiling. and mark the DiegiaM 1 7) Ensure vent is vertical and secure the base of
spot where the vent will penet ate the roof the flashing to the roof with roofing rails, slide
storm collar over the pipe section and seal with
3) A Firestop spacer must be installed in the floor a mastic.
or ceiling of every level. To install the Firestop 8) Install the vertical termination cap by twist-
spacer in a flat ceiling or wall, cut a 10 inch locking it.
square hole. Frame the hole as shown in
Diagram 2 and install the firestop. Note: Any closets or storage spaces. which the
vent passes through must be enclosed.
Note: All vertical terminations are vented Diagram 3: TheupperhalfMho flashingisinstalled
using 4" x 6-5/8" venting and rigid pipe under the roofing material and not nailed down
adaptor #510-994. until the chimney is installed. This allows for small
adjustments.
6) Continue to assemble pipe lengths.
11Y(254nun)
souare hole —1\
framing
Note: II an offset is necessary in the attic to
avoid obstructions, it is important to
support the vent pipe every 3 feet. to
firestop avoid excessive stress on the elbows.
spacer and possible separation. Wall straps
are available for this purpose.
Galvanized pipe is desirable above the moans
Diagram 2 due to its higher corrosion resistance. Continue
to add pipe sections through the flashing until the
height of the vent cap meets theminimum height
requirements specified in Dia. 4 or local codes.
Note that for steep roof pitches, the vertical
height must be increased. Apoorctraftordown
drafting can result from high wind conditions
near big trees or adjoining roof lines, in these
cases, increasing the vent height may solve
the problem.
Regency Horizonm 14240E Gas Fireplace
EFTA00301454
INSTALLATION
HZ40E-NG1 SYSTEM DATA
PILOT ADJUSTMENT 880 S.I.T. VALVE
Min. Supply 5" WC (1.25 kpa)
Periodically cheek the pilot flames. Correct flame
DESCRIPTION
Pressure
pattern has two strong blue flames: 1 flowing
Manifold Pressure 3.5" WC (0.87 kpa) around the flame sensor and 1 flowing across
the burner (it does not have to be touching the 1) Pilot adjustment
Orifice Size 440 DMS 2) Outlet Pressure Tap
burner).
Maximum Input 26,000 Btu'h 3) Inlet Pressure Tap
(7.61 kW) Burner o o 000 00 00 4) Pilot Outlet
000oo001t000oo00 5) Main Gas Outlet
Minimum Input 18,000 Btu/h
6) Main Gas Inlet
(5.28 KW) Flame Sensor
HZ40E-LP1 SYSTEM DATA 2
Min. Supply Pressure 11" WC (2.73 kpa)
Manifold Pressure 10" WC (2.49 kpa) Pilot Ignitor
Orifice Size 453 DMS
Maximum Input 25.500 Btuth Note: If you have an Incorrect flame pattern,
(7.47 kW) contact your Regency' dealerfor further
Instructions.
Minimum Input 21.000 Btuth
(6.15 KW) Incorrect flame pattern will have small, probably
yellow flames, not coming into proper contact
with the rear burner or flame sensor.
HIGH ELEVATION
GAS PIPE PRESSURE
This unit is approved for altitude 01o4500 ft. (CAN.'
2.17-M91). TESTING
The appliance must be isolated from the gas sup.
ply piping system by closing its individual manual
GAS LINE shutoff valve during any pressure testing of the
INSTALLATION gas supply piping system at test pressures equal
to or less than 1/2 psig. (3.45 kPa). Disconnect
piping from valve at pressures over 112 psig.
Since some municipalities have additional local
codes it is always best to consult with your local The manifold pressure is controlled by a regulator
authorities and the CAN/CGA 8149 installation built into the gas control, and should be checked
code. at the pressure test point.
For USA installations follow local codes and/or the Note: To properly check gas pressure, both
current National Fuel Gas Code. ANSI Z223.1. inlet and manifold pressures should be
checked using the valve pressure ports
When using copper or flex connectors use only
approved fittings. Always provide a union so that
on the valve. AERATION ADJUSTMENT
gas lines can be easily disconnected for servicing. 1) Make sure the unit is in the "OFF' position.
Flare nuts for copper lines and flex connectors are The burner aeration is factory set but may need
usually considered to meet this requirement. 2) Loosen the 'IN" and/or "our pressure tap(s). adjusting due to either the local gas supply or
turning counterclockwise with a altitude. Open the air shutter for a blue flame or
NOTE: A shutoff / dante valve should be sup- 118" wide flat screwdriver. close for a more yellow flame.
plied in or near the unit (or as per local codes)
for ease of servicing this appliance. 3) Attach manometerto*IN"androCOUT pressure Minimum Air Shutter Opening:
tap(s) using a 5116" ID hose.
IMPORTANT: Always cheek for gas leaks with NG I/8"
a soap and water solution or gas leak detector. 4) Turn the unit on with the remote or wall switch LP
Do not use open flame for leak testing.
5) The pressure check should be carried out with Note: Any damage due to carboning resulting
theunit burning and 'besetting should be within from improperly setting the aeration
the limits specified on the safety label. controls is NOTcovered under warranty.
6) When finished reading manometer. turn off
the unit. disconnect the hose and tighten the
screw (clockwise) with a 118' flat screwdriver.
Note:Screw shouldbe snug. but do not over
tighten.
0 Regency Horizon"' HZ40E Gas Fireplace
EFTA00301455
INSTALLATION
AC POWER ADAPTOR INSTALLATION (FOR SUREFIRE SYSTEMS)
An optional AC power adaptor may be Installed as a constant power source for the SureFire system.
IMPORTANT: Recommend removing the 4-AA batteries in the SureFire receiver.
This will avoid battery leakage and power drainage. 4-AA Battery pack may be reinstalled into receiver during power outages.
NOTE: For all Gas Fireplaces 120 volt power must be brought to the receptacle box inside the bottom of the firebox (provided with the unit).
All Freestanding Gas Stoves & Gas Inserts will need a receptacle box located outside near the unit
so that the AC Power Adaptor can be plugged in.
INSTALL AC ADAPTOR WITH SUREFIRE WALL RECEIVER SWITCH ONLY - (WITHOUT REMOTE)
1) Locate -DC Supply" tag on wire harness. For location in unit 2) Connect the male end from AC adaptor to the female end
see remote installation page in owners manual. tagged -DC Supply" on wiring harness in unit.
3) Plug AC adaptor into 120V wall outlet (or into 120V receptacle if
installed inside the gas fireplace firebox).
4) Neatly tuck any loose AC Power Adaptor wires neatly underneath /
inside the appliance.
Note: Ensure that wires do not touch the underside of the firebox
(keep wires away from the heat as much as possible).
INSTALL AC ADAPTOR WITH SUREFIRE PROFLAME GT / GTM REMOTE
1) Connect the male end of the AC adaptor to the female end of the 3) Plug in wire adaptor to FCM COM connector - be careful not
wire adaptor (supplied with AC adaptor) together as shown . to damage ends. This only fits one way.
Wire adaptor AC adaptor AC adaptor FCM - COM
wire adaptor
2) Locate FCM COM connector on the Remote wire harness -
see manual for location in unit. 4) Plug AC adaptor into 120V wall outlet (or into 120V receptacle if
installed inside the gas fireplace firebox).
5) Neatly tuck any loose AC Power Adaptor wires neatly underneath /
inside the appliance.
Note: Ensure that wires do not touch the underside of the firebox
(keep wires away from the heat as much as possible).
FCM -COM
Regency Horizon'" HZ40E Gas Fireplace
EFTA00301456
INSTALLATION
WIRING DIAGRAM
This heater does not require a 120V A.C. supply for operation. In case of a power failure. the burner switch and the optional remote control/thermostat will
continue to operate. However. a 120V A.C. power supply is needed for the taniblower operation.
(Do not cut the ground terminal off under any circumstances.)
NOTE: Even if the fan Is not purchased with the unit, it Is still a good Idea to bring power to the receptacle box (provided with the unit) in case the
Ian Is Installed at a later date.
PROFLAME SYSTEM GT
IMIralnal•
885 POW. Sworn
Coregurabon
886 GMT
%Ste Daarem
Swarms"' Swtth
0.564 302
Pradess INC Beard
Optional AC Adaptor
0.6setitt2
VC Wee Hsenees Ammar
0.564.860 s(das. Piot Gym a CHOI Setts
High Temperature 1125E )
AMC Power A00004
PROFLAME SYSTEM GTM
Wear Clicirtel•
-E4.1E , M# 5
Proterne System
Corisstraters
885611AF
wre Dasgrats
MILE-
StreFtre". Switch
- •
Prcasgrealerd
Optional AC Adaptor
I 0 554 9/ 2
ae VIre Harress Cr
0.564.8.50 0ncluclors %a CA-4 CRAM Swath)
High Temperature (HST)
AGOG Power Ad40 44
CAUTION: Label all wires priori° disconnection Caution: Ensure that the wires do not touch any
when servicing controls. Wiring errors can cause hot surfaces and are away from sharp edges.
improper and dangerous operation.
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301457
NSTALLATION
PROFLAME SYSTEM GTMF WITH OPTIONAL FAN
Sera Electrode
--Fa4=90: )
Proflame System
Configuration
885 GTMF
Wye Diagram
%SASSO Mon
SureForems Switch tr—riti
P 0 0 DIO
O a0
0564.1 I
Fan °card Module
0.584.523
0584.
doere
Prc8ame DFZD2
0.584.905
GTMFS Vilna Meows.
0.584.912
DFC Wire HarnessAssembly
(Includes Plot Gin0 8 CPUIPI Switch)
®a Ground I
is
Fan
Neutral Black White
L Black
Live 'Green
120V AC Ground _
60 Hz
Black Black
Fan Thermodisc
(normally open)
Caution: Ensure that the wires do not touch any
hot surfaces and are away from sharp edges.
CAUTION: Label all wires priorto disconnection
when servicing controls. Wiring errors can cause
improper and dangerous operation.
Regency Hodzonm 14241)E Gas Fireplace
EFTA00301458
INSTALLATION
OPTIONAL FAN WIRING DIAGRAM
WITHOUT PROFLAME GTMF SYSTEM
Lockwasher
Star washer Ground
#8 Ground Lug
(for mobile home)
Fan
Neutral Black White
Black
Live "Green
120VAC Ground
60 Hz
0
Black Black Red
Fan Fan Thermodisc
ground wire (normally open)
L
Electrical Connection Alternative Scheme "A",
Power at Stove Electrical Connection Alternative Scheme "B",
Power at Switch
Wall Junction Box
`Speed Control Wall Junction Box
• Switch with ----- - - - -
'Speed Control
Wire Nuts lead wires
Switch with lead wires
(Regency)
Wire Nuts
14 AWG wire Black (Hot) Black
120 Volts WhiteiNesitraiL
60 Hz CCalittGt0urAL__,_ + __ S P - 14 AWG wire
'Wire Ciampi
Wire
•_ S,mpndiii,1
till
Ill
*Receptacle Box
inside stove 'Wire
'Receptacle Clamp111
*Receptacle Box
(dedicated use inside stove
by stove fan only) • = supplied with fan kit
Other parts are to be supplied
by electrician or installer
Copper Ground) 'Receptacle
120 Volts White Deutra11_, (dedicated use
60 Hz by unit Ian only)
BlackjHot)___
14 AWG wire
Caution: Ensure that the wires do not touch any
hot surfaces and are away from sharp edges.
CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can cause
improper and dangerous operation.
40
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301459
INSTALLATION
Optional RECEIVER WALL SWITCH
(Included with Unit)
REMOTE CONTROL
1) Run the supplied 10' of the wire harness through the right or left side gas
inlet opening- connect the ONIOFF wire harness. Be careful not todamage
Use the Regency' Remote Control approved for this unit. Use of other systems wire.
may void your warranty.
2) Choose a convenient location on the wall to install the receiver and the
The remote control comes with a hand held transmitter. receptacle box (protection from extreme heat is very important). Run wires
from the fireplace to that location.
*Profiame GT remote control 946-700
RF remote. ONIOFF Thermostat. ON/OFF Flame Control 3) Connect the wire to the receiver wall switch and install into the low voltage
Large blue backlit LCD screen with temperature display receiver. receptacle box.
'Proflame GTM remote control 946-701.
RF remote. ONIOFF Thermostat. ON/OFF Flame Control
Large blue backlit LCD screen with temperature display receiver.
nProflame GTMF remote control 946.702.
RF remote. ONIOFF Thermostat. ON/OFF Flame Control
ON,OFF fan control with 3-stage adjustment. Requires a fan (if not included).
to be installed for fan function to operate.
'Must also chose one of the following which enables the flame to be turned
down using the remote control:
'Modulator Surefire NG 946.693
'Modulator Surefire LP 946-694
Large blue backlit LCD screen with temperature display receiver.
Regency Horizon"' HZ40E Gas Fireplace gal
EFTA00301460
INSTALLATION
WALL MOUNT ON / OFF SWITCH AND BATTERY COMPARTMENT INSTALLATION
AND/OR RECEIVER INSTALLATION
REQUIRED FOR ALL INSTALLATIONS - INCLUDING PROFLAME REMOTE CONTROLS
JMPORTANT INSTAII ATION NOTE.
The Receiver must be placed inside the supplied (Low Voltage)
junction type wall box and installed into the wall only.
DO NOT INSTALL WITHIN THE CONFINES OF THE FIREPLACE.
Remote Receiver Installation
1. Install the low voltage junction box to the framing, at desired location within 10 ft. from fireplace.
2. Feed the 12 pin connector through the opening at back of junction box.
3. Connect the 12 pin connector to the back of the receiver.
4. Install the Receiver in the Low Voltage Junction box.
5. Insert the 4 AA type batteries in the battery compartment with the correct polarity.
6. Place the slider into the cover plate.
7. Put the Receiver switch in the "OFF position, to allow correct lineup for slider switch.
8. Make sure the Receiver and cover plate words `OW and "Ur are on the same side.
9. Align the slider with the switch on the Receiver and couple the switch into the slider.
10. Align the screw holes.
11. Using the two (2) screws provided secure the cover plate to the Receiver.
Low Voltage Junction Box
Optional Proflame Receiver
J-Box
Slider Switch Receiver
"1449// Plate
Rumples WA Plant
10 ft. wire harness with
12 pin connector
Diagram 1
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301461
INSTALLATION
GTMF REMOTE INSTALLATION
120 VoltAC power is needed for the fan. The fan can be hard wired if desired. INTO EXISTING INSTALLATIONS
The receptacle box should be Installed on the right hand side of the unit
by a qualified electrician. The neutral (wider) slot of the polarized receptacle 1) Shut off the gas and power supply to the unit.
should be at the top.
2) Remove the faceplate or door frame - see instruction in manual.
Unit must be grounded at all times. Do not cut the ground terminal off
under any circumstances. 3) Remove the glass door.
Note: Follow instructions below -if unit has not yet been installed -otherwise a) Remove the 3 screws shown below at the bottom of the glass
skip to existing installtions section.
door.
1) Remove 8 screws to remove front access panel. b) Swing the door out 45° from the bottom and lift up and out.
2) Remove 2 top screws and loosen 2 bottom screwsto remove side access
panel.
4) Remove the inner panels - reverse of 'Inner panel installation' in the
installation manual.
5) Remove the burner tray cover by lifting up and out as shown below.
3) Install fan control module (FCM) into bracket on the Inside of the panel.
plug the (FCM) into the outlet in the unit - reinstall the panel with 4 screws
from step 2. T
• Prior to removing burner - remove crystals, pebbles, spa stones and inner
panels - if installed.
4) Proceed to Step 11.
Regency Horizon"' HZ4OE Gas Fireplace a
EFTA00301462
INSTALLATION
8) Once the top panel is removed - the left side panel will be accessible.
5) Loosen 2 screws at the back of the burner to release it. Remove 3 screws from the left side access panel In locations shown
below.
Note: Some components have been removed for illustration purposes.
6) Remove the burner by sliding it to the right - then lift out.
9) Install the fan control module (FCM) through the opening created by the
removed loft side access panel.
7) Remove the left access plate by removing 8 screws - see locations below.
Left side access
10) Install the fan control module (FCM) into the bracket as shown below.
0 Regency Horizon"' HZ40E Gas Fireplace
EFTA00301463
INSTALLATION
11) Locate the digital firebox control box.
12) Plug the fan power cord Into the fan control module in the outlet marked
fan. Plug in the FCM wire (from the digital firebox control box wire har-
ness) into the location on the fan control module marked com
13) See Proflame remote instructions for coding remote to receiver as well
as operating instructions.
14) Reverse steps 2-1 for new installations.
Reverse steps 8 - 1 for existing installations.
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301464
INSTALLATION
OPTIONAL FAN INSTALLATION
120 Volt AC power is needed for the fan switch and blower. The fan can be 5) Connect one of the black wire to the Black wires from the power cord.
hard wired if desired. The receptacle box should be installed on the left (light blue connector). Connect the other end to one spade on the ther-
hand side of the unit by a qualified electrician. The neutral (wider) slot of the modisc.
polarized receptacle should be at the top.
6) Connect the red wire end to the other open spade one the thermodisc.
Unit must be grounded at all times. Do not cut the ground terminal off Connect the other end of the red wire to the black wire from the fan motor.
under any circumstances.
7) Connect the white wire from the fan motor to the black wire on the power
Follow these instructions before the initial installation into the framing. If cord.(dark blue connector).
installing the optional fan into an exiting installation • follow instructions on
the next two pages.
1) Remove lower front face nailing strips (2 screws per nailing strip).
8) Slide in the thermodisc to the clip in the location shown below.
2) Remove 8 screws to remove front access panel.
Thermodisc dip
9) Secure the ground wire from the fan assembly, also secure the ground
wire from the power cord to the stud on the back left near the fan.
3) Slide the fan assembly through the front access panel • slide all the way
back to the back of the two tabs.
10) Plug the fan into the receptacle located in the lower left front corner at
Tabs
the base of the unit.
NOTE: If installing the fan with a GTMF remote • please see GTMF remote
instructions in the manual.
4) Secure the fan to the floor of the unit with 2 screws. in locations show
below. TO REMOVE THE FAN
1) Turn the power off.
2) Reverse the above instructions.
Maintenance: The sealed bearings are lubricated, there is no need to lu-
bricate them further. (Extra lubricant will cause more lint and dust buildup
- causing the bearings to prematurely fail).
Regular cleaning and vacuuming of the fan area will add to the life of the
motor.
IMPORTANT:
ese fans collect a lot of dust from within your home. Ensure you
maintain these fan motors on a regular basis by vacuuming
he fan blades and housing using a soft brush nozzle.
a Regency HorlzonTM HZ40E Gas Fireplace
EFTA00301465
INSTALLATION
OPTIONAL FAN INSTALLATION - INTO EXISTING INSTALLATIONS
120 Volt AC power is needed for the fan switch and blower. The fan can be 7) Loosen 3 screws at the back of the bumer to release it.
hard wired if desired. The receptacle box should be installed on the left
hand side of the unit by a qualified electrician. The neutral (wider) slot of the
polarized receptacle should be at the top (see page 41 for wiring diagram).
Unit must be grounded at all times. Do not cut the ground terminal off
under any circumstances.
1) Shut off the gas and power supply to the unit.
3) Remove the faceplate or door frame by lifting it up oft the glass door.
— 1_ I
'Cl
8) Remove the bumer by sliding it to the right - then lift out.
Glass Door
Faceplate
(4pc style
shown)
4) Remove the glass door.
a) Remove the 3 screws shown below at the bottom of the glass
door.
b) Swing the door out 45° from the bottom and lift up and out.
9) Remove the left access plate by undoing the 8 screws - see locations
below.
5) Remove the inner panels - reverse of inner panel Installation' in the
installation manual.
Location of screws on access plate
6) Remove the burner tray cover by lifting up and out as shown below.
10) Remove the left access plate by undoing the 8 screws - see locations
below.
• Prior to removing bumer - remove crystals, pebbles, spa stones and Inner
panels - if installed.
Regency Horizon*" HZ40E Gas Fireplace
EFTA00301466
INSTALLATION
10) Maneouver fan through left access panel opening.
11) To complete fan Installation - follow steps 2- 7 on previous page.
NOTE: The right access panel wasremoved to allow easier access to secure
the right screw on the fan base.
12) Reverse steps 9-1 to complete install.
C Regency Horizon"' HZ40E Gas Fireplace
EFTA00301467
INSTALLATION
INNER PANEL INSTALLATION
Handling Instructions 7) Install the loll side enamel panel • secure in position with the panel
clip and two tighten two screws loosened in step 2, as shown in the
Black Enamel Panels diagram below.
• Black Enamel panels must be inspected for watches and
dimples prior to installation. All claims to be recorded at this time.
Claims for damage after installation will not receive consideration.
• Black Enamel panels will discolor a little during normal operation.
This is normal and should not be considered a defect.
* Al hand and finger marks MUST be cleaned off with a soft cloth.
Use an ammonia based cleaner (ie. glass cleaner) to remove any
fingerprints before applying heat to the unit.
Failure to do this will result in bum stain on panels which you
will be unable to remove. Not protected by product warranty.
1) Remove the faceplate and glass door it already installed • see
manual for instructions.
2) Remove 4 screws to remove top heat deflector.
8) Install the right side enamel panel - secure in position with the panel
dip and two screws loosened in step 4.
3) Remove installed factory panels.
Loosen 2 screws (do not remove) on panel clip securing side panel.
Slide panel dip down away from screws.
Remove side panel. 9) Reinstall heat deflector.
10) Reinstall glass door • reinstall faceplate.
I— MI
panel clap
4) Repeat on opposite side.
5) Remove back panel.
6) Install the back enamel panel first. Tilt the panel lanyard • position
the bottom of the panel first. Use care not to scratch or mar the panel
on the pilot shield.
Final /naafi
Regency HorizonTM HZ40E Gas Fireplace LI
EFTA00301468
INSTALLATION
GLASS CRYSTALS OR OPTIONAL CERAMIC STONES
INSTALLATION ON BURNER
Evenly spread the Glass Crystals or optional Ceramic Spa Stones or Volcanic Stones over the burner. Ensure the crystals (or stones) do not
ovedap too much as this wi effect the flame pattern.
IMPORTANT NOTE:
Onlythe supplied approved Glass Crystals and Ceramic Spa/lava Stones are to be used with these fireplaces. Use of any other type of glass crystals
or stones can alter the tilts performance. any damage caused by the use of any unapproved glass or stones will not be covered under warranty.
When using Ceramic Spa/ Lava Stones DO NOT cover burner ports or riot light that lead to pilot flame. Ensure the crystals or stones do not overlap
excessively as this will effect the flame pattern.
BURNER PACKAGES
Unit •Glass Crystals Ceramic Spa / Volcanic Stones
HZ54E 1HZ54EPV 3 lbs 1 lb Glass + 2 packages (140 spa stones)
HZ42 / I4Z42E I HZ40E 2 lbs I lb Gass • 1 package (70 spa stones)
HZ42ST / HZ42STE 2 lbs 1 lb Glass + 1 package (70 spa stones)
HZ42STEPV
HZ30E •• 1lb I lb Glass + 1 package (70 spa stones)••
HZI234E ••• 3141b 3/4 ti Glass + 1 package 70 spa stones)•••
HZI390E/ HZ1390EB • 7 lbs (4 lbs burner + 3 lbs firebox) 2 lb Glass + 1 package (70 spa stones) / 2 lb Glass + 1package (volcanic stones)
HZI540EB • 8 Ds [4 lbs burner + 4 lbs firebox] 21b Glass +1package (70 spa stones)/ 2lb Glass + 1package (volcanic stones)
HZO424-1ZO42 (AUS) 3 lbs Not Approved
L6765 1lb 1 package = (70 spa stones)
P33S1233SE •— 1lbs I package = (70 spa stones)—
PTO3r/ Plateau Series 10 Ds Not Approved
PTO60- 20 lbs Not Approved
U32S / U32SE 1lb 1 package = (70 spa stones)
E335 1 lb I package = (70 spa stones)
NOTE: • Glass Crystals are available in llb and 5Ib bags. All units come standard with Cobalt Blue glass crystals except:
• HZO42 comes with Copper glass crystals.
• HZI390E. HZI390EB. HZ1540EB. PTO30. PTO60 8 Plateau Series do NOT include glass crystals with units. Must purchase separately.
• 1 Ceramic Spa stone package contains 70 stones.
Recommended - use only 40 of the 70 ceramic stones on the HZ30E burner.
Recommended - use only 24 of the 70 ceramic stones on the HZ1234E burner.
•••• Recommended - use orgy 50 of the 70 ceramic stones on the P33S/P33SE burner.
-1Zelitgra'terillififtralltallisam•
Glass Crystals shown on Burner
Optional Ceramic Spa Stones + Glass Crystals shown on burner.
For Units HZ54E. HZ54EPV. HZ42ST. HZ42STE. HZ42STEPV. For Units HZ54E. HZ54EPV. HZ42ST. HZ42STE. HZ42STEPV.
HZ1234E. HZ42E. HZ42. HZ40E. HZ30E.
HZ1234E. HZ42. HZ42E. HZ40E. HZ30E only
HZO42. HZO42 (AUS) P7O30. PT060 Plateau Series only
Glass Crystals shown on Burner Optional Ceramic Spa Stones shown on burner.
For units P33.S. P33SE. L676S. U328. U32SE. E33S only For units P33aP33SE L676S. U325. U32SE. E33S only
111
Glass Crystals shown on Burner and Firebox Floor
For Units HZ1.390E. HZI390EB. HZI540EB only
Regency HorlzonTM HZ40E Gas Fireplace
EFTA00301469
INSTALLATION
OPTIONAL PEBBLE / CRYSTAL INSTALLATION
FOR FIREBOX BASE
Firebox (Around Burner) Packages
Unit Glass Crystals Pebbles
HZ54E / HZS4EPV 6 lbs 2 packages (6 x bags pebbles)
H242/ HZ42E / H240E 5 les 2 packages (6 x bags pebbles)
HZ42817H242STEMZ42STEPV 5 lbs 2 package (6 x bags pebbles)
HZ30E 2 les I package (3 x bags pebbtes)
HZI540EB 4 lbs 1.5 packages (4 x bags pebbles)
HZI390e HZI300ES 3 les I package (3 x bags pebbtes)
HZI234E 2 lbs 1package (3 x bags pebbles)
82042 / HZ042 (AUS) 3 les I package (3 x bags pebtores)
P335 / P33SE 3 lbs I package (3 x bags pebbles)
U32S I U32SE 3 les 1 package (3 x bags pebbles)
E338 3 lbs I package (3 x bags pebbles)
There are 2 optional packages to choose from to cover the firebox base:
1) Natural River Pebbles
2) Glass Crystals (4 colors available)
Spread the pebbles ? crystals evenly on the exposed base of the firebox. Pebbles are Hat to be placed anywhere on the burner or over top of the
Glass Crystals or optional Ceramic Spa Stones.
IMPORTANT NOTE: Cray the supplied and approved pebbles/glass crystals are to be used with these fireplaces. Use of any other type of pebbles.
glass crystals or other material can create a danger and will void the warranty.
Natural River Pebbles shown surrounding the a Horizon Burner
River Pebbles shown surrounding a Sunrise Burner Glass Crystals shown surrounding the Burner
Regency Horizonm 14240E Gas Fireplace
EFTA00301470
INSTALLATION
GLASS DOOR INSTALLATION
The glass door comes with a black frame. 2) With the door in proper position • secure with 2 screws in locations shown
1) To install the frame and glass door, simply hook the top door flange onto in Diagram 3.
the top of the unit and swing the door towards the unit, Diagram 1.
Note: Be careful that the glass gasket does not roll up: there must be a gap
between the gasket and the door lip to ensure that the door sits
securely on the unit. See Diagram 2.
Diagram 3
3) Install cover plates over each screw with 2 magnets each as shown below.
Magnet
Cover Plate Diagram 4
Hook top of
door onto
top flange
Flush
Door
Cover Plates Installed
Flush Diagram 5
Door Incorrect
Gasket:
Glass doubled
Gasket up, filling
Correct gap.
Door/Glass/Gasket
Installation. Diagram 2
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301471
INSTALLATION
OPTIONAL MESH GLASS GUARD
3) Install mesh screen. flush side facing out.
1) Remove left side and right side door frame screws.
4) Install left side and right side top mountng dips approximately 3' from
each side.
NOTE: Clips should line up with the edge of the outer edge of the glass
door flange - see glass door nstall for illustration.
2) Using existing door frame screw, install latrer mesh mounting brackets
on left side and right side. as shown.
Mesh mounting clips
Lower mesh mown ing brackets
5) Install faceplate - refer to faceplate installation instructions in manual.
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301472
INSTALLATION
4 PIECE FACEPLATE INSTALLATION
1) If installing optional mesh glass guard - See °Monet 'Mesh Glass
Guard' installation instructions.
2) Instal brackets onto me back of me faceplate - 3 screws for each
bracket in locations shown below.
Hook bracket over
these tabs
Edge of
3) To instal me 4 pc. faceplate - hook brackets (located on back of Hangs on
faceplate) over the two middle tabs on the glass door frame. fireplace
If thicker finishing materials are used - the faceplate may be
adjusted out - up to lir
1 4 (38mm)
Important: L2' gap required between faceplate and
Wished mai when using part 0256-924. 256-926.256-
927 (4 pc. faceplate).
1 NV?
.1H' Use era notch al bracket
for standard instagetton
Final Instal
Regency HorizonTM HZ40E Gas Fireplace
EFTA00301473
INSTALLATION
INNER AND OUTER DOOR FRAME INSTALLATION
Note: HZ40E only - if instilling optional mesh glass guard -
Bracket in Una
See optional mesh glass guard instruction in the manual.
Tab on Faceplate
1) Install 4 magnets onto 4 comers of glass frame prior to installing
the inner door frame.
2) Install the inner door frame - lit it over the glass door frame.
3) Instal theouterdoorframeto the uni1by hooking the left and right sxle
mounting brackets into the mounting slots at the sale of the firebox
as shown below. It is recommended that you use the first mounting
slot (the one closest to the door frame overlay) out of the 3 so that
the faceplate and door frame overlay are flush with one another.
NOTE: There are 3 mounting slots available. this is toaccommodate
any finishing that protrudes sightly beyond the faceplate.
Pin Note:
CompletoO .nner occr
frame and faceplate
instatfabon
Inner door frame may be installed by itself, or with the outer
door frame.
The outer door frame cannot be installed by itself - if install-
ing the outer door frame - the inner door frame must also be
installed.
918-905a
Fl 1 08124111
Regency Horizon*" HZ40E Gas Fireplace
EFTA00301474
OPERATING INSTRUCTIONS
OPERATING LIGHTING NORMAL OPERATING
INSTRUCTIONS PROCEDURE SOUNDS OF
IMPORTANT GAS APPLIANCES
1) Read and understand these instructionsbefore To ignite or reignite the pilot, you
operating this appliance. It is possible that you will hear some sounds from
must first remove the glass door. your gas appliance. This is perfectly normal due to
2) Check to see that all wiring is correct and the fact that there are various gauges and types
enclosed to prevent possible shock. 1) Press and release on ON:OFF button once of steel used within your appliance. Listed below
on the remote control or ON/OFF switch. are some examples. All are normal operating
3) Check to ensure there are no gas leaks. sounds and should not be considered as defects
in your appliance.
4) Make sure the glass in the glass door frame 2) After approximately 4 seconds the spark
is properly positioned. Never operate the ignition system will spark for 60 seconds to Burner Tray:
appliance with the glass removed. light the main burner. The burner tray is positioned directly under the
burner and is made of a different gauge material
5) Verify that the venting and cap are unobstructed. from the rest of the firebox and body. Therefore, the
3) The unit will turn on.
varying thicknessesof steelwillexpandancicontract
6) The unit should never be turned off, and on at slightly different rates which can cause 'licking'
again without a minimum of a 60 second wait. Note: The first try for Ignition will last approxi- and "cracking' sounds. You should also be aware
mately60seoonds. If thereisnoflame ignition that as there are temperature changes within the
(rectification) the board will stop sparking for unit these sounds will likely re-occur. Again, this is
normal for steel fireboxes.
approximately 35 seconds. After wait time
the board will start second try for ignition Pilot Flame:
FIRST FIRE by sparking for approximately 60 seconds . While the pilot flame is on it can make a very slight
If there is still no positive ignition the board "whisper" sound.
The FIRST FIRE in your heater is part of the paint
curing process. To ensure the paint is properly will go into lock out.
Gas Control Valve:
cured, it is recommended you burn your fireplace As the gas control valve turns ON and OFF, a
for at least four (4) hours the first time. The system will need to be reset as follows: dull clicking sound may be audible, this is normal
operation of a gas regulator or valve.
When first operated. the unit will release an odour
a) Turn the system off using ON/OFF switch
caused by the curing of the paint and the burning Unit Body/Firebox:
off of anyoilsremaining from manufacturing. Smoke or press ON/OFF button • if using optional
Different types and thicknesses of steel will expand
detectors in the house may go off at this time. Open remote.
and contract at different rates resulting in some
a few windows to ventilate the room for a couple of b) After approximately 2 seconds turn on ON/ "cracking" and "ticking' sounds will be heard
hours. The glass may require cleaning. OFF switch or press ON/OFF button if using throughout the cycling process.
optional remote.
NOTE: When the glass is cold and the appliance Blower Thermodlsc:
c) Repeat step 2.
is lit, it may cause condensation and fog When this thermally activatedswitch turns ON it will
the glass. This condensation is normal and create a small "clicking" sound. This is the switch
will disappear in a few minutes as the glass If the appliance will not operate, follow the
instructions "To Turn Off Gas to Appliance" contacts closing and is normal.
heats up. and call your service technician or gas
supplier.
DO NOTATTEMPTTO CLEAN THE GLASS
WHILE IT IS STILL HOT!
DO NOT BURN THE UNIT WITHOUT THE SHUTDOWN
GLASS DOOR IN PLACE.
PROCEDURE
1) Turn the wall mounted switch or remote to
During the first few fires, a white film the "OFF" position.
maydevelop on the glass front as part of
the curing process. The glass should be 2) Press 'OFF' on the remote control.
cleaned after the unit has cooled down
or the film will bake on and become very
difficult to remove. Use a non-abrasive
cleaner and DO NOT ATTEMPT TO
CLEAN THE GLASS WHILE IT IS HOT.
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301475
OPERATING INSTRUCTIONS
COPY OF LIGHTING PLATE INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING -
TIM appllance must be installod In accoedanco MUI bral codes. II any:
Il none. loges th* National Font Cas Code.»al 2223.UNFPA 54. or
Nattmal Cas and Program In/aandien Codes, CSA B141.1
WARNING: II you do not fellow these instructions exactly. a lire er explosion may fezelt
tauzing preparty damage. personal Injury or loss of file. Improper installallen. adjustment.
alterahon. service or maintenance ten cause injury or property dametje. Refer to the ownees
information menuet provided with this appliance. For assistente or additional information
consult a qualilied insteller. service agency or gas supplier.
AVERTISSEMENT. Ouiconque ne respecte pas á la lettre les instructions dans la presente notiee
risquede déclencher u ' ' uneexplosion entrainant des des blessures ega
mort. Une installation. de medification.deserviceou peut provoquer des
blessures ou des dommages ma erwt,. Reportez•vous au menuet u propt ire de rinformation
fournie avec cel :Beparelt. Peur obtenir de raide ou des inlormations supplémentaires tonuller
un installateur geologe. une agente de service ou fournisseur de gaz.
A) ibis ~hamen cpapped vees art IgnOon amme ehichaldenalealy sghis iho o/ol.
Dona sy b fghl dm pk) by eend.
B) BEFORE OPERATING snee MI Rand !he ~erna OM fer EM. Be etre le enne oen s, ge hm,
botaus* tann gis m barut [han alt end Mi soli»on eti box
VMATTOOOIFVOU SNEU. CAS
- Don« bylolittenyezerinee.
• Do not touch Day stetest Mick da nol uso arry phono in das bulding.
• Immedlay ron yo.rgassuppler kon a neighbous necne. Forma dm gas suppedys calruCba,
• II ytYJ om«Mede treur gal Papptet. cal dm fee depeilmeni.
C) De nol zee The apeliVraellanyMel hes been Omkenter Immedady alla ~Wel service
tocImMan to Impact lep opplenen and roplaco arry pan WIM control sysum and any
pas oanird %%Neb bas been underwalor.
G) Cel apentelg aar diaah) bui /gumt eutematiquement le miteuee
No lento pas a voticsno memo
B)AVANT DE FAIRE FONCT1ONNER. renner DR aitar de lapparel pour ~dor am <cc-,
de go. Rasnet erts du ortinchm. cv totoks g« Smit Diorti4dir Ra Oor el peuven:
8.erraiMuler ee niveau du sol.
OUE FARE Si VOUS WOU UNE COEUR DE 43AZ:
• Ne Oe lente( WE
• Ile Molmt i alt m «Item/plm. ne pee MMInsi des Matptmee se Ircvmanl dans le
baansent.
-Appelez nwedialemeni enho toonamm do gat doom un vaan Sumaz les
metageis du reuma em
• S: voos ne panset mitste le legml meur. acetat le ~b°, ene anneks
Cl OM pas col enorm se aØ Ocege aanstorm. MMO parhollomont, Fades irrigator I appatol par un toch.
noen godtfil el real layez Mulo ~Ie di systime de conhOW el lokte commtsle eo. ent 410 plenaire &n I eau
CAUTION: Hot whie in *penden. Do not touch. Severe Burns may result. Due to high surface
ternperatures keep chRdren. clothing and furngure.gasoline and ether liquide hoving flammable
vapors away. Keep burner and control compartment clean. See installation and operating
instructions accompanying appliance.
OPERATING INSTRUCTIONS
STOP! Read the safety information above on Ns label.
ll nam on ØF switch
2) ARM ePflrosirnatelY I timend* Uw spark ignalnal syarm vin *park fa 40 iemands le light Re main
Immer,
3) Re eelt vnll turn on.
Nota: The Rat anemie' Iro Ignition wel last approximatoly 60 seconde.. II teem Is no name [gallon troctillca•
timp th* boardME stop onreine let approMmilety 15 maand,. After INti weitime. Ms board wIll start a
ristend to lor ignition by eparkIng tor appmaimately 60 monde. IV Thee, in elIll no posidve Ignhion ener tnt
second anemel th* board MUI go INC lock out.
Tin system wal nood to be fesol as folkwes (alter goIng Ina lotto.« mode):
a) Tom Cie spleen ofl esing ROOF, crash
Vlag 5 Mnute' to daar out any gas. Tinto smelt lor ges. blote:eng nou Te nov.
Il you smell gas STOMERIJ/ra stop ' In the Satety information above on this label. It you dool smolt gas.
go to the nest slep.
bi Turn on °ROEF match er press ØF button II sang optional ~Me,
c) Unit mil repeat step 2.
It lbo epigram* Mg not opmat*. kaow the instructIons me Tum On Gas to Appllance" and earl your
service technician or ges supPliw
STOP! Lire les consignes de sécurité cidessus sur tette Etiquette
1) Aanwet le bouten OIO OFF
2) Allerdre a seconden. te eysléme produira des 'Onmens pendant 10 secondes abn -
lo Orateur penlaat.
9) les Rammen n'allumeront.
ftsmarque ' Au premier allurnage. le systeme lente jles flanwies pendant 60 secondes Si Fesal
est moutoryx. le system lalt un pause
Co atal al OcoM. systems lento d nouveau
<l e... 'old co pion appeae telededo rectlfkathan.
les dommes en produlsaM des seincodes pendant%
seconden. Si les Rammes ne trallunent Muleta* pan. Ie eyeAéme se mel en mede venomalege.
H fer /dom le réinklelieer en suivant lee *Mee sidesaus Ipour Ie ~mondt«) :
a) beIgnia le systemo en utaisant nntenupteur ON t OFF.
Mende* 5 minute* peur bisser *Rapper toet le gab Puls somt« pons uno *dat do pm. y tempels pees du
plancherli mus ambo une odeur de gat ARReitz, Stayer Mime lam des consigne, de sluret cldeseue
em tall. étiquelle. SI MIS na tantes pas de gas. passes i ritme suivante.
b) Et ralla or le sysame a raldo de l'Internapteur ou do la tatecomnando.
c) L'unatá repelera retort 2.
SI rappere« ne toneonna pas. sundt los Instructions "aow cours le gat a rappe/odb et appel« volro lach.
Mcien mi volte knamleseur de ged.
TO TURN OFF GAS APPLIANCE
1) Turn ott OreOFF svritth
2) tt service is to be pertomwd • you MUM clisconnect power to tact unit hom tb, baeery pack. retor to
manual.
1) Ap1/11yOZ slit le bouten ON1OFF
2) SI Ie bonk* est offottuée. voos dam clabrancter rapperell. W Moed:dos. vok lo manual
POLI' plus de Mails.
DO NOT REMOVE THIS INSTRUCTION PLATE Mt.426.
Regency Horizon"' HZ40E Gas Fireplate
EFTA00301476
MAINTENANCE
MAINTENANCE GLASS GASKET GENERAL VENT
INSTRUCTIONS If the glass gasket requires replacement use a MAINTENANCE
tadpole glass gasket (Part # 936-159).
1) Always turn off the gas and electrical supply Conduct an inspection of the venting system semi-
before cleaning. For relighting. refer to lighting annually. Recommended areasto inspect asfollows:
instructions. Keep the burner and control
compartmentcleanbybrushingandvacuuming
GLASS DOOR 1) Check the Venting System for corrosion in areas
that are exposed to the elements. These will
at least once a year. appear as rust spots or streaks. and in extreme
Your Regency° fireplace is supplied with high
temperature 5mm-Ceramic glass. If your glass cases. holes. These components should be
2) Clean appliance and door with a damp cloth replaced immediately.
requires cleaning, we recommend using an
(never when unit is hot). Never use an abrasive
approved glass cleaner available at all authorized
cleaner. The glass shouId be cleaned with a gas 2) RemovetheCap. and shinea flashlight down the
dealers. Do not use abrasive materials.
fireplace glass cleaner. The glass should be Vent. Remove any bird nests. or other foreign
cleaned when it starts looking cloudy. material.
CAUTION & WARNINGS:
3) The faceplate is finished in a heat resistant 3) Cheddorevidencesofexcessivecondensation.
paint and should only be refinished with heat ' Do not clean when the glass is hot.
such as water droplets forming in the inner
resistant paint. Regency' uses StoveBright ' The use of substitute glass will void all product
warranties. liner, and subsequently dripping out the joints.
Paint Metallic Black #6309. Continuous condensation can cause corrosion
• Care must be taken to avoid breakage of the
of caps. pipe. and fittings. It may be caused
Note: Faceplates and Inner panels made from glass.
by having excessive lateral runs. too many
stalnlesssteelwillnaturallychangecolor • Do not strike or abuse the glass.
elbows, and exterior portions of the system
over time. • Do not operate this fireplace without the glass
front or with a cracked or broken glass front. being exposed to cold weather.
4) Make a periodic check of burner for proper • Weargloves when removing damaged orbtoken
4) Inspect joints. to verity that no pipe sections or
position and condition. Visually check the flame glass.
fittings have been disturbed, and consequently
of theburner periodically. making suretheflames • Replacement of the glass panel(s) should be
loosened.Alsocheck mechanical supports such
are steady: not lifting of floating. If there is a done by a licensed or qualified service per son.
as Wall Straps. or plumbers' tape for rigidity.
problem. call a qualified service person.
GLASS REPLACEMENT
5) The appliance and venting system must be
inspected before use. and at least annually, by In the event that you break your glass by impact.
a qualified field service person. to ensure that purchase your replacement from an authorized
the flow of combustion and ventilation air is not Regency' dealer only.
obstructed.
Replacement neocetamic glass
Note: Never operate the appliance without the (Part # 9403611P) is shipped with gasket.
glass properly secured in place.
6) Do not use this appliance if any part has been
underwater. Immediately call a qualified service
technician to inspect the appliance and to CAUTION: Weargloves when removing
replace any part of the control system and any damaged or broken glass.
gas control which has been under water.
7) In the event this appliance has been serviced
checkthatthevent-airsystem hasbeen properly WARNING: Do not operate the
resealed & reinstalled in accordance with the appliance with the glass panels
manufacturers instructions.
removed, cracked or broken.
8) Verily operation after servicing. Replacement of the glass panels
should be done by a licensed or
qualified service person.
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301477
MAINTENANCE
VALVE ASSEMBLY REPLACEMENT
1
1) Turn the unit off and allow it to cool down to room temperature. 8) Remove the burner by sliding it to the right then lift out.
2) Shut off the gas and power supply to the unit.
3) Remove the faceplate or door frame -see instruction in this manual.
4) Remove the glass door.
a) Remove the 3 screws shown below at the bottom of the glass
door.
b) Swing the door out 45° from the bottom and lift up and out.
9) Remove the valve access plate by undoing the 8 screws - see locations
below.
5) Remove the inner panels - reverse of 'Inner panel Installation' in this
manual.
6) Remove the burner tray cover by lifting up and out as shown below.
' Prior to removing burner - remove crystals. pebbles, spa stones and inner 10) Disconnect the inlet gas line and remove the valve
panels if installed.
Illata.;;;;; r NaiL
11) Replace valve assembly and reverse steps.
7) Remove 3 screws on the bumer to release it - locations shown below.
Regency Horizon*" HZ40E Gas Fireplace
EFTA00301478
PARTS LIST
MAIN ASSEMBLY
Part If Description Part a Description
1 256-038 Frame Door HZ40E 6 911-024 Valve NG 880 SIT IPI
2 940-361/P Glass Neoceram Flush HZ40E 911-025 Valve LP 880 SIT IPI
3 256-039 Bottom Tray HZ40E 7 911-006 Pilot Assembly IPI NG
4 256-525 Burner Assembly NG c/w Cap HZ40E 911-007 Pilot Assembly IPI LP
256-530 Burner Assembly LP c/w Cap HZ40E 8 256-574E/P Valve Assembly HZ40E NG SIT
5 904-345 Orifice #53 LP 256-576E/P Valve Assembly HZ40E LP SIT
904-593 Orifice a40 NG 9 910-157/P Fan Low Speed (Dual Blower)
911-012 Ignition board
911-013 IPI/CPI Switch
Not Shown
60
Regency HorizonTM HZ40E Gas Fireplace
EFTA00301479
PARTS LIST
ACCESSORIES
Pait # Description
10) 316-907 Reflective Stainless Steel Inner Panels
316-908 Black Enamel Inner Panels
11) 256-924 Faceplate Black
256-926 Faceplate Sunset Bronze
256-927 Faceplate Brushed Stainless
256-934 Outer Door Frame Black
256-936 Outer Door Frame Bold
256-947 Outer Door Frame Stainless
256-944 Inner Door Frame Black
256-946 Inner Door Frame Bold
256-947 Inner Door Frame Stainless
946-676 Copper Glass Crystals
946-672 Natural River Pebbles
946-673 White River Pebbles
946-674 Ceramic Spa Stones
11
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301480
NOTES
Regency Horizon"' HZ40E Gas Fireplace
EFTA00301481
WARRANTY
OR FIREPLACE PRODUCTS ('
Regency' Fireplace Products are designed with reliability and simplicity In mind. In addition. our Internal Quality Assurance Team carefully inspects each unit thoroughly
before it leaves our facility. Regency* Fireplace Products is pleased to extend this limits lifetime warranty to the ordained purchaser of a Regency' Product. This warranty is
not transferable.
The Warranty: Limited Lifetime
The combustion chanter. heat exchanger. burner tubesiVans. logs. glass crystals. ceramic spa stones, potties. ea* panels and gold pasting (against defective manufacture only) are
covered under the Limed Warne Warranty for five (5) years for parts and subsidized labour' and pads only thereafter.
Glass is covered for lifetime against thermal breakage only. pans and subsidized labour' for live (5) years and pans only thereafter from date 01purchase.
External casting, surrounds and grills are covered against cracks and warps resultng from manufacturer defects. pans and subsidized labour for three (3) years from the date of purchase
and pads only thereafter.
Special Finishes One year on stainless steel panes. nickel overlays.nickel taceplates. Crushed nickel and antique copper full screens and doors. You can expect some changes ri color
as the product 'ages' with constant heating and cooling. Regency warranties the product for any manufacturing defects on the original product. However. the manufacturers warranty does
not cover changing colors and marks. ie. finger prints. etc applied after the purchase of the product. Damage from the use of abrasive cleaners is not covered by warranty.
Electrical and mechanics components such as blowers. switches. wiring, themiodiscs. Regency° remote controls. spa switches. themvpiles. thermocouples. plot assembly components.
and gas valves are covered for Iwo years pans and one year subsidized labour' from the date of purchase. Blowers and valves replaced under warranty are considered repairs and continue
as if new with appbance. ie. lweNe 112) months from original purchase date ci appliance with a minimum 01 three (3) months coverage from date of replacement.
Regency venting components are covered pans and subsidized labour' for three (3) years from date of purchase.
Simpson Dura-Vent venting conponents (Direct Vent units) are covered by Simpson Dura-Vent Inc. warranty.
Repair/replacement pans purchased by the consumer from Regencye after the original coverage has expired on the unit will carry a 90 day warranty. valid with a receipt only. Any nem
shorn to be defective will be repaired or replaced at our discretion. No labor coverage is included vnth these pans.
Conditions:
Any pan or pads of this unit which in our judgement show evidence of such defects will be repaired or replaced at Regency's option. through an accredited distnbutor or agent provided that
the defective pan be relumed to the distnbutor or agent Transportation Prepaid if requested.
Porcelain£namel - Absolute perfection is either guaranteed nor commercially possible. My chips must be reported and inspected by an authorized dealer within three days of instalation.
Reported damage after this time will be subject to rejection
It is the general practice of Regency. to charge for larger, higher priced replacement pans and issue credit once the replaced component has been returned to Regency and evaluated for
manutaclurer defect.
The authorized selling dealer is responsible for all n -field service work earned out on your Regencr product. Regency will not be liable for results or costs of workmanship from unauthorized
service persons or dealers.
At as times Regency reserves the right to inspect product in the field which is claimed to be defective.
Al claims must be submitted to Regencye by authorized selling dealers. It is essential that as submitted class provide all 01 the necessary information including customer name. purchase
date. serial N. type of unit, problem. and pad or parts requested. without this information the warranty will be invald.
Exclusions:
This limited Lifetime Warranty does not extend to or include paint. door or glass gaskebng or Inn.
At no time via Regency° be liable for any consequential damages which exceed the purchase prize 01 the unit. Regency'shas no orolgation to enhance or modify any unit once manufactured.
ie. as products evolve. field modifications or upgrades will not be performed.
Regency° will not be liable for travel costs for service work.
Installation and environmental problems are not the responsibility of the manufacturer and therefore are not covered under the terms of this warranty policy.
Embers. rockwool. gaskets, door !uncles and pawn are not covered under the terms of this warranty policy.
Any unit which shows signs of neglect or misuse Is not covered under the terms of this warranty policy.
The warranty via not extend to any pad which has been tampered with or altered in any way, or in our judgment has been subject to misuse. improper instalation. negbgence or accdent
spillage or downdrafts caused by enwonnental or geographical conditions. inadequate venblation. excessive onsets. negative art pressure caused by mechanical systems such as lumaces.
fans. clothes dryer. etc.
Freight damage to stoves and replacement pads is not covered by warranty and is subsol to a claim against the freight carrier by the dealer.
Regency will not be liable for acts 01God, or acts 01 terrorism. which cause mallunclion 01 the appliance.
Performance problems due to operator error will not be covered by this warranty policy.
Products made or provided by other manufacturers and used in conjunction with the operation of this appliance without prior authorization from Regency.. may nobly your warranty on
this product.
My alteration to the lint which causes sooting or carbonng that resins in damage to the interior / exterior facia is not the responsibility of Regency°.
• Subskly according to job scale as predeterrnmed by FPI.
Regency HorizonTM HZ40E Gas Fireplace
EFTA00301482
Register your Regency° warranty online
www.regency-fi
Reasons to register your product online today!
• View and modify a list of all your registered products.
• Request automatic email notification of new product updates.
• Stay informed about the current promotions, events, and special
offers on related products.
Installer: Please complete the following information
Dealer Name & Address:
Installer:
Phone #:
Date Installed:
Serial No.:
Regency Honzon and SureFire are trademarks of FPI Fireplace Products International Ltd.
© Copyright 2012 FPI Fireplace Products International Ltd. All rights resented. Printed in Canada
EFTA00301483