CAT
Project Submittal
For
LSJE, LLC - ST. THOMAS
Two (2) Caterpillar Model D125 - 8
Engine Driven Generator Set
Warren Cat ID No.: M0114821, M0114822
Warren Cat EA No.: CE36505, CE36506
CATERPILLAR
EFTA00798769
LSJE, LLC - ST. THOMAS
6100 Red Hook Quarter B3
St. Thomas, VI 00802 - 1348
Project Submittal
125 kW Electric Generator Set
Little St. James
Two (2) Caterpillar Model D125 - 8
Customer Purchase Order No.: CBO
Warren Cat ID No.: M0114821, M0114822
Warren Cat EA No.: CE36505, CE36506
Warren CAT
15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
19 July 2018
EFTA00798770
Warren CAT
WARREN CAT 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
CONTENT
SECTION DESCRIPTION
SCOPE OF SUPPLY
Standard Consist
Selected Caterpillar Options
Documentation
Start Up & Commissioning
Warranty
II GENERATOR PACKAGE
C7.1 Generator Set — Electric Power
III ALTERNATOR DATA
Generator Data
Operating Chart
IV TECHNICAL DATA (Cut Sheets)
Weather Protective Enclosure
ADEM
EMCP 4.2 Controller
Permanent Magnet Generator
Integrated Voltage Regulator
Excitation Module
Coolant Heater
Circuit Breaker Application
Breaker Curves
Ground fault Relay
Battery Charger
Battery
UL Listed
V MECHANICAL DRAWINGS
VI ELECTRICAL DRAWINGS
VII START UP AND COMMISSIONING CHECK LIST
VIII CATERPILLAR WARRANTY
Note: Images shown in this document may not reflect the actual configuration.
EFTA00798771
Warren CAT
WARREN CAT 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
SECTION I
SCOPE OF SUPPLY
The following is a listing of the equipment and services to be provided with each of two (2) sets:
Item 1 One (1) Caterpillar Model D125 - 8 diesel engine generator sets with the following
configuration:
Configuration
EPA STATIONARY EMERGENCY
PRIME POWER APPLICATION
Rating
114 ekW, 0.8 pf, 208 / 120 Volt, 3 Phase, 60 Hz, 1,800 rpm
Unit Consist
Diesel Engine: Model C7.1-ELEC
Alternator: Frame LC3114J
Single Bearing, Random Wound
Standard Consist for C7.1 PGABR
ENGINE PACKAGE DESCRIPTION
ENGINE
Electrical system,12 VDC
Coolant and lube drains piped to the edge of base
D125-8 includes ADEM A4 electronic engine control
with Speed Adjust thru EMCP
Tier 3 EPA Approved Emissions Certified
INTEGRATED VOLTAGE REGULATOR (Digital):
EM10 Excitation Module
Voltage within +/- 0.25% at steady state from no load to full load
Provides fast recovery from transient load changes
CHARGING SYSTEM
CAT Premium High Output Battery with rack & cables
Installed (wet); 1000 CCA; 90amp hr;12V
EFTA00798772
Warren CAT
WARREN CAT 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
SECTION I
SCOPE OF SUPPLY (continued)
Standard Consist for C7.1 PGABR (continued)
CONTROL SYSTEM
CONTROL PANEL
NEMA 1 enclosure with hinged door
Wiring loom
DC and AC wiring harness
EMCP 4.2 controls including:
Run / Auto / Stop Control
Speed Adjust
Engine Cycle Crank
Emergency Stop pushbutton
EMCP 4.2 controller features:
12-volt DC operation
Environmental sealed front face
Text alarm/event descriptions
Digital indication for:
RPM
DC Volts
Operating Hours
Oil Pressure (psi)
Coolant Temperature
Volts (L-L & L-N). frequency (Hz)
Amps (per phase & average)
Power Factor (per phase & average)
kW (per phase,average & percent)
kVA (per phase,average & percent)
kVAr (per phase,average & percent)
kW-hr (total)
kVAr-hr (total)
Warning/shutdown with common LED indication of shutdowns for:
Low Oil pressure
Low Coolant temp alarm (detects jacket water heater failure)
High Coolant temperature shutdown
EFTA00798773
Warren CAT
WARREN CAT 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
SECTION I
SCOPE OF SUPPLY (continued)
Standard Consist for C7.1 PGABR (continued)
CONTROL PANELS (continued)
Programmable protective relaying functions:
Generator phase sequence
Over/Under voltage (27/59)
Over/Under Frequency (81 o/u)
Reverse Power (KW) (32)
Reverse Reactive Power (kVAr) (32RV)
Overcurrent (50/51)
Communications
Customer DATA link (Modbus RTU)
RS485 Serial DATA link (terminals only)
8 programmable digital outputs available
2 relays pre-programmed
8 programmable digital inputs available
2 pre-programmed
CIRCUIT BREAKERS
UL/CSA listed mainline breaker
Single Breaker 100% Rated 3-pole with solid neutral
NEMA 1 steel enclosure
Electrical stub-up area directly below circuit breaker
COOLING SYSTEM
Radiator and cooling fan complete with protective guards
Standard ambient temperatures up to 50degC (122degF)
50% coolant antifreeze/corrosion inhibitor
Coolant reservoir
EFTA00798774
Warren CAT
WARREN CAT 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
SECTION I
SCOPE OF SUPPLY (continued)
Standard Consist for C7.1 PGABR (continued)
GENERATORS
GENERATOR SET
Complete system designed and built at ISO 9001:2000 certified facilities
Factory tested to design specifications at full load conditions
and all protective devices and control functions simulated and checked
GENERATOR
Insulation system, class H
Drip proof generator air intake (NEMA 2,IP23)
Electrical design in accordance with BS5000 Part 99,EN61000-6,
IEC60034-1,NEMA MG-1.33
EQUIPMENT FINISH
All electroplated hardware
Anticorrosive paint protection
High gloss polyurethane paint for durability and scuff resistance
QUALITY STANDARDS
BS4999,BS5000,855514,EN61000-6.IEC60034,NEMA MG-1.33,
NFPA 110 (with optional equipment)
LITERATURE / DOCUMENTATION
Operation and maintenance manual pack and OMM Storage Compartment
Wiring diagrams included
MOUNTING SYSTEM
Heavy-duty fabricated steel base with lifting points
Anti-vibration pads to ensure vibration isolation
Complete OSHA guarding
Stub-up pipe ready for connection to silencer pipe work
Flexible fuel lines to base with NPT connections
GENERAL
Factory Test Report
EFTA00798775
Warren CAT
WARREN CAT 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
SECTION I
SCOPE OF SUPPLY (continued)
Item 1 One (1) Caterpillar Model D125 — 8 diesel engine generator set with the following:
Selected Caterpillar Options
208 / 120 v. 3 Phase
60 Hz, 114 kW
UL 2200 Listed Package Gen Set
EPA Stationary Emergency
Prime Power
ENGINE
Air Inlet System
Single element Air Filter — Light Duty
Cooling System
Standard Radiator
Coolant Heater
TECHNICAL: On at 100 and off at 120 degree F
Low Coolant Level Shutdown
GENERATOR
Generator
Frame: LC3114J Attunement 4545283
Excitation
Permanent Magnet Excitation
Main Breaker
400 Amp First Breaker 100% Rated UL
ENCLOSURE
Enclosure
Sound Attenuated Enclosure 12 (White)
TECHNICAL: Foam enclosure with endbox Critical Silencer
Audible Alarm
Panel Mounted Audible Alarm
Emergency Stop
External Emergency Stop Button
STARTING SYSTEM
Battery
Wet Battery
Battery Charger
NFPA Batter Charger UL 10A 120 VAC
EFTA00798776
Warren CAT
WARREN CAT 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
SECTION I
SCOPE OF SUPPLY (continued)
Item 1 One (1) Caterpillar Model D125 — 8 diesel engine generator set with the following:
Selected Caterpillar Options (continued)
GROUND RELAY SYSTEM
Ground Fault Relay
TECHNICAL: GROUND FAULT INDICATION
CONTROL PANEL OPTIONS
Generator Control
EMCP 4.2 Generator Control Panel
Control Panel Options Box
Accessory Connections
NFPA 110 Bundle
Bundled option to include:
Low Coolant level shut down
Low Coolant temperature alarm
Panel mounted audible alarm
NFPA Battery Charger
EFTA00798777
Warren CAT
WARREN CAT 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
SECTION I
SCOPE OF SUPPLY (continued)
Documentation
Submittals Electronic Copy One (1)
Operation and Maintenance Manuals One (1)
Parts Disc One (1)
Start Up and Commissioning
By Others
Caterpillar Warranty
Standard Caterpillar Prime Power Warranty
EFTA00798778
Warren CAT
WARREN Mi 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
SECTION II
GENERATOR PACKAGE
EFTA00798779
C7.1 Generator Set
Electric Power
CAT®
Caterpillar is leading the power generation marketplace
with Power Solutions engineered to deliver unmatched
flexibility, expandability, reliability, and cost-effectiveness.
Image shown may not reflect actual configuration
Specifications
Generator Set Specifications
Rating 114 ekW (142.5 kVA)
Voltage 480 Volts
Frequency 60 Hz
Speed 1800 rpm
Generator Set Configurations
U.S. EPA Certified for Stationary Emergency Use Only
Emissions/Fuel Strategy
(Tier 3 Nonroad Equivalent Emission Standards)
Engine Specificatio
Engine Model C7.1 In-line 6, 4-cycle diesel
Bore 105 mm 4.13 in
Displacement 7.01 L 427.8 in3
Stroke 135 mm 5.31 in
Compression Ratio 16.7:1
Aspiration Turbocharged Air-to-Air-Aftercooled
Governor Type Electronic
Fuel System Common Rail
Package Dimensions*
Length 3039mm 119.7 in
Width 1110 mm 43.7 in
Height 1476 mm 58.1 in
Weighty 1500 kg 3307 lb
*Note: For reference only — do not use for installation design. Please contact your local dealer for exact
weight and dimensions.
tWeight includes: Oversize generator, skid base, circuit breaker, oil, and coolant.
LEHE0889-02 Page 1 of 7
EFTA00798780
C7.1 Generator Set
Electric Power
CAT®
Benefits & Features
Car Diesel Engine
• Reliable, rugged, durable design
• Four-stroke cycle diesel engine combines consistent performance and excellent fuel economy
with minimum weight
• Electronic engine control
Generator
• Matched to the performance and output characteristics of Cat engines
• Industry-leading mechanical and electrical design
• Industry-leading motor starting capabilities
• High efficiency
Cat EMCP Control Panel
The EMCP controller features the reliability and durability you have come to expect from your
Cat equipment. EMCP 4 is a scalable control platform designed to ensure reliable generator set
operation, providing extensive information about power output and engine operation. EMCP 4
systems can be further customized to meet your needs through programming and expansion
modules.
Seismic Certification
• Seismic certification available
• Anchoring details are site specific, and are dependent on many factors such as generator set
size, weight, and concrete strength
IBC certification requires that the anchoring system used is reviewed and approved by a
professional engineer
Seismic certification per applicable building codes: IBC 2006, IBC 2009, IBC 2012, IBC 2015
Design Criteria
• The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5
transient response
• Cooling system designed to operate in 50`C/122T ambient temperatures with an air flow
restriction of 0.5 in. water
UL 2200/CSA — Optional
• UL 2200 Listed
• CSA Certified
Certain restrictions may apply. Consult with your Cat dealer.
Single-Source Supplier
Fully prototype tested with certified torsional vibration analysis.
Worldwide Product Support
Cat dealers provide extensive post-sale support including maintenance and repair agreements.
Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar
S•O•Ss" program cost-effectively detects internal engine component condition, even the presence of
unwanted fluids and combustion by-products.
LEHE0889-02 Page 2 of 7
EFTA00798781
C7.1 Generator Set
Electric Power
CAT®
Standard Equipment
Air Inlet
• Dry replaceable paper element type with restriction indicator
Cooling
• Radiator and cooling fan complete with protective guards
• Standard ambient temperatures up to 50°C (122°F)
Exhaust
• Exhaust flange outlet
Fuel
• Primary and secondary fuel filters
• Fuel priming pump
• Flexible fuel lines
Generator
• Matched to the performance and output characteristics of Cat engines
• Load adjustment module provides engine relief upon load impact and improves load acceptance
and recovery time
• IP23 protection
• Integrated Voltage Regulation
Governor
• Electronic governor — ADEM TPA A4
Control Panels
• EMCP 4.2 Series generator set controller
Mounting
• Rubber vibration isolators
Starting/Charging
• 12 volt starting motor
• Batteries with rack and cables
General
• Paint — Caterpillar Yellow except rails and radiators gloss black
LEHE0885-02 Page 3 of 7
EFTA00798782
C7.1 Generator Set
Electric Power
CAT®
Optional Equipment
Exhaust
• Industrial, residential, critical mufflers
Generator
• Excitation: [ ] Permanent Magnet Excited (PM) ] Internally Excited (lE)
• Anti-condensation heater
Oversize and premium generators
Starting/Charging
Battery charger — UL 10 amp
• Battery disconnect switch
Jacket water heater
General
• UL 2200
• CSA Certification
Enclosures: sound attenuated, weather protective
• Sub-base dual wall UL Listed fuel tanks
• Automatic transfer switches (ATS)
LEHE0889-02 Page 4 of 7
EFTA00798783
ELECTRIC POWER — Technical Spec Sheet
STANDARD
C7.1
CAT®
114 ekW/ 142.5 WA/ 60 Hz/ 1800 rpm/ 480V/ 0.8 Power Factor
Rating Type: PRIME Emissions: U.S. EPA Certified for Stationary Emergency Use Only
(Tier 3 Nonroad Equivalent Emission Standards)
D125-8
114 ekW/ 142.5 kVA
60 Hz/ 1800 rpm/ 480V
Image shown may not reflect actual configuration
Package Performance
Generator Set Power Rating with Fan @ 0.8 Power Factor 114 ekW
Generator Set Power Rating 142.5 kVA
Fuel Consumption
100% Load With Fan 35.2 Uhr 9.3 g/hr
75% Load With Fan 28.2 Uhr 7.4 g/hr
50% Load With Fan 20.3 Uhr 5.4 g/hr
Cooling System'
Engine Coolant Capacity 9.5 L 2.5 gal
Radiator Coolant Capacity 11.5 L 3.0 gal
Engine Coolant Capacity with Radiator/Exp Tank 21.0 L 5.5 gal
Air Flow Restriction (System) 0.12 kPa 0.48 in Water
Combustion Air Inlet Flow Rate 13.9 ms/min 490.9 cfm
Exhaust System
Exhaust Stack Gas Temperature 439°C 822°F
Exhaust Gas Flow Rate 28.8 ms/min 1017 cfm
Exhaust System Backpressure (maximum allowable) 15.0 kPa 60.2 in water
Exhaust Flange Size (internal diameter) 89.0 mm 3.5 in
LEHE0889-02 Page 5 of 7
EFTA00798784
ELECTRIC POWER — Technical Spec Sheet
STANDARD
C7.1
CAT®
114 ekW! 142.5 kVA/ 60 Hz! 1800 rpm! 480W 0.8 Power Factor
Rating Type: PRIME Emissions: U.S. EPA Certified for Stationary Emergency Use Only
(Tier 3 Nonroad Equivalent Emission Standards)
Heat Rejection
Heat Rejection to Coolant (total) 69.0 kW 3924 Btu/min
Heat Rejection to Exhaust (total) 120.0 kW 6796 Btu/min
Heat Rejection to Aftercooler 30.0 kW 1689 Btu/min
Heat Rejection to Atmosphere from Engine 26.0 kW 1496 Btu/min
Heat Rejection to Atmosphere from Generator 8.8 kW 500.4 Btu/min
Alternator
Motor Starting Capability @ 30% Voltage Dip 363 skVA
Frame LC3114G
Temperature Rise 105°C 189°F
Excitation Self Excited
Sump Refill with Filter 17.5 L 4.6 gal
Emissions (Nominal)'
NOx + HC 4.0 g/kW-hr
CO 1.0 g/kW-hr
PM 0.2 g/kW-hr
'For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to the
existing restriction from the factory.
2Generator temperature rise is based on a 40°C (104°F) ambient per NEMA MG1-32.
'The nominal emissions data shown is subject to instrumentation, measurement, facility and engine to
engine variations. Emissions data is based on 100% Prime load. This information should not be used for
permitting purposes and is subject to change without notice. Contact your Cat dealer for further details.
LEHE0889-02 Page 6 of 7
EFTA00798785
ELECTRIC POWER — Technical Spec Sheet
STANDARD
C7.1
CAT®
114 ekW! 142.5 kVA/ 60 Hz/ 1800 rpm! 480W 0.8 Power Factor
Rating Type: PRIME Emissions: U.S. EPA Certified for Stationary Emergency Use Only
(Tier 3 Nonroad Equivalent Emission Standards)
DEFINITIONS AND CONDITIONS
Applicable Codes and Standards:
AS1359, CSA C22.2 No 100-04, UL142, UL489, UL601, UL869, UL2200, NFPA 37, NFPA 70, NFPA 99,
NFPA 110, IBC,IEC60034-1, ISO3046, ISO8528, NEMA MG 1-22, NEMA MG 1-33, 72/23/EEC, 98/37/EC,
2004/108/EC.
PRIME: Output available with varying load for an unlimited time. Average power output is 70% of the
prime power rating.Typical peak demand is 100% of prime rated ekW with 10% overload capability for
emergency use for a maximum of 1 hour in 12. Overload operation cannot exceed 25 hours per year.
Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard
conditions.
Fuel Rates are based on fuel oil to specification EPA 2D 89.330-96 with a density of 0.845 - 0.850 kg/L
(7.052 - 7.094 lbs/U.S. gal.) @ 15°C (59°F) and fuel inlet temperature 40°C (104°F).
Additional ratings may be available for specific customer requirements, contact your Cat representative
for details.
www rat-FlartriePnwor relit
Performance No.: P4392C-00 O2016 Caterpillar
Feature Code: NAC160P All rights reserved.
Generator Arrangement: 4545273 Materials and specifications are subject to change without notice.
Date: 09/13/2016 The International System of Units (SI) is used in this publication.
Source Country: U.S. CAT. CATERPILLAR. their respective logos. ADEM. S.O.S, 'Caterpillar Yellow'.
the "Power Edge" trade dress as well as corporate and product identity used
LEHE0BB9-01 herein, are trademarks of Caterpillar and may not be used without permission.
EFTA00798786
Warren CAT
WARREN CAT 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
SECTION III
ALTERNATOR DATA
EFTA00798787
7/18/2018 Caterpillar Generator Data
GENERATOR DATA JULY 18, 2018
For Help Desk Phone Number,
Selected Model
Engine: C7.I Generator I. aloe: LC31143 Genset Rating (kW): 114.0 Line Voltage: 208
Fuel: Diesel Generator Arrangement: 4545283 Genset Rating (kVA): 142.5 Phase Voltage: 120
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 395.5
Duty: PRIME Connection: PARALLEL STAR Application: EPG Status: Current
Version: 41764 /41736 /42059 1633
Spec information
Generator Specification Generator Efficiency
Frame: LC3114J Type: LC No. of Bearings: I Per Unit Load kW Efficiency %
Winding Type: RANDOM WOUND Flywheel: 11.5 0.25 28.5 91.1
Connection: PARALLEL STAR Housing: 3 0.5 57.0 93.5
Phases: 3 No. of Leads: 12 0.75 85.5 94.0
Poles: 4 Wires per Lead: I 1.0 114.0 93.8
Sync Speed: 1800 Generator Pitch: 0.6667 1.1 125.4 93.6
Reactances Per Unit Ohms
SUBTRANSIENT - DIRECT AXIS ri d 0.0929 0.0282
SUBTRANSIENT - QUADRATURE AXIS ri g 0.1835 0.0557
TRANSIENT - SATURATED rd 0.1545 0.0469
SYNCHRONOUS - DIRECT AXIS Xd 3.2147 0.9760
SYNCHRONOUS - QUADRATURE AXIS X4 1.9288 0.5856
NEGATIVE SEQUENCE X2 0.1380 0.0419
ZERO SEQUENCE X0 0.0033 0.0010
lime Constants Seconds
OPEN CIRCUIT TRANSIENT - DIRECT AXIS Tdo 2.0791
SHORT CIRCUIT TRANSIENT - DIRECT AXIS Td 0.1000
OPEN CIRCUIT SUBSTRANSIENT - DIRECT AXIS T"do 0.0167
SHORT CIRCUIT SUBSTRANSIENT - DIRECT AXIS T"d 0.0100
OPEN CIRCUIT SUBSTRANSIENT - QUADRATURE AXIS T"q0 0.1052
SHORT CIRCUIT SUBSTRANSIENT - QUADRATURE AXIS T"q 0.0100
EXCITER TIME CONSTANT; 0.0300
ARMATURE SHORT CIRCUIT Ta 0.0150
Short Circuit Ratio: 0.37 Stator Resistance = 0.0118 Ohms Field Resistance = 3.29 Ohms
Voltage Regulation Generator Excitation
Voltage level adjustment: +/- 5.0% No Load Full Load, (rated) pf
Voltage regulation, steady state: +/- 0.5% Series Parallel
Voltage regulation with 3% speed change: +1- 1.0% Excitation voltage: 5.82 Volts 28.27 Volts Volts
Waveform deviation line - line, no load: less than 2.0% Excitation current 0.45 Amps 1.8 Amps Amps
Telephone influence factor: less than 50
https://tmiwebelassie.cat.corn/tmi/servlet/TMIDirector?Action=openvAndow&log=genXml0ata&type=RNGenDataRelNum&relno=8.selection=&unitType... 1/8
EFTA00798788
7/18/2018 Caterpillar Generator Data
Selected Model
Engine: C7.I Generator Frame: LC3114J Genset Rating (kW): 114.0 Line Voltage: 208
Fuel: Diesel Generator Arrangement: 4545283 Genset Rating (kVA): 142.5 Phase Voltage: 120
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 395.5
Duty: PRIME Connection: PARALLEL STAR Application: EPG Status: Current
Version: 41764 /41736 142059 1633
Generator Mechanical Information
Center of Gravity
Dimension X 0.0 nun 0.0 IN.
Dimension Y 0.0 nun 0.0 IN.
Dimension Z 0.0 nun 0.0 IN.
• "r is measured from driven end of generator and parallel to rotor. Towards engine
fan is positive. See General Information for details
• "Y" is measured vertically from rotor center line. Up is positive.
• 7" is measured to left and right of rotor center line. To the right is positive.
Generator WT = 0 kg ■ Rotor WT = 0 kg * Stator WT = 0 kg
0.0 LB 0.0 LB 0.0 LB
Rotor Balance = 0.0508 mm deflection PTP
Overspeed Capacity = 125% of synchronous speed
HIOVV\V IVIKM
Generator Torsional Data
0
c>
J1 = Coupling J2 = Rotor J3 = Exciter
and Fan TOTAL J = J1 +J2 + J3 End
ICI = Shaft Stiffness between 1C2 = Shaft Stiffness between
JI + J2 (Diameter 1) J2 +J3 (Diameter 2)
JI ict Min Shaft Dia I J2 K2 Min Shaft Dia 2 J3
0.0 LB IN. 52 0.0 MLB IN./rad 0.0 IN. 0.0 LB IN. s2 0.0 MLB IN./rad 0.0 IN. 0.0 LB IN. s2
0.0 N m 52 0.0 MN mired 0.0mm 0.0 N m 52 0.0 MN m/rad 0.0mm 0.0 N m s2
Total .1
0.0 LB IN. s2
0.0 N m52
Selected Model
Engine: C7.1 Generator Frame: LC31143 Genset Rating (kW): 114.0 Line Voltage: 208
Fuel: Diesel Generator Arrangement: 4545283 Genset Rating (kVA): 142.5 Phase Voltage: 120
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 395.5
Duty: PRIME Connection: PARALLEL STAR Application: EPG Status: Current
Version. 4170/41736 /43059 /633
hupsfitmiweleclassiocat.com/tmi/servleUTMIDirector?Action=openvAndownlog=genXmiDatantype=ftNGenDataftelNum&relno=8.selection=&unitType... 2/8
EFTA00798789
7/18/2018 Caterpillar Generator Data
Generator Cooling Requirements -
Temperature - insulation Data
Cooling Requirements: Temperature Data: (Ambient 40 0C)
I lest Dissipated: 7.5 kW Stator Rise: 105.0°C
Air Flow: 18.0 m3/min Rotor Rise: 105.0°C
Insulation Class: Ii
Insulation Reg. as shipped: 100.0 MI/ minimum at 40 °C
Thermal Limits of Generator
Frequency: 60 Hz
Line to Line Voltage: 208 Volts
B BR 80/40 141.5 kVA
F BR -105/40 161.0 kVA
H BR - 125/40 177.0 kVA
F PR - 130/40 177.0 kVA
H PR -150/40 187.5 kVA
H PR27 - 163/27 194.5 kVA
Selected Model
Engine: C7.I Generator Frame: LC31143 Genset Rating (kW): 114.0 Line Voltage: 208
Fuel: Diesel Generator Arrangement: 4545283 Genset Rating (kVA): 142.5 Phase Voltage: 120
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 395.5
Duty: PRIME Connection: PARALLEL STAR Application: EPG Status: Current
%miens:41764 /41736 /42059 /633
Starting Capability & Current Decrement
Motor Starting Capability (0.6 pf)
Percent Motor Starting
SKVA Volt Dip
21 23 40
44 5.0
68 73 O . 35
93 10.0 30
119 123
147 15.0 25
177 173
, 20
209 20.0 C
242 22.5 ;I' 15
278 25.0 I.
317 273 10
358 30.0
5
402 323
450 35.0 0
501 373 0 leo zoo 300 460 560
557 40.0
SKVA
https://tmiwebelassie.eat.corn/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlOata&type=RNGenDataRelNum&relno=aselection=&unitrype... 3/8
EFTA00798790
7/18/2018 Caterpillar Generator Data
Current Decrement Data
E Time AMP
Current Decrement
Cycle
0.0 4232
1.0 2,505
4,000
2.0 1.918 3,500
3.0 1.587
4.0 1.336 3,000
5.0 1.126 2,500
7.5 n9
10.0 463 2,000
12.5 286 1,500
15.0 185
20.0 98 1,000
25.0 69
500
30.0 57
35.0 53 0
40.0 51 0 10 20 30 40
45.0 50 E Time Cycle
Instantaneous 3 Phase Fault Current: 4232 Amps Instantaneous Line - Line Fault Current: 2945 Amps
Instantaneous Line - Neutral Fault Current: 5033 Amps
Selected Model
Engine: C7. I Generator Frame: LC31I4J Genset Rating (kW): 114.0 Line Voltage: 208
Fuel: Diesel Generator Arrangement: 4545283 Genset Rating (kVA): 142.5 Phase Voltage: 120
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 395.5
Duty: PRIME Connection: PARALLEL STAR Application: EPG Status: Current
Version: 41764 /41736 /42059 /633
Generator Output Characteristic Curves
Open Circuit Curve
Open Circuit
300
Field Line •
Current Line Volt 250
44
0.0 0
2.7 125
3.2 146
3.8 166 150
4.4 187
5.2 208
tal 100
6.3 229
8.2 250 z
11.4 270 50
17.6 291
0
0 5 10 15
Field Current
httpsditmiwebelassie.cat.com/tmi/sarvlet/TMIDIrector?ActIon=opanvAndow&log=genXmlOata&type=RNGenDalaReINum&reino=8.salection=&unItType... 4/8
EFTA00798791
7/18/2018 Caterpillar Generator Data
Short Circuit Curve
Short Circuit
Field Armature 500
Currant Current
0.0 0
400
8.7 237
7
10.2 277 U
11.6 316 ad 300
13.1 356 7
14.5 396 ▪ 200
16.0 435
17.4 475
18.9 514
100
20.3 554
0
0 5 10 15 20
Field Current
Selected Model
Engine: C7. I Generator Frame: LC31143 Genset Rating (kW): 114.0 Line Voltage: 208
Fuel: Diesel Generator Arrangement: 4545283 Genset Rating (kVA): 142.5 Phase Voltage: 120
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 395.5
Duty: PRIME Connection: PARALLEL STAR Application: EPG Status: Current
Venien: 41764 141736 /42059 /633
Generator Output Characteristic Curves
Zero Power Factor Curve
Zero Power
Field Line - 250
Current Lino Volt
14.5 0 O 200
17.3 104
17.8 125 eu
18.4 146 c 150
19.1 166
19.9 '87 at 100
21.2 208 C
23.4 229
27.3 250
▪ 50
34.7 270
0
15 20 25 30 35
Field Current
https://tmiwebelassie.eat.cern/trni/scoviet/TMIDirector?Action=openvAndow&log=genXmiData&type=RNGenDataRefNum&refno=8.seleetion=&unItType... 5/8
EFTA00798792
7/18/2018 Caterpillar Generator Data
Air Gap Curve
Air Gap
300
Field Line -
Current Lino volt 250
0.0 0
2.7 125 > 200
3.1 146 w
C
3.6 166 150
4.0 187
4.5 208
tal 100
4.9 229
SA 250
5.8 270 50
6.3 291
0
0 1 2 3 4 5 6
Field Current
Selected Model
Engine: Cl.l Generator Frame: LC31143 Genset Rating (kW): 114.0 Line Voltage: 208
Fuel: Diesel Generator Arrangement: 4545283 Genset Rating (kVA): 142.5 Phase Voltage: 120
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 395.5
Duty: PRIME Connection: PARALLEL STAR Application: EPG Status: Current
Version. 41764 /41736 /42059 /633
Reactive Capability Curve
Click to view Chart
Selected Model
Engine: C7.I Generator Frame: LC31I4J Censet Rating (kW): 114.0 Line Voltage: 208
Fuel: Diesel Generator Arrangement: 4545283 Censet Rating (kVA): 142.5 Phase Voltage: 120
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 395.5
Duty: PRIME Connection: PARALLEL STAR Application: EPG Status: Current
%erskos: 41764 /41736 /42059 /633
https://tmiwebelassie.cat.corn/tmi/servlet/TMIDirector?Action=openvAndow&log=genXmlOata&type=RNGenDataRelNum&relno=8.selection=&unitType... 6/8
EFTA00798793
7/18/2018 Caterpillar Generator Data
General Information
GENERATOR INFORMATION (DM7900)
I. Motor Starting
Motor starting curves arc obtained in accordance with IEC60034. and
arc displayed at 0.6 power factor.
2. Voltage Dip
Prediction of the generator synchronous voltage dip can be made by
consulting the plot for the voltage dip value that corresponds to the
desired motor starting kVA value.
3. Definitions
A) Generator Keys
Frame: abbreviation of generator frame size
Freq: frequency in hertz.
PP/SR: prime/standby duty respectively
Volts: line - line terminal voltage
kW: rating in electrical kilo watts
Model: engine sales model
B) Generator Temperature Rise
The indicated temperature rises are the IEC/NEMA limits for standby
or prime power applications. The quoted rise figures are maximum
limits only and are not necessarily indicative of the actual
temperature rise of a given machine winding.
C) Centre of Gravity
The specified centre of gravity is for the generator only. For single
bearing, and two bearing close coupled generators, the center of
gravity is measured from the generator/engine flywheel-housing
interface and from the centreline of the rotor Shaft.
For two bearing, standalone generators. the center of gravity is
measured from the end of the rotor shaft and from the centerline of
the rotor shaft.
D) Generator Current Decrement Curves
The generator current decrement curve indicates the generator
armature current arising from a symmetrical three-phase fault at the
generator terminals. Generators equipped with AREP or PMG excitation
systems will sustain 300% of rated armature current for 10 seconds.
E) Generator Efficiency Curves
The efficiency curve is displayed for the generator only under the
given conditions of rating, voltage, frequency and power factor. This
is not the overall generating set efficiency curve.
Caterpillar Confidential: Green
Content Owner: Commercial Processes Division
httpsfieniwebelassic.cat.corrandserviat/TMIDirector?Action=opanwindow&log=genXml0ata&typa=RNGenDataRelNum&relno=8salection=&unitType... 7/8
EFTA00798794
7/18/2018 Caterpillar Generator Data
Web Master(s): PSG Web Based Systems Support
Current Date: 7/18/2018, 1:52:06 PM
C Caterpillar Inc. 2018 All Rights Reserved.
Pala Privacy Statement.
https://tmiwebelassic.cat.com/linikervletf7MIDirector?Action=openwindene&log=genXmloata8type=RNGenDataRetNum&retno=itselection=&unitType... 818
EFTA00798795
Operating Chart
Leading Lagging
I.2
kW/ Rated kVA
-1 -0.8 -0.6 -0.4 -0.2 6 0.2 0.4 0.6 0.8
kVAr/ Rated kVA
EFTA00798796
Warren CAT
WARREN EZI 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
SECTION IV
TECHNICAL DATA (Cut Sheets)
Cat Batteries
EFTA00798797
Enclosures
CAT
Weather Protective and Sound
Attenuated Enclosures
D40-6 to D200-2
D40-6S to D100-8S
Picture shown may not reflect actual configuration
Features
Highly Corrosion Resistant construction Options
• Stainless steel flush fitting latches and hinges • Weather Protective - constructed with 16 gauge
tested and proven to withstand extreme steel; industrial silencer mounted within the
conditions of corrosion main enclosure body
• Zinc plated or stainless steel fastener • Sound Attenuated Level 1 - constructed with
16 gauge steel; weather protective with critical
Excellent Access silencer - silencer mounted in separate upward
• Single side access for service and controls discharging radiator hood
• All non-service sides have removable doors • Sound Attenuated Level 2 - constructed with
and/or panels 16 gauge steel; weather protective with critical
• Radiator fill access silencer and 100% lined with sound deadening
• Lube oil and coolant drains piped to the material — silencer mounted in separate upward
exterior of the enclosure base discharging radiator hood
Large cable entry area for installation ease • Sound Attenuated Aluminum constructed with
• Double doors on both sides 14 gauge Aluminum 5052 grade. Weather
Vertically hinged doors with solid bar door protective with critical silencer and 100% lined
stays to hold doors in place when open with sound deadening material — silencer
mounted in separate upward discharging
Security and Safety radiator hood
Lockable access doors which give full access • Caterpillar Yellow" or white paint
to control panel and breaker • UL Listed sub base tanks
• Cooling fan and battery charging alternator • Externally mounted emergency stop button
fully guarded • Seismic certification per applicable building
Fuel fill, oil fill, and battery can only be reached codes: IBC 2000, IBC 2003, IBC 2006, IBC
via lockable access 2009, IBC 2012, CBC 2007, CBC 2010
• Stub-up area is rodent proof • IBC certification for 180 mph wind loading
'Not available with Aluminium enclosures
Transportability
These enclosures are of extremely rugged
construction to withstand outdoor exposure and
rough handling common on many construction
sites. The sound deadening material is of a
self-extinguishing design
This range of enclosures are designed on
modular principles with many interchangeable
components permitting on site repair
LEHE0417-09 Page 1 of 6
EFTA00798798
Enclosures
CAT
Enclosure Sound Pressure Levels (SPL) at 100%
Weather Protective Cooling Air SPL Q7m
Enclosure Flow Rate (23ft)
Standby
Model eKW m'is cfm dBA
D40-6 40 1.6 3475 72
D50-6 50 1.6 3475 72
D60-6 60 1.9 3920 75
D80-8 80 3.2 6696 79
0100-8 100 3.6 7564 81
O125-8 125 4.6 9676 78
D150-10 150 4.6 9676 79
O175-4 175 5.9 12431 84
O200-2 200 5.9 12431 89
SA Level 1 Cooling Air SPL Q7m
Enclosure Flow Rate (23ft)
Standby
Model eKW m'is cfm dBA
D40-6 40 1.7 3602 66
D50-6 50 1.7 3602 66
O60-6 60 1.8 3899 71
D80-8 80 3.2 6696 78
O100-8 100 3.2 6696 79
D125-8 125 4.2 8899 74
D150.10 150 4.2 8899 74
O175-4 175 5.6 11830 78
0200-2 200 5.5 11654 81
SA Level 2 Cooling Air SPL Q7m
Enclosure Flow Rate (23ft)
Standby
Model eKW mils cfm dBA
D40-6 40 1.7 3602 65
D50-6 50 1.7 3602 66
D60-6 60 1.8 3899 69
D80-8 80 3.2 6696 75
0100-8 100 3.2 6696 76
O125-8 125 4.2 8899 74
D150-10 150 4.2 8899 74
D175-4 175 5.2 11018 74
D200-2 200 5.1 10806 75
LEHE0417-09 Page 2 of 6
EFTA00798799
Enclosures
CAT
SA Aluminum Cooling Air SPL @lm
Enclosure Flow Rate (23ft)
Standby
Model eKW mgs cfm dBA
D40.6 40 1.7 3602 68
050.6 50 1.7 3602 69
060.6 60 1.8 3899 70
D80•8 80 3.2 6696 73
D100-8 100 3.2 6696 74
D125-8 125 4.2 8899 74
D150-10 150 4.2 8899 75
D175-4 175 5.2 11018 75
D200-2 200 5.1 10806 75
The sound pressure level data shown above is quoted as free field and is forguidance only.
Actual levels produced may vary according to site conditions.
LEHE0417-09 Page 3 of 6
EFTA00798800
Enclosures
CAT
Enclosure Dimensions and Weights
• •
HEIGHT(H) =3 =
• ll
• id
6 t
-es LENGTH (L) WIDTH (WI —a.]
Image represents SA Level 1, SA Level 2 and SAAluminum enclosures on skid base only
•
;Os •
• •
CS g01
• •
HEIGHT(H)
• 0 =I •
• •
0 0
• •
• •
LENGTH (L) -a—WIDTH (W),-
Image represents SA Level 1, SA Level 2 and SA Aluminum enclosures mounted on optional UL listed sub base tank
Model Standby WP Industrial SA Level 1 SA Level 2 SA Aluminum
eKW kg lb kg lb kg lb kg lb
D40-6 40
D50-6 50 220 484 272 599 278 612 117 258
D60-6 60
D80-8 80
D100.8 100 263 580 313 690 321 708 142 312
D125-8 125
D150-10 150
348 768 393 867 406 896 176 387
D175.4 175
D200-2 200
Enclosure weights (Includes muffler)
LEHEOei7-09 Page 4 of 6
EFTA00798801
Enclosures
CAT
Enclosure Dimensions Skid Bases
Generator Width 'W Length 12 Height 'H'
Engine
Set Rating Enclosure
Model mm in mm in mm in
ekW
40
50 WP 1110 43.7 2055 80.9 1590 62.6
C4.4 60
40 SA Level 1, SA
Level 2 and SA
50 1110 43.7 2335 91.9 1570 61.8
Aluminum
60
80
WP 1110 43.7 2523 99.3 1773 69.8
100
C4.4
80 SA Level 1, SA
Level 2 and SA 1110 43.7 2891 113.8 1852 72.9
100 Aluminum
125
150
WP 1110 43.7 3204 126.1 1773 69.8
175
200
C7.1
125
SA Level 1, SA
150 Level 2 and SA
1110 43.7 3659 144.1 1852 72.9
175 Aluminum
200
LEHE0417-09 Page 5 of 6
EFTA00798802
Enclosures
CAT
Enclosure Dimensions on UL Listed Sub Base Tanks
Generator 146 Gallon Sub Base Tank 271 Gallon Sub Base Tank
Engine Set Length 'L' Height 'H' Length 'L' Height 'H'
Enclosure
Model Rating
ekW mm In mm in mm in mm in
40
50 WP 2726 107.3 2087 82.1 2726 107.3 2417 95.1
60
C4.4
40 SA Level 1,
SA Level
50 2726 107.3 2067 81.4 2726 107.3 2397 94.4
2 and SA
60 Aluminum
Generator 209 Gallon Sub Base Tank 394 Gallon Sub Base Tank
Engine Set Length 'L' Height 'H' Length 'L' Height 'H'
Enclosure
Model Rating
ekW mm in mm in mm in mm in
80
WP 3447 135.7 2258 88.9 3447 135.7 2608 102.7
100
C4.4 80 SA Level 1,
SA Level
3147 135.7 2337 92.0 3447 135.7 2687 105.8
100 2 and SA
Aluminum
Generator 402 Gallon Sub Base Tank 777 Gallon Sub Base Tank
Engine Set
Enclosure Length 'L' Height 'H' Length 'L' Height 'H'
Model Rating
ekW mm in mm in mm in mm in
125
150
WP 4035 158.9 2420 95.3 5035 198.2 2706 106.5
175
200
C7.1
125
SA Level 1,
150 SA Level
4035 158.9 2499 98.4 5035 198.2 2785 106.5
175 2 and SA
Aluminum
200
Note: Weight includes oil and coolant but not fuel
Ref: WPIA, WPIB, WPIC, SATCBA, SATCBB, SAT, CBC, SATFBA, SATFBB, SATFBC, ENCAL02, ENCAL03, ENCAL04.
www CattlectricPower.com
02016 Caterpillar
All rights reserved.
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, their respective logos. "Caterpillar Yellow",
the tower Edge' trade dress as well as corporate and product identity used
LEHE0417-09 (6-16) herein, are trademarks of Caterpillar and may not be used without permission.
EFTA00798803
ENGINE CONTROLLER CAT
ADEM" A4 Engine
Controller
The ADEM' A4 is the main Electronic Control
Module (ECM) used on select diesel engines.
The ADEM A4 provides a higher degree of
control over a large number of combustion
variables. The ADEM A4 is designed to control/
interface Electronic Unit Injector (EUI) equipped
engines. The ADEM A4 engine system is
composed of the ADEM A4 ECM, control
software, sensors, actuators, fuel injectors,
and interface to the generator system. The
prime benefit of an ADEM A4 engine system is
to better control and maintain the particulate
emissions, both steady state and transient, while
improving engine performance
FEATURES SELF DIAGNOSTICS
RELIABLE, DURABLE Each ADEM A4 ECM has a full compliment of
All ADEM A4 controllers are designed to survive the diagnostics. The ECM can detect faults in the
harshest environments. electrical system and report those faults to the service
• Environmentally sealed, die-cast aluminum housing technician for quick repair.
isolates and protects electronic components from • Self-diagnostic capability pinpoints operational prob-
moisture and dirt contamination. lems in need of attention.
• Rigorous vibration testing ensures product reliability
and durability. ADVANCED FEATURES
• Accuracy maintained from -40° C to 85° C • Enhanced performance from fuel injection timing
and limiting
• Electrical noise immunity to 100 volts/meter
• Adjustable monitoring of vital engine parameters
• Internal circuits are designed to withstand shorts to
• Programmable speed acceleration ramp rate
+ battery and -battery.
• Data link interfaces
SIMPLE SERVICING
Each ADEM A4 system works in combination with
the Catl'ET service tool software to keep the engine
operating at peak performance.
• Displays measured parameters
• Retrieves active and logged event code document-
ing abnormal system operation
• Performs calibrations and diagnostic tests
• Supports flash programming of new software into
the ADEM A4 ECM
LEHE5347-01
EFTA00798804
ENGINE CONTROLLER CM'
DESCRIPTION INFORMATION MANAGEMENT
The ECM is housed in an environmentally sealed cast- The ECM stores information to assist with electronic
ing. All wiring connections to the ECM are made using troubleshooting. Active and logged diagnostic codes,
two sealed connectors: a single seventy-pin connector active events, logged events, fuel consumption,
and a single one hundred twenty-pin connector. engine hours, and instantaneous totals aid service
technicians when diagnosing electronic faults and
ENGINE SPEED GOVERNING scheduling preventive maintenance.
Desired engine speed is calculated by the ECM and
held within ±0.2 Hz for isochronous and droop mode. CALIBRATIONS
The ECM accounts for droop that is requested. The Engine performance is optimized through injection
proper amount of fuel is sent to the injectors due to timing. Auto/manual sensor calibrations are standard
these calculations. The ECM also employs cooldown/ features.
shutdown strategies, acceleration delays on startup,
acceleration ramp times and speed reference. ON-BOARD SYSTEM TESTS
System tests are available to assist in electronic trou-
FUEL LIMITING bleshooting. These tests include: injector activation,
Warm and cold fuel-air ratio control limits are con- injector cutout, and override of control outputs.
trolled by the ECM. Electronic monitoring system
derates, torque limit, and cranking limit, programma- DATA LINK INTERFACES
ble torque scaling, and cold cylinder cutout mode are The ADEM A4 communicates with the EMCP via a
standard features. dedicated communication network.
FUEL INJECTION TIMING ELECTRONIC SENSING
Master timing for injection is controlled by the ECM The following sensing is available on the ADEM A4: oil
control. Temperature dependencies are accounted for pressure, fuel pressure, fuel temperature, atmospheric
in the fuel injection calculations. pressure, air inlet temperature, turbo outlet pressure,
engine coolant temperature, engine speed, throttle,
ELECTRONIC MONITORING position, exhaust temperature, oil filter pressure
Electronic monitoring of vital engine parameters can differential, fuel filter pressure differential, air filter
be programmed. Warning, derate, and shutdown event pressure differential and crankcase pressure.
conditions may be customized by the user.
2
LEHE5347•01
EFTA00798805
ENGINE CONTROLLER CAT
SPECIFICATIONS
Impervious to:
salt spray, fuel, oil and oil additives, coolant,
spray cleaners, chlorinated solvents, hydrogen
sulfide and methane gas, and dust
Input and output protection
all inputs and outputs are protected against
short circuits to +battery and -battery
Input voltage range (24 VDC nominal)
18 to 32 VDC
Mounting
engine mounted
Reverse polarity protected
Shock, withstands 20 g
Temperature range
Operating: -40° C to 85° C (-40° F to 185° F)
Storage: -50° C to 120° C (-58° F to 248° F)
Vibration
withstands 8.0 g @ 24 to 2 kHz
3
LEHE5347•01
EFTA00798806
ENGINE CONTROLLER CAT
This page is intentionally left blank
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow," the "Power Edge" 'x' 2013 Caterpillar
trade dress as well as corporate and product identity used herein, are trademarks All Rights Reserved.
LEHE5347-01 108/131 of Caterpillar and may not be used without permission. Printed in U.S.A.
EFTA00798807
EMCP 4 CAT
EMCP 4.2
& c) GENERATOR SET
•• - CONTROLLER
Caterpillar is leading the power generation market
© 0 place with power solutions engineered to deliver
10 > unmatched performance. reliability, durability and
cost-effectiveness.
Image shown may not reflect actual package
FEATURES
GENERAL DESCRIPTION • Real-time clock allows for date and time stamping
The Cat' EMCP 4.2 offers fully featured power of diagnostics and events in the control's logs as
metering, protective relaying and engine and generator well as service maintenance reminders based on
control and monitoring. Engine and generator controls, engine operating hours or calendar days.
diagnostics, and operating information are accessible • Up to 40 diagnostic events are stored in the non-
via the control panel keypads; diagnostics from the volatile memory.
EMCP 4 optional modules can be viewed and reset
• Ability to view and reset diagnostics on EMCP 4
through the EMCP 4.2. optional modules via the control panel removes
the need for a separate service tool for
FULL RANGE OF ATTACHMENTS troubleshooting.
• Wide range of system expansion attachments,
• Set points and software stored in non-volatile
designed specifically to work with the EMCP 4.
memory, preventing loss during a power outage.
• Flexible packaging options for easy and cost effective
installation. • Reduced power mode offers a low power state to
minimize battery power requirements.
WORLD WIDE PRODUCT SUPPORT • Three levels of security allow for configurable
• Cat dealers provide extensive pre and post sale operator privileges.
support. • Selectable units
• Cat dealers have over 1.600 dealer branch stores - Temperature: °C or °F
operating in 200 countries. - Pressure: psi, kPa, bar
- Fuel Consumption: Gal/hr or Liter/hr
FEATURES
• A 33 x 132 pixel. 3.8 inch, graphical display denotes STANDARDS
text alarm/event descriptions, set points, engine and • UL Recognized
generator monitoring, and is visible in all lighting • CSA C22.2 No.100,14, 94
conditions. • Complies with all necessary standards for
• Textual display with support for 28 languages. CE Certification
including character languages such as Arabic, 98/37/EC Machinery Directive
Chinese, and Japanese. — BS EN 60204-1 Safety of Machinery
• Advanced engine monitoring is available on systems 89/336/EEC EMC Directive
with an electronic engine control module. — BS EN 50081-1 Emissions Standard
• Integration with the Cat Digital Voltage Regulator — BS EN 50082-2 Immunity Standard
(CDVR) provides enhanced system performance. 73/23/EEC Low Voltage Directive
— EN 50178 LVD Standard
• Fully featured power metering, protective relaying, • IEC529, IEC60034-5, IEC61131-3
engine and generator parameter viewing, and • MIL STND 461
expanded AC metering are all integrated into this
controller.
LEHE0138.00
EFTA00798808
EMCP 4.2 GENERATOR SET CONTROLLER
CAT
STANDARD FEATURES
• Voltage (L-L, L-N)
• Current (Phase)
• Average Volt, Amp. Frequency
• kW, kVAr. kVA (Average, Phase, %)
Generator Monitoring • Power Factor (Average, Phase)
• kW-hr, kVAr-hr (total)
• Excitation voltage and current (with CDVR)
• Generator stator and bearing temp (with optional module)
• Generator phase sequence
• Over/Under voltage (27/59)
• Over/Under frequency (81 ON)
Generator Protection • Reverse Power (kW) (32)
• Reverse Reactive Power (kVAr) (32RV)
• Overcurrent (50/51)
• Coolant temperature
• Oil pressure
• Engine speed (RPM)
• Battery voltage
Engine Monitoring
Run hours
• Crank attempt and successful start counter
• Enhanced engine monitoring (with electronic engines)
• Control switch not in auto (alarm)
• High coolant temp (alarm and shutdown)
• Low coolant temp (alarm)
• Low coolant level (alarm)
Engine Protection • High engine oil temp (alarm and shutdown)
• Low, high, and weak battery voltage
• Overspeed
• Overcrank
• Low Oil Pressure
• Run / Auto / Stop control
• Speed and voltage adjust
Control • Local and remote emergency stop
• Remote start/stop
• Cycle crank
• Two dedicated digital inputs
• Six programmable digital inputs
Inputs & Outputs • Six programmable form A dry contacts
• Two programmable form C dry contacts
• Two digital outputs
• Primary and accessory CAN data links
Communications • RS-485 annunciator data link
• Modbus RTU (RS-485 Half duplex)
Arabic, Bulgarian, Chinese, Czech, Danish, Dutch, English, Estonian,
Finnish, French, German, Greek, Hungarian, Icelandic, Italian, Latvian,
Language Support Lithuanian, Japanese, Norwegian, Polish, Portuguese, Romanian,
Russian, Slovak. Slovene. Spanish. Swedish, Turkish
• Control module operating temperature: -40°C to 70°C
• Display operating temperature: -20°C to 70°C
Environmental • Humidity: 100% condensing 30°C to 60°C
• Storage temperature: -40°C to 85°C
• Vibration: Random profile, 24-1000 Hz, 4.3G rms
LEIIE0138 CO 2
EFTA00798809
EMCP 4.2 GENERATOR SET CONTROLLER
CAT
OPTIONAL MODULES
—a 7v 'Min"
/ ' DWI
NOWT0RW0
SOFTWARE
=1 1
sm Q. /
WM =1 Ir.ne
REMOTE MONITORING SOFTWARE
CAN ANNUNCIATOR The EMCP 4 remote monitoring software package
The EMCP 4 CAN Annunciator serves to display genset is a PC based program which allows the user to
system alarm conditions and status indications. monitor and control a generator set, and is capable
The annunciator has been designed for use on of running on a Windows based operating system.
the accessory communication network and may be used The remote monitoring software allows the user
in either local (package mounted) or remote (up to 800 to configure data monitoring and data acquisition
feet) application. A maximum of three annunciators may processes for monitoring, graphing, and logging
be used with a single EMCP 4.2. of genset data.
RS-485 ANNUNCIATOR
The EMCP 4 RS-485 Annunciator serves to display
genset system alarm conditions and status indications.
The annunciator has been designed for use on
the long distance annunciator datalink and is used for
remote (up to 4000 feet) application.
LEHEO 38.00 3
EFTA00798810
EMCP 4.2 GENERATOR SET CONTROLLER
CAT
OPTIONAL MODULES
RTD MODULE
The RTD module serves to provide expandable
generator temperature monitoring capability of the
EMCP 4 and is capable of reading up to eight type
2-wire. 3-wire and 4-wire RTD inputs. The RTD
Module has been designed for use on the
Accessory Communication Network and may be
used in either local (package mounted) or remote
(up to 800 feet) application. A maximum of one RTD
Module may be used with a single EMCP 4.2.
THERMOCOUPLE MODULE
The thermocouple module serves to provide
expandable engine and generator temperature
DIGITAL INPUT/OUTPUT MODULE monitoring capability of the EMCP 4 and is
The Digital Input/Output (DI/O) module serves to capable of reading up to twenty Type J or K
provide expandable Input and Output capability thermocouple inputs. The thermocouple
of the EMCP 4 and is capable of reading 12 digital module has been designed for use on the
inputs and setting 8 relay outputs. The DI/O accessory communication Network and may be
module has been designed for use on the accessory used in either local (package mounted) or remote
Communication Network and may be used in (up to 800 feet) application. A maximum of one
either local (package mounted) or remote thermocouple modules may be used with a single
(up to 800 feet) application. A maximum of four DI/O EMCP 4.2 on each datalink.
modules may be used with a single EMCP 4.2.
Information contained in this publication may be considered confidential. Discretion is recommended when distributing.
Materials and specifications are subject to change without notice.
CAT. CATERPILLAR. their respective logos. 'Caterpillar Yellow.' the Tower Edge' trade dress as well as corporate
and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
werw.Cat-ElectricPower.com
©2010 Caterpillar
All Rights Reserved.
LEHE0138-00 (03.10) Printed in U.S.A
EFTA00798811
GENERATORS CATERPILLAR
AVR12 - PERMANENT
MAGNET GENERATOR
The permanent magnet generator (PMG) option
upgrades the excitation system of the generator
from the standard self-excited system to a
separately-excited system. The PMG couples to
the non-drive end of the generator and provides
an independent source of excitation power that
ensures initial voltage build-up. The PMG improves
the voltage response of the generator during
transient load application, such as motor starting,
and provides a sustained short-circuit current for
the operation of protective devices. Isolation of
the excitation power ensures that regulation is
not affected by non-linear distorting loads.
Electrical Power Output Power
Set reference
cat
AVR
Stator
Lj of PMG
Permanent
Mechanical
Magnet
Rotation
F old
Power
(rotor)
Input
BLOCK DIAGRAM OF PMG
www.cat-ElectricPower.com
Market: N. America
Information contained in this publication may be considered confidential. D 2006 Caterpillar
LENE4016 I01-06) Discretion is recommended when distributing. MI Rights Reserved.
Materials and specifications are subject to change without notice. Printed in U.S.A.
EFTA00798812
INTEGRATED VOLTAGE
REGULATOR
F Genset Control INTEGRATED VOLTAGE
I with IVR Logic Geneietof REGULATOR
I VoltageSensing
&Current
The Integrated Voltage Regulator IIVR) is
designed to provide robust, precise closed-loop
control of the generator voltage, optimized
transient performance and industry leading
feature specification.
Excdation Excrietion
Excitation
Command
Module
Current Caterpillar is leading the power generation
marketplace with power solutions engineered to
IntegratedVoltage Regulator
deliver unmatched flexibility, expandability,
reliability and cost-effectiveness.
FEATURES WORLDWIDE PRODUCT SUPPORT
When used with an Excitation Module, EMCP 4.3/4.4 • Worldwide parts availability through the Cat dealer
and IVR-compatible EMCP 4.1/4.2 controllers offer: network
• AutomaticVoltage Regulation (AVR) • Over 1,800 dealer branch stores operating in
200 countries
• Programmable stability settings
• The best product support record in the industry
• Soft start control with an adjustable time setting in
AVR control mode • Cat dealers provide extensive post sale support including
maintenance and repair agreements
• Dual Slope, Configurable Under Frequency (Volts/
Hz) regulation
• Three-phase or single-phase generator voltage COMPLETE SYSTEM INTEGRATION
(RMS) sensing/regulation in AVR mode
Fully designed and factory tested to work seamlessly
• Setpoint adjustment from the EMCP display or Cat. with Cat generators using Self Excitation (SE),
ET ServiceTool Internal Excitation (1E) or Permanent Magnet (PMG)
• IVR Operating Status and Voltage Bias Overview excitation systems and EMCP controls.
screens to provide an enhanced level of user
interface
• IntegratedVoltage Regulator event monitoring
EMCP 4.3/4.4 and IVR-compatible EMCP 4.2
controllers also offer:
• Power Factor Regulation (PF)
• Reactive Droop compensation
• Line drop compensation
LEHE0448.00
EFTA00798813
INTEGRATED VOLTAGE
REGULATOR CAT'
INTEGRATED VOLTAGE REGULATOR FEATURE SPECIFICATION
EMCP 4.1 EMCP 4.2 EMCP 4.3 EMCP 4.4
inan4
• •
SPECIFICATIONS
No Load to Full Load Regulation ±0.5% ±0.25% ±0.25% ±0.25%
Configurable Volts / Hz Characteristic • • • •
Configurable Knee Frequency • • • •
Regulator ResponseTime 10 ms 10 ms S ms 5 ms
Single andThree Phase Sensing • • • •
Voltage Adjustment Range
± 30% ± 30% ± 30% ± 30%
(Configurable up to)
CONTROL W
Dual Slope Configurable Volts / Hz
• • • •
Characteristic
Excitation Enable / Disable Selection • • • •
Line Loss (12R) Compensation - • • •
Reactive Droop Compensation - • • •
Power Factor Control Mode - • • •
PROTECTION / ALARMS
Generator Overvoltage • • • •
Generator Undervoltage • • • •
Over Excitation • • • •
Loss of Sensing • • • •
Generator ReverseVARs - • • •
Event Log • • • •
METERING
EMCP AC Metering • • • •
EMCP Power Metering - • • •
Excitation Command Percentage • • • •
Operating Mode Status Indication • • • •
LEHE0448-00
2
EFTA00798814
INTEGRATED VOLTAGE flAT®
REGULATOR
INTEGRATED VOLTAGE REGULATOR FEATURE SPECIFICATION (continued►
EMCP 4.1 EMCP 4.2 EMCP 4.3 EMCP 4.4
• •
VOLTAGE ADJUSTMENT
EMCP 4 Display Voltage Bias • • • •
Digital Input (Raise / Lower)Voltage Bias' • • • •
Potentiometer Voltage Bias' • • • •
AnalogVoltage Bias -Voltage Range' OV to 5V OV to 5V -101/ to +10V -10V to +10V
AnalogVoltage Bias - Current Range' - - 0mA to 20mA OmA to 20mA
AnalogVoltage Bias - PWM Range' - - 0% to 100% 0% to 100%
SCADA (Modbus) Voltage Bias - • • •
'Requires an available input on the EMCP 4.
LEHE0448-00
3
EFTA00798815
INTEGRATED VOLTAGE
REGULATOR CAT'
EXCITATION MODULE SPECIFICATION
The Integrated Voltage Regulator consists of an EMCP 4 interfacing with an Excitation Module. There are a range
of Excitation Modules available to match Cat generator sets.
Figure 1: Figure 2:
EM10 Excitation Module EMI S Excitation Module
EXCITATION MODULE TECHNICAL SPECIFICATION
EM10 EM15
Compatible Generator ExcitationTypes Self Excitation (SE)
Internal Exci ation (IE)
Permanent Magnet (PMG)
Nominal Field Current Output 6 Amps 7 Amps
Maximum (forcing) Field Current Output 10 Amps IS Amps
Maximum AC Voltage Input 180 Vrms 240 Vrms
For more information on the Excitation Module refer to the component spec sheet.
LEHE0448.00
4
EFTA00798816
INTEGRATED VOLTAGE
REGULATOR CAT
EMCP 4 DISPLAY
EXAMPLE SCREENS - EMCP 4.1/4.2
VOLTS / Hz VOLTAGE BIAS OVERVIEW
TARGET VOLT 480 V MANUAL 10.0%
EXCITATION CMD 4.5 % ANALOG 2.0%
Figure 3: IVR Overview Screen
DROOP -2.0%
TOTAL 10.0%
Figure 4: Voltage Bias Overview Screens
EXAMPLE SCREENS - EMCP 4.3/4.4
IVR OVERVIEW VOLTAGE BIAS OVERVIEW
OPERATING MODE: ACTIVE VOLTAGE BIASING:
VOLTS/Hz MANUAL 10.0%
TARGET VOLTAGE 480 V ANALOG INPUT 2.0%
EXCITATION COMMAND 4.5% DROOP - 2.0%
COMPENSATION DROOP
TOTAL BIAS 10.0%
L GENSET I
PAGE
DOWN
GENSET PAGE
UP
Figure 5: IVR Overview Screen Figure 6: Voltage Bias Overview Screen
www.Cat•Electric Power.com
.2013 Caterpillar
All rights reserved
Materials and specifications are subject to change without notice.
The International System of Units (SI) is used in this publication.
CAT. CATERPILLAR, their respective logos, "Caterpillar Yellow", the
"Power Edge" trade dress, as well as corporate and product
LEHE0448.00 (08/131 identity used herein, are trademarks of Caterpillar and may not be
used without permission.
EFTA00798817
EXCITATION MODULE CAT'
EM10
The EM10 Excitation Module is a power
electronics component designed to provide
excitation current to the generator that is
controlled by the Integrated Voltage Regulator
(IVR) feature in the EMCP 4 controls.
Caterpillar is leading the power generation
marketplace with power solutions engineered to
deliver unmatched flexibility, expandability,
reliability and cost-effectiveness.
FEATURES WORLDWIDE PRODUCT SUPPORT
• Over-excitation protection - limit can be adjusted • Worldwide parts availability through the Cat dealer
via a potentiometer (IEXC.) network
• Green status LED indicating unit is powered on • Over 1,800 dealer branch stores operating in
200 countries
• Red status LED indicating excitation current limiting
(flashing) or shutdown (solid) • The best product support record in the industry
• Cat dealers provide extensive post sale support including
When used with EMCP 4.3/4.4 and IVR-compatible maintenance and repair agreements
EMCP 4.1/4.2 controllers, the Integrated Voltage
Regulator system offers:
• AutomaticVoltage Regulation (AVR) COMPLETE SYSTEM INTEGRATION
• Programmable stability settings Fully designed and factory tested to work seamlessly
with Cat generators using Self Excitation (SE),
• Soft start control with an adjustable time setting in Internal Excitation (IE) or Permanent Magnet (PMG)
AVR control mode excitation systems and EMCP controls.
• Dual Slope Under Frequency (Volts / Hz) regulation
• Three-phase or single-phase generator voltage
(RMS) sensing/regulation in AVR mode
EMCP 4.3/4.4 and IVR-compatible EMCP 4.2
controllers also offer
• Power Factor Regulation (PF)
• Generator paralleling with reactive droop
compensation
• Line drop compensation
LEHE0449.00
EFTA00798818
EXCITATION MODULE - EM10 CAT'
SPECIFICATIONS
ELECTRICAL
Generator ExcitationTypes Self Excitation / Internal Excitation / Permanent Magnet (PMG)
Max. Continuous Field Current Output 6 Amps
Max. Forcing Field Current Output 10Amps
Max. AC Voltage Input (X19(2, Z122) 180Vrms
ENVIRONMENTAL
OperatingTemperature Range -40 °C (-40 °F) to +70 *C (+158 °F)
StorageTemperature Range -40 "C (-40 °F) to +85 °C (+185 °F)
Relative HumidityTolerance 95% non-condensing humidity
Salt Spray 5% salt (NaCI) solution for 120 hrs
Vibration 4.5 G-rms, 24-2000 Hz in 3 orthogonal planes
Electromagnetic Compatibility RF Immunity (Radiated & Conducted)
RF Emissions (Radiated & Conducted)
ElectricalTransients
Weight 770 g ± 309
Power Consumption (at Max. Continuous Rating) <450VA
CONFORMITY V
UL Recognized (U.S. and Canada)
UL
File No. E334232
CE Integration Certificate In conformity with the applicable requirements of the following
Standards:
EN 50178
EN 60204-1
EN 61000-6-2
EN 61000-6-4
LEHE0449-00
2
EFTA00798819
EXCITATION MODULE - EM10 CAT ®
OVER-EXCITATION PROTECTION
• If a short-circuit fault occurs at the generator terminals, the EM10 will allow the excitation current to rise to the
upper limit value set by the adjustment potentiometer (max. 10 Amps).
• The excitation current will be clamped at the upper limit value for 10 seconds (fixed internally).
• After 10 seconds, the excitation current is reduced to a value of 10% of the potentiometer setting.
Excitation ;IL
Current IAl
Excitation Current
Upper Limit
(adjusted using a
Potentiometer,
Maximum 10 Amps,
Minimum 4 Amps)
Shutdown Level
Excitation Current
10% of Upper Limit Shutdown Level
(fixed internally, no adjustment)
Time (s)
10 seconds
(fixed intemally, no adjustment)
LEHE0449-00
3
EFTA00798820
EXCITATION MODULE - EM10 CAT'
OUTLINE DRAWING Dimensions in mrn
115 65
p,m110 £P
.r000
a
0o
0
0 0
I 6'
. .
[OEN i
0
tiOi] I
" I
I1 1I lit i 6 iii
LEHE4444430
4
EFTA00798821
EXCITATION MODULE - EM10 CAT'
EXAMPLE CONNECTION DIAGRAM (Permanent Magnet Excitation)
EMCP 4.314.4
1209^Cant
MY Culprla
Stall ROM Mono
IS 21
EMCP 4.114.2
l0oliCarrwol
Ban Nowise 9.111 ‘s;a1..
Spa Pasant sets
HD ocES a 60a 65
II X2
• Z1
,--
cs ii (9 • )(1
CS • e 22
ill
• F•
O
• F.
L/1
• •
a 'NOV
2-vny Conran/ Factions
Tama Land fadipc
P24 F. ca Fre Asa 0.nut
P2-2 F- En*. Fen Itoatwe 044 FIELD
lacy Connecter Functions ARMATURE
Tema Land Ewan
.--MSIMIlilaralabialall
P3-2 CS. Exam Canna Pave Iron
P3-3 CS- Earan Card War host
Icy Connector Functions LPIIG Esc 'anon] 4-va Co mica Functions Salf-Exalaakm Comedy( F unctions lima lExciation):
;mann Labs Function Tainal label Function Talnal Label Function
R1-1 /0 Eascn Pea Supply npn ‘Pl13 Mate 81 P4-1 X2 Exoexa Pose Sarnia anlarcbasr/ P4-1 g Examen Par &pair ban (Asx ?trim9 I - Pea)
F4-2 Z1 Na Drrad P4-2 21 AnCarnecan P4-2 Z1 Eamon Poe Slapply Input (AnWneling 2- Rana)
F4-1 X1 Ennaa PowerSony nAlt(P610Ftese Al P4-3 X1 kaaincn Pawn Swab/ Iroutlanielabasel P4-3 X1 /anon Paw Salv IroAlAaxYlmdem1- Wave/
F4-4 Z2 Exam Paver Soda nonlIpteR•am 0 P4-4 22 Nx Dona P4-4 Z2 Eamon Poser &any InenlAxYlan 2- anal
www.Cat-Electric Power.com
02013 Caterpillar
All rights reserved
Materials and specifications are subject to change without notice.
The International System of Units (SI) is used in this publication.
CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow", the
"Power Edge" trade dress, as well as corporate and product
LEHE0449•00 (08/13) identity used herein, are trademarks of Caterpillar and may not be
used without permission.
EFTA00798822
Attachments
CM®
Coolant Heater (WHH)
Appropriate when the generator set is to be
sited in a low ambient environment, the heater
maintains the engine coolant at a temperature
[typically 38°C (100°F)] which facilitates rapid
starting and load acceptance. The heater
assembly uses UL compliant components (to
UL1030) and has CSA certification which is to
both CSA and UL Standards.
The heater itself is powered by a 110/120 volt
(VAC 120) AC auxiliary supply protected by a
safeguard breaker inside the main control panel.
A thermostatic controller is included to regulate
the output temperature to within safe limits. When
the generator set is not running the heater is
automatically connected to the AC supply through
a power relay mounted in the control panel.
Upon receiving a start signal the AC supply is
automatically disconnected by the power relay
and automatically reconnected when the start
signal is removed and the engine has stopped.
Features
• Molded from Polyphenylene Sulphide
c recs. enc.
• Rust free, corrosion resistant with exceptional
tensile strength
• Vibration and shock tested to extreme limits to
ensure durability
wwr
• Compatible with all coolant additives 14•In.r
• Incoloy element for longer service life IONLA [CLAY
can 4
MCA WW /14 MM SU
Stan
VAC 120
Diesel Generator Set Engine Models Nominal Coolant Heater Power Consumption (Watts)
C2.2, C4.4, C4.4 ACERT' 1000
C7.1 ACERT 1800
Gas Generator Set Models Nominal Coolant Heater Power Consumption (Watts)
DG30-2, DG50-2, DG60-2, DG80-2 1000
DG100-2, DG125.2, DG150-2 1800
www.Cat-ElectricPower.com
©2018 Caterpillar
M rights reserved.
Materials and specifications are subject to change without notice.
CAT. CATERPILLAR, their respective logos, *Caterpillar Yellow*,
the tower Edge" trade dress as well as corporate and product identity used
LEHE4035-07 (097181 herein. are trademarks of Caterpillar and may not be used without permission.
EFTA00798823
Circuit Breakers
Manually Operated Circuit Breakers for 40 — 200 ekW
Diesel Generator Sets
Number
Interrupting Ratings
kA nns Lugs
1
Current of Auxiliary
(A) Frame Poles 240V 480V 600V Trip Units Size # per phase Options
30 T1N 3 50 22 10
40 T1N 3 50 22 10
50 T1N 3 50 22 10
60 T1N 3 50 22 10
14 AWG-1/0 1
70 TIN 3 50 22 10 1 Form C
+1
80 T1N 3 50 22 10 Thermal Bell Alarm
90 T1N 3 50 22 10 Magnet
Shunt Trip
100 T1N 3 50 22 10 12VDC
125 T3N 3 50 25 10
150 T3N 3 50 25 10
4 AWG - 300 1
175 T3N 3 50 25 10 kcmil
200 T3N 3 50 25 10
225 T3N 3 50 25 10
250 T4N 3 65 25 18 6 AWG 350 kcmil 1 1 Form C + 1
Electronic Bell Alarm
400 T5N 3 65 25 18 3/0 — 250 kcmil 2 250VACNDC
LS/l (S or I)
600 T6N 3 65 35 20 2/0 —400 kcmil 3
Shunt Trip
800 T6N 3 65 35 20 2/0 - 400 kcmil 3 12VDC
LEHE0469-04 Page 1 of 3
EFTA00798824
D40 — D200 Range (C4.4 & C7.1)
First Breaker
L
Second Breaker
CATg
■ Circuit Breaker Size (A) i Circuit Breaker Size (A) —. Mr
50 100% UL 30 100% UL
60100% UL 40 100% UL
70100% UL 50100% UL
80100% UL 60 100% UL
90100% UL 70 100% UL
100 100% UL 80 100% UL
125100% UL 90100% UL
150 100% UL 100100% UL
175 100% UL 125 100% UL
200 100% UL 150 100% UL
225 100% UL 175 100% UL
250 100% UL 200100% UL
400 100% UL 225 100% UL
600 100% UL 250 100% UL
800 100% UL
Available Breaker Configurations
First Circuit Breaker Second Circuit Breaker
T1 T1 13 T4
T3 T1 13 T4
14 T1 13 T4
T5 T1 13 T4
T6 T1 13 T4
LEHE0469.04 Page 2 of 3
EFTA00798825
CAT'
L
D40 — D60 LC Range (C4.4 LC)
First Breaker Second Breaker Third Breaker
Circuit Breaker Size (A) Circuit Breaker Size (A) Circuit Breaker Size (A)
50A 50A 50A
100A 100A 100A
150 A 150 A
225A
250A
w
Available Breaker Configurations
First Circuit Breaker Second Circuit Breaker Third Circuit Breaker
T1 - -
T1 T1 -
T1 T1 T1
T3 - -
T3 T1 -
T3 - -
T3 T1 T1
T4 - -
T4 T1 -
T4 T1 T1
www.cat.com/electricpower
©2017 Caterpillar
MI rights reserved.
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, their respective logos, 'Caterpillar Yellow',
the Tower Edge" trade dress as well as corporate and product Identity used
LEI-1E0469-04 (06/17) herein, are trademarks of Caterpillar and may not be used without permission.
EFTA00798826
CIRCUIT BREAKERS
CAT®
Molded Case
Circuit Breakers:
30A -1200A
40 kW — 600 kW Gensets
Picture shown may not represent actual package
Features Conformity with
International Standards
• 100% UL Listing
• Thermal Magnetic Trip Units (Frames TIN and The TIN through T6N and T7S/T7M-S Frame
T3N) Circuit Breakers have been designed to comply
• Electronic Trip Units (Frames T4N, TSN, T6N with these major standards:
& T7S/T7M-S) • UL 489
• Double insulation • CSA22.2 No.5
• Clear indication of breaker status • IEC 60947-2
• Can be used in normal operation in an
ambient of —25° C and +70° C
• Auxiliary contacts available
• Insulating case constructed from fiberglass
reinforced synthetic resin
• Anti-corrosion treatment on all metal parts
• Optional Dual Circuit Breakers
LEHE0470-02 (06/18) Page 1 of 16
EFTA00798827
CIRCUIT BREAKERS
CAT®
Manually Operated Circuit Breakers
Current Frame Number of Interrupting Ratings Trip Units
(A) Poles (kA rms)
240V 480V 600V
30 TIN 3 50 22 10
40 T1N 3 50 22 10
50 TIN 3 50 22 10
60 TIN 3 50 22 10
70 TIN 3 50 22 10
80 TIN 3 50 22 10
Thermal
90 TIN 3 50 22 10
Magnetic
100 T1N 3 50 22 10
125 T3N 3 50 25 10
150 T3N 3 50 25 10
175 T3N 3 50 25 10
200 T3N 3 50 25 10
225 T3N 3 50 25 10
250 T4N 3 65 25 18
400 T5N 3 65 25 18 Electronic
LS/1(S or I)
600 T6N 3 65 35 20 Or
800 T6N 3 65 35 20 LSI
1200 T7S 3 65 50 25
Electrically Operated Circuit Breakers
Current Frame Number of Interrupting Ratings (kArms) Trip Units
(A) Poles
240V 480V 600V
800 Tflol-S 3 65 50 25
Electronic
LSI
1200 TMI-S 3 65 50 25
Electronic LS/I Trip Units offer LS or LI Protection
L-I Mode
• Long Time / Overload Protection, "V has an adjustable trip threshold and adjustable time delay
• Instantaneous Short Circuit Protection, "l has an adjustable short circuit trip threshold and once
exceeded will cause the circuit breaker to trip instantaneously
L-S Mode
• Long Time / Overload Protection, "L' has an adjustable trip threshold and adjustable time delay
• Short Circuit Protection. "S" has an adjustable short circuit trip threshold and adjustable time delay if
necessary for coordinating with downstream loads
• Instantaneous Short Circuit Protection, "r is still included, but the threshold level is not adjustable and
exists at a predetermined level
Electronic L-S-I Trip Units
• Long Time / Overload Protection, "V has an adjustable trip threshold and adjustable time delay
• Short Circuit Protection, "S" has an adjustable short circuit trip threshold and adjustable time delay if
necessary for coordinating with downstream loads
• Instantaneous Short Circuit Protection, has an adjustable short circuit trip threshold and once
exceeded will cause the circuit breaker to trip instantaneously
LEHE0470-02 (06/18) Page 2 of 16
EFTA00798828
CIRCUIT BREAKERS
CAT®
T1 100 -TMF
In = 15 770A
t[s]
104 --... -------..
.---.....
.,.m m.....
MME
------------
mm....i
MM:• : M=MM•
mm.....
103 Min • IiiiiiiiiMiiiiiiii
mr, maaillEi. waEmaili
------ -------Mmsaiiii•
M=MEMMI M=MME• ==••••
IllM ...•••. M MMEEMInMM•EMI
II
Mi.
' M=MMENIIII 1=MMEMIll =MMEN011
100 MEMIIIIIII
,--MMEEEEEM
WIIIIIMEN111111
-IMMEEIN MME EI
1 ======2::=
M=MEN• lk
CIhJ!
MM=MEN• M=MME•
E=
ECI
=MMEMEM NEMMEME nMEEME
=MMEMIll k ' ‘IMIII =MMEM011
10
mmmmoss mmi, , ‘Enmmsom
=MMENIII =MM■. `MMENNIII
MEMESSIE MEMESEET-
w=mmownse mmmENNE lik,
MiniiiiiMMENIMillL.
MEEEEIBE====EBEi r9EM MEE
IIII
im im mujimminnim Nd,erj aiglig
10 3
0-, 10 02
xll
LEHE03170.02 (WM) Page 3 of 1I3
EFTA00798829
CIRCUIT BREAKERS
CAT®
T1 100 - TMF
I n = 80 =100A
10-1
•
10-2
0-1 10 01
XI,
LEHEN70-02 (06,18) Pegs 4 of 1I3
EFTA00798830
111111•1-
T3 225 — TMF
In = 125 111225 A
1 M=MMENE M=MMENN
==MMENIII =MMENIII
mirr=mnson
'
mmENENN Nom
=MMEMAI
mmmENNE
=M1h,
======c2 —=mmEiii 6 MMESEESE
mmmENNE MMMEW-- MMMENNI
=MMENI. MMENIII
=MMIIIIII= =MMIIIII!
=SIMI
=MINIING=1.1.11IIIII MENNE
10 102
xi,
LEHE0,110.02 (MIS) Papa 5 of 16
EFTA00798831
CIRCUIT BREAKERS
CAT®
T4 250 / T5 400 - PR221DS
L-I Functions
Note: For T5 In 600 A kJ 13max = 9.5 x In
t [s]
104
==411 0.4.0.440.49-0.52-0,56-0,6-0,64-0,68-0,72.0.760,84,844.884,924196.1
1,5 2 25 3 35 45 55 65 7 75 8 85 9 10.
4,1F
103
I II
102
10
102
=MMNN;;
••••••••••••••••••IMPIMP.I••••
10-1 ME711111
•IMIMIIIIMIN•
10-2
104 MENEM
10-1 1 10 0
x In lu [kA]
LEHE0470-02 (06/18) Page 6 of 16
EFTA00798832
CIRCUIT BREAKERS
CAT®
T4 250 / T5 400 - PR221DS
L-S Functions
Note: For T5 In 600 A El 12max = 9.5 x In
t [s]
104
74Tril 0,4-0,44-0,48-0,52-0.56-0,6-0,64.0,68.0,72-0,76-0,8•0,84-0,88-0,92-0,96-1
al
ISBEICEIMIEMBEIDEIElla
103 G
41 --
102
L
41
10
102
1
10.1 T4 5
10-2
10.9
10.1 1 10 10
x In lu [k/1]
LEHE0470-02 (06:18) Page 7 of 16
EFTA00798833
CIRCUIT BREAKERS
CAT®
T6 600 / 800 - PR221DS
L-I Functions
t isl
104 4:3
[t 4
102
10
02
I
10.1
10.2
10-3
10.1 10 10
x In I [kA]
LEHE0470-02 (06/18) Page 8 of 16
EFTA00798834
CIRCUIT BREAKERS
CAT®
T6 600 / 800 - PR221DS
L-S Functions
[s]
o4 4:0
31.* ►
Ci
10;
Ci
CI
.....
102
I
10 -
02
10.1
10.2
10-3
10.1 10 10
x In I [kA]
LEHE.I70-02 (06(18) Page 9 of 16
EFTA00798835
CIRCUIT BREAKERS
Tmax T7 PR2 31/P Functions L -I Trip curves
10000
t [s]
1000
a
100
10
1
U
01
0 01
0.001
01 1 10 100
x In
LEHE0470-02 (06118) Page 10 of 16
EFTA00798836
CIRCUIT BREAKERS
CAT®
Tmax 17 PR231/P Functions L-S Trip curves
10000
= L Fag . 4 ============
.
t [s] —ImommamM• nmmom mm•NE
ME =MENEM fl MMEEN M=MMENN
1000
--------
imummum _sum
ME lag.IMENN h..`91 MMIMIMMEN
100 IMININISPIII=1211M51111531 MINEMEIll
10
ii.7(16.7.1.0.1 1.711101••••
----IM=MM
MEMEMMINI=MQ3.00
=—===
==a=Mini; ENNUI
01 =MUM
M=IMM
==EEggi ff 2iti
M=MME•
0 01
—====== — =ZZ.,E;; ;NoWalTarolii
0,001
0.1
=MUM
10
ES 100
x In
LEHE0470-02 (08/18) Page 11 of 16
EFTA00798837
CIRCUIT BREAKERS
CAT®
T4 250 / T5 400/600
PR222DS/P and PR222DS/PD-A
L-S-I Functions (I2t const = ON)
Note: For T5 In = 600 A l2max = 9.5 x In, l3max = 9.5 x In
t [s]
104 , --==—===_
.-- -",—.--,_=—=== • , .142-0.44-0.46-0.40.5-0.52-0.54-0.56-0.58-0.6.0.62.0.64.0,66.0.68. = _-gg-
• Iii_ ----.••••
MN .--0.724,74.0,76.0,78-0,80,82.0.840.86.0.88.0,9-0.92.0.$44/96.0,98.1 MWM1 ''
im
li. 1n MI
iMP7giii
===MI
m..i..iini.
11Plm r.
■~ WWII
— ===[ NE
103 "- M.
===== IMM
I I-.. .
IMl=. .= •••••••
A Ellin
r- ImImmm•
IM=MME= ,II M= NI M IMINII 01=1. l===.•
=P7 I. I•Z‘MIIMININIIM NOIMINM- 1- 71- "MMIIIMEINII 4=MMENI
MillmIMMME PIOIIIIN 00. 11LIJLAIN IIIIIIIMIMMLIMMIll
102 r 7._ I 9.50 POI IIIIIIIII.S'OMAIIII
.-1. , -...-77=..:
=.:
......—. ill -•••:i=m;-iEEE=
--, --- , —=., , mm.•
moih. .= zlt—ImENEN
=MMINIkb,.
10 El 4411 IIII
I1 P I•lliiii
I . .1=' ,EE—
=
. k il41 --= =kaaill
• II 102
■ mm.ISIIIIM
1
m... - i r u —=;Tg::
fl .... = =non
-"; Mill I'il
=MMENNI =M MI M I: II
104 IIIII . NEW III
---........=..
______________ mItiiiiil 111
---...•----
mm....II mm
milmim . ■
=MIR III
10-2 --= mEtt, '"II
— I ====.:
i nmmm.... i mimn...•n mmoul:
MIMMMEI IMMIIMMIll I =MINIIIII
104 IIIII Mill II11TH
10.1 1 10 0
x in in [kA]
LEHE0470-02 (06118) Page 12 of 16
EFTA00798838
EFTA00798839
9l 1o£ I .6ed (8 L90)£0.04.1.03H31
l'DI
C-0
...
monimumu,—.i
..m ; :,.. .. I.
iiiiiii -AL I I II I' lli ; ki MEM
onsEmr-inm sii I i in Nioi, :•111011 :IM=
•Nommmi-ii 1111 I IAN& 11 IMMIE1611MI=
:22 ! -- ..! :I!!!!!IVA Mlipr..?.
4...7 'UniZ.:i?M -_---
04 NI .z
iiiiiina iiiiiiiIIIIIIii \ -. h. I
MEM= IMIIIIIIIIIIIIIRmloilmuikaakonsoitsmm
...ml .i Num -; I I I-•.......!!!!!...45 U —im
=._' .11., ..:I. ..... :,..
EMM:MMIlli iiii1EMIEEMES EBSEESIEM=ML:a'
ilsoriTTT :: _:' :'TTrrlx- 33:FE:Ammo:AI
litatr96.016.016.0.6.012.018.0-48.0.Z8.0 .01t0lL'0lt011.0-1:0
..„,-
"89'0,19.0.69'0.t9V9V-IT0.950.110-6'0-50-810-94'0.W0-Z4*01•0
EZEMEM===
[911
ul X 9.6 = xetin 'ul X g*6 = XewZl G V009 = ul e3oN
(jjO 1SUO0 sumound I-S-i
V-ad/SOZZZad DUe d/SCIZZZlid
009/00t7 91 / 09Z VI
SHDIVRIEILIn0aI0
CIRCUIT BREAKERS
CAT®
===griiE
r7'7°I L Ennio
""r-
-EEEEEEEE
MI
MIWWIIMOMESITrIMITM19
Mani
=====NT.1===7,=,WZMZEIZ
iii
MMENNii ==MMENii
MEEEEEE MEEEEEE-
IMI=MMUNI MHZaiiiii
LEHE04Z0-O2 (06/111) Page 14 of 16
EFTA00798840
CIRCUIT BREAKERS
CAT®
T7 1000/1200 - PR232/P
L-S-I Functions
t Is]
10,
• •
—I-
4S1
103 421
42
I r.
102
— k/I1
10
102
t=k
10.1
17 S. I.L
10.2
10.3
10-1 10 10 102
xIn I[kA]
LEHE0470-02 (06118) Page 15 of 16
EFTA00798841
CIRCUIT BREAKERS
CAT®
Electrically Operated Circuit Breakers
T7 1000/1200 - PR332/P
LS I Func:cms
10.
a
is
101
0
10 4
10
10
"O2018 Caterpillar All Rights Reserved."
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow" and the "Power Edge" trade dress, as well as corporate
and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
LEHE0470-02 (06118) www.Cat-ElectricPower.com
EFTA00798842
Controls
CAT
GROUND FAULT RELAY
(GFR)
4, 1 11.111
(
• • S • S'
0 ; .;
Trcr PfCIT)
Picture shown may not reflect actual configuration
GENERAL DESCRIPTION
GFR is a microprocessor-based ground-fault relay for resistance- and solidly-grounded systems.
In addition to common systems, it is uniquely suited for use on systems with significant harmonic content.
GFR can provide main-plant protection, feeder-level protection, or individual-load protection.
Proper current transformer selection provides the desired pickup range. The output contacts can be
connected for use in protective tripping circuits or in alarm indication circuits. The analog output can be used
with a PLC or a meter.
FEATURES & BENEFITS
Benefits Features
• Trip setting based on input CT primary, allows • Adjustable pickup (1-99%)
use with any CT. Minimum 50 mA with EFCT • Adjustable time delay (50 ms - 2.5 s)
Series. • Output contacts
• Adjustable trip delay allows quick protection and • Analog output (0 - 5 V)
system coordination • CT-Loop monitoring
• Form A and Form B ground-fault output contacts • Selectable DFT or peak detection filtering
for operation of separate annunciation and trip • Harmonic filtering
circuits
• Non-volatile trip memory
• Alarms when CT is not connected
• Microprocessor based
• Compatible with variable-speed drives
• Universal power supply
• Eliminates nuisance tripping
• Retains trip state while de-energized to simplify
troubleshooting
• No calibration required, saves on maintenance
cost
• Allows operation in application where one side
of PT is faulted, provides flexibility for numerous
applications
LEHE1236-00
EFTA00798843
Controls
CAT
FRONT-PANEL CONTROLS
Ground-fault trip level Front-panel indication
The % CT PRIMARY selector switches are
used to set the ground-fault trip level as a • Power
percentage of the CT-primary rating. The green LED labelled PWR indicates the
In tripping systems, a ground-fault trip level of presence of supply voltage.
10 to 20% of the prospective ground-fault
current is often used. In alarm-only systems, • Trip
a value of 50% of the prospective ground- The red LED labelled TRIP indicates a trip. A
fault current is often used. To avoid solid red LED indicates a ground-fault trip. A
sympathetic tripping, the trip level must be flashing LED indicates a trip initiated by a CT
above the charging current of the protected fault. Two fast flashes indicate a diagnostic
feeder. trip.
A 0% selection provides protection at 1%.
Self diagnostics
Ground-fault trip time A diagnostic trip is indicated by two fast
GFR has a definite-time trip characteristic. flashes of the TRIP LED. It can be caused by
The TIME (s) selector switch is used to set a diagnostic problem detected by the
the ground-fault trip delay time for watchdog timer or from an incorrect reading
coordination with upstream and downstream from non-volatile memory. Press RESET or
ground-fault devices. Coordination requires cycle supply voltage.
the same trip level for all ground-fault devices
in a system and the trip time to progressively • Trip inhibit
increase upstream. The amount of equipment The yellow LED labelled INHB indicates that
removed from the system will be a minimum if output relay operation was inhibited during a
the first ground-fault device to operate is the high-current ground fault. When a ground-
one immediately upstream from the fault. fault trip occurs during a high-current ground
fault, both the TRIP and INHB LED's will be
Reset ON. Inhibit indication is reset when the
If the Reset Mode switch is in the LATCHING ground-fault trip is reset. Inhibit operation and
position, a trip remains latched until the indication will not respond if the trip-inhibit
RESET button is pressed or the remote-reset switch is in the OFF position.
terminals are momentarily connected. In the
non-fail-safe mode, cycling the supply voltage
will also reset the GFR. SPECIFICATIONS
If the Reset Mode switch is in the • IEEE Device Numbers - Ground fault
AUTORESET position, a trip will reset when (50G/N, 51G/N)
the fault is removed. The reset circuit • Dimensions
responds only to a momentary closure so that o H 75 mm (3.0")
a jammed or shorted button will not prevent a o W 55 mm (2.2")
trip. The front-panel RESET button is o D 115 mm(4.5")
inoperative when the remote-reset terminals • Trip Level Settings - 1-99% CT-Primary
(6 and 7) are connected Rating
Test • Trip Time Settings - 0.05-2.5 s
The TEST button is used to test the ground- • Contact Operating Mode - Selectable
fault circuit, the indication, and the output fail-safe or non-fail-safe
relay. When the TEST button is pressed for • Output Contacts Isolated Form A and
one second, a test signal is applied to the Form B
ground-fault-detection circuit, the circuit will • Approvals CSA certified, UL Listed
trip, the TRIP LED will light, and the output (E340889), CE (European Union), C-
relay will operate. If high-current inhibit has Tick (Australian)
been selected, the INHB LED will light.
• Analog Output 0-5 V
LEHE1236-00 2
EFTA00798844
Controls
CAT'
OUTLINE AND MOUNTING DETAILS
CONFIGURATION
SWITCHES
8.7
(0.34) r 55.0
(2.17)
37.5
(1.48)
5 AtIT0NESET NOTE 2
Rem woe ' Arne.°
FILTER SEtECTI0N 4 Meaeicv
RMCY P
mE0UE
CTVERIFCAlI0N CiF I 13 ON
TRIP 'NNW Off I 12 ON
RELAY OPERATING MOE
FAL.WE LLJ1 xCNAMLEMI
NOTE 5 •
MOUNTING DETAIL
118.0 (NOTE 3)
(4.65)
TOP
55.0
(2.11)
OROUNO.FAUlT INOWIOR
iNria IP?
%Cr rlOmANY
0
I
• • • • • • • •
FRONT SIDE
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. MOUNTING SCREWS: M4 OR 8-32.
3. OVERALL DIMENSION WHEN MOUNTED ON
DINEN50022 35 mm x 7.5 mmTOP-HAT RAIL.
4. ADJUSTMENT KNOBS ARE REMOVABLE.
5. CONFIGURATION SWITCHES SHOWN IN
DEFAULT POSITION.
BOTTOM
Materials and specifications are subject to change without notice.
CAT. CATERPILLAR, their respective logos. 'Caterpillar Yellow." the Power Edge" trade dress as well as corporate and
product identity used herein, are trademarks of Caterpillar and may not be used without permission.
catcomfelectricpower
LEHE1236-00 (02/17) er2o17 Caterpillar
All rights reserved.
EFTA00798845
ATTACHMENTS .11111 CAT®
UL 10 AMP BATTERY CHARGER
60HzOnly
This battery charger offers accurate, automatic charging
of lead-acid and nickel cadmium batteries. The output
voltage automatically adjusts to changing input, load,
battery and ambient conditions. This prevents battery
over-charging and consequent loss of battery electrolyte.
Standard features include AC line compensation,
precision voltage regulation, current limiting, automatic 2-
rate charging, voltmeter and ammeter, temperature
compensation and UL Listing.
The user interface is easy to understand with digital
metering, NFPA110 alarms and a battery fault alarm.
Pictureseownmaynotrepresentacwai una.
Specification Features
Input Supply 110-120 V • Electronically current limited at 105% of
208-240 V rated output.
AC and DC Fuse 2 input and 2 output Output • Alarm system
Voltage 12V • Lightning and voltage transient
protection
Frequency 60Hz
• Protection of connected equipment
Operating temperature -20°C1 -4°F) to 60°C(140°F) against load dump protection
Housing constructed of rustproof anodized aluminum. • Constant voltage, current limited, 4-rate
automatic equalization
• IP20 housing
Standards • AC isolated from DC
• C-UL listed to UL 1236 • Temperature compensation
• On board temperature sensor with
• NFPA 70, NFPA 110
remote port
• CSA 22.2 No 107 certified
• UL 1564
• CE DOC to EN 60335
• IBC Seismic Certification
LEHE01434)2 Page 1/2
EFTA00798846
ATTACHMENTS W®
Output Input
Amps Volts Hz Volts
110 -120
10 60 208 -240
Width Depth Height Weight
165mm (6.5 in) 125 mm (4 9 r 300 mm .8 In) 2.1 kg (4.61b)
Feature Code: PBC1ONU
LED Indication
In normal operation, the fourcircuit board LEDs indicate operating status: fault conditions, charge mode, temperature compensationandAC
supply.
LED Operation Status
• Red on Fault condition (except AC supply & battery connection errors)
flashing slow AC Supply not available (DC connected)
flashing fast Battery connection error
off No fault conditions
• Yellow On In float mode
flashing slow In autoboost mode
flashing fast In AutoBoost extension mode / boost decay
off Output off /output to nominal
• Blue on Temperature compensation active
flashing slow Temperature compensation auto disabled due to external fault
flashing fast Temperature compensationat absolute limit Le. circ or >+5O'C
off Temperature compensation disabled
• Green on AC supply available, charge output on
flashing slow ACsupply available, charge output off
flashing fast Boost decay or battery missing lit red LED is also on)
off ACsupply not available
Information contained in this publication may be considered confidential. Discretion is recommended when distributing. Materi3ls and specifications are subject to
change without notice. CAT. CATERPILLAR, their respective logos, 'Caterpillar Yellow," the -Amer Edge" trade dress as well as corporate and product identity used
herein, are trademarks of Caterpillar and may not be used without permission.
www.Cat.ElectricPower.com
02017 Caterpillar
All Rights Reserved.
LEHE0143-02 Page 2/2
EFTA00798847
World's Toughest Batteries
Premium High Output — Maximum Vibration Resistance
.. - ...
caa car • Vibration Resistance...five times the Industry Standard
--- ".... •
.......„, • Exclusive "flat top" BCI group 4D & 8D batteries are Maintenance Free
and have the industries highest cold cranking amps (CCA)
-Maar
4 -- • Popular BCI group 31 Maintenance Free batteries with industry leading
. -.'
MEra cold cranking amps...up to 1000 (CCA), for electric power, machine or
on-highway truck and bus applications. Deep cycle models available for
CAT
ar truck, marine or recreational usage
Specifications for Cat Premium High Output Batteries — Available Worldwide
Nominal Weieht
BO Cold Restive Amp Hi Add Water BCI Owrall ninimmton, Satinet
Onus Cranking Capacity Capacity Maimenaoce Leap& Milk Hair Wet Dry Acid toFIN
Sin Part No. Amps' Millt(Of Volts a20 His. Construction Check Hems In Urn In60W la laiml Lb Ng) n(k0) et oiled
8D 1515720 1500 465 12 210 C ME 20.47 15201 10.8 12751 9.7612181 132 (60) — —
8D 101.000 1400 400 12 190 LAC+ 1000 20.7 152651 10.9642781 9.760181 132 (60) 86 (39) 18.0 117.01
ID 153-5710 1400 425 12 200 C ME 20.47 15201 8.58 12181 9.7612181 119 (54) - -
ID 153-5700 1125 305 12 145 C ME 20.47 15201 8.5812181 9.7612181 101 (46) - -
4D 98-9730 1300 400 12 190 LAC.. 1000 20.7515271 8.5812181 9.7612181 119 (54) 81 (37) 14.8 114.01
4D 98-9720 1000 275 12 140 LAC.. 1000 20.750271 8.5812181 9.7612181 101 (46) 59 (27) 15.9 115.01
31 175-4390 1000 180 12 90 CS MFA 12.9 028.41 6.74117121 9.290361 60 tin - -
31 175-4370 825 190 12 100 CA** MFA 12.9 028.41 6.74117121 9.290361 60 (27) - -
31 175-4360 710 185 12 100 C/S"' MFA 12.9 028.41 6.741171/1 9.290361 60 (27) - -
31 250-0480 710 186 12 100 morn MF 12.9 028.41 6.74117111 9.290361 60 (27) - -
31 115-2422 1000 170 12 90 C SAE MFA 12.9 1328A1 6.74117121 9.461240.31 60 On - -
31 116.2421 950 170 12 90 C SAE + MFA 12.9 028.41 6.74117121 9.461210.31 60 (27) 44 (20) 6.6(6.3)
31 98-3404 950 165 12 100 C SAE ME 13 (33011 6.77 11721 9.461740.31 58 (26) - -
31 3T-5760 750 165 12 100 C SAE ME 13 (33011 6.77 11721 9.461740.31 55 (25) - -
24 153-5656 650 110 12 52 SC MF 10.981278.91 6.85 11711 9.0 123.11 39 (18) - -
65 230-6368 880 140 12 80 SC MF 11.9 130&41 7.5 (190.81 7.5 1191.41 45.5 121) - -
74 153-5660 650 110 12 52 SC' MF 10.98127891 7.0(17821 8.15120891 39 (18) - -
58 175-4280 500 70 12 35 SC MF 9.961253.11 7.2 08151 6.911761 31 (14) - -
2 153-5690 765 210 6 90 LAC+ 1000 10.2112601 6.8(173) 8.72 1n1.61 37 071 22 (101 4.8 (4.5)
Construction Notes:
LAC = Low Maintenance. Hybrid Construction Ir- Rugged Design - Built Tough - Reliable Starting
C = Calcium Lead Alloy Grid Design
MF = Maintenance Free • Positive and Negative plates are anchored to container bottom and locked at
MFA = Maintenance Free with Accessible Vent Caps the top of cell clement for maximum vibration resistance.
S = Stud Terminals • Heavy-duty forged terminal post bushings provide maximum strength and
+= Shipped Dry Only resistance to acid seepage.
• = Side Terminals
•• = Starting and Deep Cycle Battery • Hefty full-frame grids. no sharp edges. optimum acid/paste combination
••• = Deep Cycle and Starting Battery provides better charge acceptance after deep discharge.
" = For 30 seconds at 0° F (-18° C)
' = Minimum of 25 amp output at 80° F (27° C) • Manifold vented cover with built-in Flame Arrestor...a safety feature that
SAE = Uses SAE Posts directs corrosive gases away from the battery and hold-downs.
SOT = Dual. Top mounted Terminals. Stud and SAE Post. • Thick. robust container resists lugged treatment typical of heavy-duty
Marine Deep Cycle/Starting Battery commercial use. Embossed pan number & descriptors for easy
SC = Silver (Ag) Calcium Alloy Grids for resistance to high serviceability.
underhond temperatures
2
EFTA00798848
ATTACHMENTS CAI
ULCERT
UL 2200 LISTING
LISTED
INCLUDES THE FOLLOWING: ELECTRICAL OPTIONS
The table below shows electrical options that meet
ALTERNATOR UL requirements:
Alternator insulation system is UL Recognized (UL 1446).
PMG and AREP alternators are available. Automatic EBH Battery Heater
voltage regulators are UL Recognized. EOS Lube Oil Sump Heater
WCA1 Low Coolant Level Shutdown
WIRE HARNESS
AC, DC, and power harnesses are made with UL Listed WSS1 Low Coolant Temperature Alarm
wire and UL Listed terminals. Al-Ill-I Anti-Condensation Heater
WHH Coolant Heater
CONTROL PANEL
Control panels are comprised of UL Listed and UL GOVE5 Electronic Governor (Fully Adjustable)
Recognized components. EMCP is UL Recognized. FSS1 Critical Low Fuel Level Shutdown
FSS2 Low Fuel Level Alarm
CIRCUIT BREAKER
Output circuit breaker is 100% rated and UL Listed. FSS5 Critical High Fuel Alarm
PBC5UL UL Listed Battery Charger
TESTING PBC10NU NFPA Battery Charger, UL Listed
All UL Listed sets are designed and rigorously tested in
accordance with UL Standard for Safety, UL 2200. UL Listing is available on all diesel fuelled generator sets up
to 175 kW at 60 Hz, 600 vac maximum.
LABELING
Labeling meets UL requirements.
MECHANICAL OPTIONS
Mechanical options do not require UL Listing and,
therefore, are not affected. The exceptions to this are:
FUEL TANKS
If a fuel tank is ordered with the unit, it must be
UL Listed. Two versions are available: 24 hour integral
(FCUL2) and 24/48 hour sub-base (FSBT)
ENCLOSURES
Factory installed enclosures meet UL requirements.
Weatherproof and sound attenuated versions are
available.
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, their respective logos. 'Caterpillar Yellow," the 'Power Edge" trade dress as well as corporate
and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
www.Cat-ElectricPower.com
O2013 Caterpillar
All Rights Reserved
LEHE0410-00 (01/13) Printed in U.S.A.
EFTA00798849
Warren CAT
WARREN CAI 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
SECTION V
MECHANICAL DRAWINGS
NUMBER TITLE PAGE
460-0870 A Installation - Composite 1 of 2
C7.1 ENCL SA L1 & L2 W/O FT
460-0870 B Installation - Composite 2 of 2
C7.1 ENCL SA L1 & L2 W/O FT
EFTA00798850
I Mirea .1.460-0870
3658.5 (144.03) Ott ENGINE CONNECTIONS SIZE SHEET
0s£RALL LENGTH CCOLAIIT 13/16-16 THD 2
EXCESS FUEL RETURN 1/2-14 NPTr 2
1 ERK4UST 076.2 [43.00] 00 2
FUEL INLET 1/2-14 NPIF 2
1 OL DRAIN 3/4-1S 4140 2
110.0 [43.70] 4INDOM
1172.1 [46.15: OVERALL Worn
ME NOTE BELOW)
s?_10 sr 3;1 / CCOR SWING
DouR Se NL
792.5 (31.20)
DOM SWING
1655.0 (73.42)
OVERALL HEIGHT
..--..--
198.0 (7.80)
1
873.0 34.371
DOOR SWNS 1172.1 06.15]
0 CCOR SWING
LIFTING ENE UFI1NG ErE
050.0 (01.961
2 PLACES EACH SCE
ELECTRICAL
STUB-UP AREAS
TOP vEw
REAR •AEN
ELECTRICAL STUB-UP AREAS 811.0 (31.93)
OuSTOvER TADuNTRIC HOLES .4-1500 (5 RI]
17.5 (0.68) X 32.0 (1.26) — -- 50.0 (5.90
6 SLOTS EACH SIX
201.0 (7.91)
'58.0 (6.22)
71 0 (2.60)
358.0 04.09:
14
27.0 ('.06)
00TH SIDES
34.0 (1.34) 1
80114 SIDES
100.0 (3.94)_
L1000. TYPE PRONG AR ENCLOSURE BOTH SCES
LS-2090 CHO 04
LS-2091 CHG 04 L5-1037 040 02
15-2092 CHG 04 LS-1041 Ore 03
LS-2093 CHO 04 920.0 (36.22)-
LS 1047 CHG 04 788.0 (31.0 )-
15-2604 CHO 04
LS-2605 CHG 04 LS-105I CHG 03 606.0 (2 .86) 131 (5.19)
LS-2606 CHO 04 15-2482 CNC 00 160.0 (6 91 HO (366)
Y 15-2607 CHG 04
C7.1 150.0 (5 91 - sirs 50.0 (I.97)
LS-2095 CHG 03
15-2095 CHG 03 15-1036 CHG 03 812.0 (3 .97)
NOTE. PAO<ACE uFTED IN
LS-2608 CHG 03 LS-1040 CHO 03 812.0 (31 97) WINDOW IS NOT 4 PLACES
15-2509 CHG 03 INCLUDED 01/
LS 1046 CHO 04 LS-1036. 15-1037. PACKAGE S140.411 'MTH
15-2610 CHG 03 CNINIIAM
LS-2511 04C 04 L5-1050 CHG 03 FOOTPRINT 1.5-1046. 1.5-1047. LICK DETAIL ON
(ONENSIONED OUTLINE VIEW FRO/ ASORE) LS-2481. LS-2482 SHEET 2
LS-2512 CHG 04 15-2481 CHG 00
Ls-2513 CHG 04 460-0870
EFTA00798851
460-Cd.O
VENTS 3598.4 (141.67)
RAtaTOR ACCESS 3250 4 ( 1 27 97)
ExH4UST 3051 4 (120.13)
I e
945.5 (37.22) 2891 9 ( 1 1386)
786.0 (30.94) 3351 0 (• 31 93)
427.5 (16.83) -
394.5 (15.63)-
319.9 (I .59)-
253.5 (9.98)-
2 0.5 (8.68) - TOP VIEW
50.5 ( .69)-
EmERGEF7C7 2579 7 (10i.56)
STCP BVTTCN 1742.2 (68.59)
VENT 143 7 (69 76)
(ON BOTH SIDES)
RADIATOR ACCESS 398.2 ( 15.65)
- I 6. (5.77)
Ex 'ST
0762 (.3.00) OD 816.0 (32.11) RADIATOR ACCESS
1406.7 (55.38) CIRCUIT rpREARERS
1679.9 (68.14)
t
57.0 (2.24)
COOLANT MAN
13/16-16 IND 108.9 (4.291 69).4 (27.22) 3250 (12.80)
OIL DRAIN 18805 (74 03) 636.4 (25.0 5350 (21 06)
3/4-16 DID (640.5 [76.40 580.4 (22.851 634 5 (24 98)
NEC INLET 2646.5 (104.191 525.4 (20.68) 745 5 (29 35)
1/2 - la NPIF
2746.5 (l08131
EXCESS FUEL RE1uRN
1/2 - la NPIF
FEFT SOE NEW REAR NEW'
nwa BR
46o-os70
EFTA00798852
Warren CAT
WARREN CAT 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
SECTION VI
ELECTRICAL DRAWINGS
NUMBER TITLE PAGE
491-9573 A Diagram — Wiring 1 of 4
Three Phase
EMCP 4.2
491-9573 B Diagram — Wiring 2 of 4
Single Phase
EMCP 4.2
491-9573 C Diagram — Wiring 3 of 4
Symbols
Abbreviations
491-9573 D Diagram — Wiring 4 of 4
Voltage Regulator
380-5925 A Diagram - Wiring 1 of 4
Options Schematic
380-5925 B Diagram - Wiring 2 of 4
Options Schematic
380-5925 C Diagram - Wiring 3 of 4
Options Schematic
380-5925 D Diagram - Wiring 4 of 4
Options Schematic
EFTA00798853
CIO
41, O
tuttiewit tarn I'M tea
Ot ne If
ita
44 I
In
ell II It
* IM 5 •
NSW
Un
0 .Gs
LW 033943
N
• 4
•••••Cen•
-•4t rre•0 Ott
0 @e (1(1) v
w Ten mvx, tA" 481 tic
kn 4tliP '.
Mk hji 64;1 sr: itt a. tg t %ea rn
rn
ea
tire in) is . v s Is Z31.1 a, nor
r* I-71 —%
tai at sorge senatt 1, watt 3. • 00
1-131-11-1
4512—airrirv n
M• CI
C•til•
V
•••
I the gegage C• 01000
re. eng
atte II I
CP LOW
I lett I
An Hale
CO - I Op rani tag en In
L.1
g w it
0:4
if Cr
Me
4if
tj
Li rsia. a/ eta
3V
e-LL
vrvi %yrwr von "C
"77
cfp• °stoop co cs, maim® CP OX8 COr1—0
T I .4.. I CED
• I MUM
il 001.4.1 er. 00 It
WI • Orin
0 4 . 04 0 0i ASETAM
491-9i7
EFTA00798854
•
METRIC( 4'11-957 3
IP CC CR
14.
100000 2•701 0.4.
V. • • 7,
o ar )2 V
s
do' de 669 OD (ORS
ca tor! Ad
d=—•
- 7 TI i •
Cam dill
r t
Cal 712 Cs 42
ism LC) NSAAr
I'M) 1. 0 0 t
6 21411#4.40.•I GOO 0
•sZ -11
tel
4,14,14.1
can
7?) cpr 132f
rl
t 141
If.
Le
7. GO
• "Pr
".
r7P4
ieft st r
r2r0
—
Y P.
t I y l
eon vv V
•• IMF
zwu1
Y'
metIla
C
r 1 r 12
V
C• .044 0 0
1.1,1,;11 ✓ OCILiall
t07.0:0
•'mm 1
I .1
a.
at) 17..10.4
I
03/1/Liaar
Cat Saa• •I TA a
we.
I tar a
fiD
12.4+1_W 4
co
iiL-vi_ p
czo Cl> CD mm m® ®®ax 0 1:3 ?Cwt. f'74.41:41-
CD CD I /sai l CD CID
ala
• ittli $1 Dal I
metion.-wiw
49I-9573 Yri
rir
EFTA00798855
METRIC( 491' 9573
SINIOLS
AMR( yitTIO.4
kito•TX • PRY*. set Moe*
▪ action.. AIM( #4...401
CCII,CYO 71.w• COOCCRP
C 41.1•WIXO.0XY
Nati X CNXI CimatiC
X IIXC' 0-0'
Gy WO CH, Wit C4c( CORI ilbea.
SIX
• Xi.
70.” OCYCI lap
CCrii. MOO ICIAI
• we 10.1, 2}
tOolVt•
CY COCY,P 44ctos. RW CCYCI 'at
- rti SYSk AtaI
say
CRY O f, own« aa.f 'KW caeca
, C7 K. at
(tV
was Ana X tildotiCcrect
(r)
f4,1 OIVp
10 MK Do. RV.
:fen XUXII
way SIC .1.00, 41. 4 r COKYCP
%%6,M
CIP•Xst ant.
CYO( SocYCYC.
CO. Nt J 11 .1141M1
OY YtanTC) Ylcve RAY, MA!, 264 El- 4- 4 - 4i • WI /13%1 oil V IZI cr.VP./0•CCIta91.
Col •CO.St "-'I
‘C. 'OPS Oa* 4.4, _ _ _ Soya, tmotre moan*
Warr
o CHM
v7 watt tn.'
Wt .7€ V la. nowt! awns
MYR
MR In cox 4loscrOMY0
WY.
UI)
•TV reg...X.14
*€-3 , r 17.14.
rie Wit 9C XI , I
EFTA00798856
• R • . . • i . 1
IMILTFIICX 491-9573
DID IvR COVECTION DINCP.M1
SELF INCITATION (SMALL
IIIII MT,
(C-.0
OM CU* AO
MI
_ • ' ENIO ILL? CONNECTIDinIICAUF
t 0 • PERNRCtiT MAGNET MO CICITATREII
rn.
•
ONO
Rots
• Pl*
• SIM OM OM *lib
IWO oINis PM a 0
st - - • n e
IS • '
Oaf a
Mel CHID
I
Pat
D c• .7
Po
T¢
Y,0116
0410 IVO CEINIECTION °loam
r FRIIILIFat EXCITATION alitP). 4-14RE
ROI Y NYS
. s
40IP alt , em
<IOW .1tb <004
• a
• a
I
• . '
• It
Pa I C/In
.1
_ t
m/1.4 et, LIN-NWO
• TIM tin(
.
roe mina
a v..
atm. IOW/CM
OE I'M I7.72.“ ..,.
all •-•••--- -- -
1St
ec3:4"-tr I74.. !:‘14-
=IMAM
111WO Ill XIII .-
49I - 9i 73 kti-itk
I I I 5 1 I I I I e I
EFTA00798857
80-5925
Inside Breoker Bo* 120 Voc, 60Hz
0.0..Cd. 3
J r r
r
reu 11. ,$) 11~
1 m er nnectcH
1 Voc.
co60Hz
Er
CV 112O
•
1251lk,
L J
L
n•:« - WIa.
0.10• nwitit U1 1..,C21.1V/
(VS I
Crarith a uMnno.
43ffue I ~I • wir....ar1k la CIluau u. - Bump
Ult. 2 AO war.
C.IU 3 1.110,II Anil
LI ra. Itl WIC. • Su. ,..rti• 0" 0 : 22,.
~. , COS: POCiot
in
Glan WI.. cuhu..k.augili
ne "0 11 n2
I» 00 23
0.0. 0~4 Pra Pap aI
UK. NLMOto 21, :Meg ,. Øp «UNIT..
Onw-,.. I åbeir WU. UU.I., 10,1runt
alp 2, 41 2.1. • 111 - 14110.
a' 1 61 3 1.111.• 14.1.
.,
'a...a Ifi. „.. 2rtok NC efu
alt. 2, (AMU C...X. neCULUZ
L C.10. GULP - J4012. Lk u?
1,12 Ult
alp'—. 21 pwrm. CrUkUtki OCSOU, 01
P120101 f01 0.14U. 7 0 a -011, 113 - 101•P CMI
0.101 C.00 V. - I ION 0' ./1 .1
V10.1,umu• 21 C<SCOUT,T. al 19s 9»85
C•3 Ulf. 1.10 LUCOM • KlIMULC - mw rib
C.101 UOUNG nip I
21 ]CMMMa ("Whir.
..0411UM. slA111.141111.1.“ etu• Um.
o.
MI «II 0.411
PAO fe0kUUC
.411 A *CUR AU =HO K14 CM COMILIJA OL
tutuUu MUM.. laUk .
MD-5929
EFTA00798858
S1, 4=‘ , 9 4: lax. ) <COWIN 380-5925
140 1PL
Cvai otaati W
WWI nualt Ca4.04(Afai ale4X0
rt P•AWICS Z=t 033— 410 MLR 0-09
(ON 411
• W.403) PfC0.44:0
Cal.405 CO arc" MC 1 vat-I (C) CNCI
• ROAM
c t i_l_rtail
le I c
ii
al).40 foul 01.4
Wan
Ocsa {SW MEW
IC.4.1 !AI MI
0"
0 ,
V I
PAWS
101111All
fa 14),Z3 M. >Ca Aggig lIMIC
C404441.4 CCW4:04.4. AUX.
380-5925
3
EFTA00798859
380-5925
..--- rin
V
-..., ri
4,-Ltr--6
4
\ r ,
.1
f
al
td- al
i
TO Out <weer
or moot rotiO.
Ctin—h r "hrE r
-.-.-...-.-...-.-.-.-...-.-.--.-.--
en-
5...•
Ir
. ..;...67--4
II j ...LII--.0
rr -r
4
4
I lir
i CI Jr r tor
55 ,
C.505
..0.0)
.0
0
n "‘"
tort total.? rtOrcotz
• irrO•rli
Pi'
Qa
orir Verne no worn cows or, ...LAI( Ont. an
5 row 00.0)1 (Mut* • ro )5 Mr. Cflror tam"
vIC 1515...S.0 cow .5•540 .0 orn rflAtioro
wr n INS a COACPCSOS r0 VII o> rani:
wutczalsimw_
conimana
f "01:1 SIX LOCI i
0•505•5.... •Croftrisr.
38D- 92S It
EFTA00798860
380-5925
SYMBO-S
ABEIREVIATIOIS
Ya
.WD oproncie
raw 2we ITRow
ov C4R0410. Op Win
c; HOMO Parktrai
0.416,0 ...Ma , teeter*. Itteem
CO CORWE IneW Rpr
MVP PION inn COSMO. WORM
COPP* iiranwP PIP 90.4r
PPP rtiora
COAror Raw onp own 0.410Pil 0102r riffwari raoawl./444,1 I caarProu ItAvnu
I war 2.0)02ratrort
Ono. artorip
2 W2 Clon:24 *PROM.
vro CO)R.Orr CCOCCRO
T( ) -
AC OPP OPti 10011 4/ Mil Mon Pirkaurt
-O
.t 20•0 uo 2.0:42i
0 -
Orop:a W. repo/IP 0.0P
MU0C
0 POPOPI
au .rap
4 —
C011/411/1
/Or MPS KC owl r
CA rlit,O. COOP•im 4pOit .590-S9fl renntt
1
EFTA00798861
Warren CAT
WARREN CAT 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
SECTION VII
START UP & COMMISSIONING
CHECK LIST
Man 'maw
• • iL
•
\r7•c $ $
EFTA00798862
CATERPILLAR RETAIL (Diesel & Gaseous Fueled). C18 and Below GENSET START-UP & COMMISSIONING CHECKLIST
CAUTION! Only qualified Caterpillar personnel who have been properly trained to support this product should
proceed with the startup process.
Note 1: Service Engineer must communicate with customer to understand site requirements for Personal
Protective Equipment (PPE), Lockout and other safety procedures.
No
Start-up & Commissioning Checklist
1. Safety and Serviceability
1 Genset is free of damage. Note: Freight damage is the Yes No N.A 16 Emergency stop functions correctly Yes No NIA
responsbilily of the Shpper
2 Hot pipes are wrapped Yes No WA 17 Sight glasses are visible Yes No N/A
3 All hoses, piping & wiring are secure Yes No NA 18 Gauges are functional (oil. fuel, air, other...) Yes No NIA
4 Spillage containment acceptable Yes No NA 19 Proper grounding (refer to RENS4634) Yes No NIA
5 Personal Protection Equip. (PPE) available & used Yes No NA 20 Air intake free of airborne debris Yes No NIA
6 Floors are dean no hazards Yes No WA 21 Access routes unobstructed Yes No NA
7 Floor openings are covered Yes No WA 22 Overhead obstructions are clearly marked Yes No NA
8 Genset is level with all holding bolts secure Yes No N/A 23 Overhead clearance is acceptable Yes No NA
9 Warning decals & plates are installed Yes No N/A 24 Canopy door access opening unrestricted fc• Yes No NA
90deg. No operator access restrictions.
10 All guards and heal shields are in place Yes No NA 25 Adequate access to fluid fill areas to prevent spills Yes No NA
11 All known safety shutdowns & warrings operational Yes No NA 26 Air / oil / fuel filters are accessible Yes No NIA
12 Fire extinguisher present & charged Yes No N/A 27 Level indicators are accessible Yes No NIA
13 Fire suppression unlocked & operational Yes No NA 28 Key components are labeled Yes No NIA
14 Pipe work & services (electrical & fuel) are color coded / Yes No N/A 29 Engine room noise level policy satisfied Yes No NIA
labeled
15 Remote start/stop checked & operational Yes No NA 30 Unauthorized Site Access Yes No NIA
2. Maintenance and Coverage
1 Reviewed start-up procedure & safety information Yes No N/A 4 Any Special Site Requirements & Testing Yes No NIA
2 Reviewed OMM. Parts Manual. Warranty. SOS & Service Yes No WA 5 Addtional parts purchased or ordered Yes No NA
Requirements with Customer
3 Verify that the appropriate customer personnel beer Yes No WA
trained on engine operation and maintenance
3. Lube System
I
1 Oil sample taken (SOS) Yes No WA 3 Check for leaks Yes No NA
2 Oil level is correct Yes No WA 4 Engine Oil Type and Viscosity Correct Yes No N.A
4. Alarm / Shutdown Verification
1 Low water level Yes No NIA 9 Over speed Yes No Nip
2 High water temperature Yes No N/A 10 Low DC Voltage Yes No NA
3 Low oil pressure Yes No N/A 11 Shutdown device Yes No NIA
4 Low oil level Yes No NA 12 High air inlet manifold temperature Yes No NIA
5 Low Fuel Level (Diesel) Yes No NA 13 Generator Over Frequency Yes No NIA
6 Low Fuel Pessure (Gaseous) Yes No NA 14 Generator Under Frequency Yes No NIA
7 E-Stop Yes No N/A 15 Generator Over Voltage Yes No NIA
8 High fuel level (Diesel) Yes No WA
Page 1 Start Up Action Items
EFTA00798863
FUELED UNIT I lYes/ No
1 Confirm Fuel Tank Base is level Yes No NA 4 Check fuel lines 8 connectors for leaks (fuel or air) Yes No NIA
2 Confirm proper Fuel Level in Tank Yes No NA 5 Confirm RLpture Basin Tank is empty Yes No NIA
3 Fuel filter primed Yes No N.A 6 Day Tank Provided Yes No NIA
GASEOUS FUELED UNIT Yes/No
1 Gaseous Fuel Type
3 Primary Fuel Pressure Regulator
N.G.. LPG-V 2 Utility or Tank Fuel Supply Pressure
I Ipsi
Manufacturer Model
Connector Size (in.) Spring Rate (inH20)
Static Output Regulator to be
Pressure (inH20) Spaced 10ft from
base rail connection.
4 Stainless Steel Flex Hose Installed Perpendicular to the Yes / No 9 LPG Fuel Tank Information. II applicable answer the If Applicable
base rail connector. Flex Hose Must Be Installed. items listed below.
5 Confirm Low Pressure Fuel Supply is not shared. Must Yes / No Vertical
be a dedicated source to the genet. LPG Tank Orientation Horizontal
6 Confirm Sediment Trap is present and located on the Yes; No LPG Tank Capacity Gallons
High Pressure side (Inlet) of the Primary Regulator
7 Primary Fuel Pressure Regulator - Diaphragm Case Yes: No LPG Tank Location Above Ground
Orientation. Vertical Not Rat. Below
8 Confirm Shut-Off valve is present and located on the Yes No 10. Confirm Fuel Type Selection Configuration Yes !No
High Pressure side of the Primary Regulator Wiring matches Fuel Source. Reference Caterpillar
Media 1.40076230. Available on SISWeb
For Natural Gas Fuel Type Configuration - No Yes No
Jumper Installed.
For Liquid Propane Gas (LPG) - Instal jumper Yes !No
across "-" and 'LP" terminals.
6. Engine - Governor Settings
1 As-Shipped. Electronic copy of the ECM Yes No 2 Commissioned: Electronic copy of the ECM Yes: No
replacement file and configuration file downloaded replacement file and configuration file
and saved. downloaded and saved.
7. Afterireatmeni
1. Followong iritial start-up procedure from Appendix B in the 8. DEF tank venting routed to meet local and OSHA
Yes No NIA Yes No NIA
A8I Guide guidelines for ammonia fumes
2. Communicate that top of CEM is not suitable for a work 9. Maximum 10kPa difference from CEM to atomospheric
Yes No NA Yes No NA
platform pressure
3. Urea quality meets ISO22241-1 Yes No NA 10. ExhaustiCEM connected properly Yes No NA
4. Urea Ines temperature between -5 deg C and 50 degC Yes No NA 11. Exhaust weight transfer to CEM meets A&I Yes No NIA
5. DEF tank sample port installed Yes No N/A Yes No NIA
6. DEF tank temperature less than 40deg. C Yes No NA Yes No NA
Yes No NIA
7. Ratio of 1 fuel tank refill to 1 DEF lank refill for systems with
Yes No NIA
a constantly v side DEF level indicator
Page 2 Start Up Action Items
EFTA00798864
8. Intake System Exhaust System
1 Pre-lute turbo charger Yes No NIA 4 Flexible exhaust fitting to isolate vibrations and Yes No NiA
allow for thermal expansion
2 Exhaust directed away from building / personnel Yes No NIA 5 Check intake and exhaust systems for leaks Yes No N/A
3 Emissions control unit installed & operational (Diesel ' Yes No NIA 6 Record intake manifold air temperature: Yes No N/A
9. Jacket Water & Space Heater
1 Jacket water heater (JWH) Ptxge Air in system required Yes No NIA 4 Adjust JWH thermostat and record selling
2 Verify JWH valve position is open during usage Yes No NIA 5 Record engine block temperature
3 If installed. operate alternator space heater(s) 48 hours Yes No NA
before start-up
10. Starter & Battery
1 Confirm battery is fuly charged Yes No NIA 6 Engine Alternator Charger Installed Yes No NA
2 Proper electrolyte level Yes No NA 7 Engine Alternator Charger Configured Properly Yes No N/A
3 Confirm battery provides proper system voltage Yes No NIA
4 Battery Charger Installed Yes No NIA
5 Battery Charger Configured Properly Yes No NA
11. Cooling System (Jacket Water and SCAC Systems)
1 Check for leaks Yes No N.A 7 Hot air recirculation prevented Yes No N/A
2 Check coolant level Yes No NA 8 Confirm Jacket Water Heater Power suppy is Yes No N/A
correct.
3 Confirm Antifreeze Mixture with a Hydrometer Yes No NA 9 Pressure lest cooing system - record test pressure Yes No NIA
(psi)
4 Isolation valves & drain valves installed Yes No N/A
5 Expansion tank highest level Yes No NIA
6 Discharge air unobstructed Yes No NA
I
12. Mechanical
1 Package properly mounted
2 Package supports & vibration isolators installed
•
Yes No N/A
Yes No N/A
■
Yes No NIA
13. Generator Set System - Electrical
1 Over voltage protection shutdown set Yes No NA 5 Adjust output voltage. within specification. Yes No N/A
2 Over current protection shutdown set Yes No NA 6 Confirm all protective covers are in position Yes No N/A
3 Confirmed correct output voltage wiring configuration Yes No NIA 7 Adjust output frequency for application (+/- 0.1hz of Yes No NIA
Nominal Rating)
4 Confirm alternator conductors are secured properly on Yes No NIA 8 Und is properly grounded (REHS4632) Yes No N/A
the link board and are routed to prevent chaffing
9 Confirm output Phase Rotation is correct Yes No NIA
Page 3 Start Up Action Items
EFTA00798865
14. Generator Set System - Control Panel
1 Confirm wire loom(s) are properly secured and routed Yes No NIA 9 Confirm Generator System control parameters are Yes No NA
properly set
2 Confirm all wire terminations for secured. Pull Test as Yes No NIA 10 Confirm Control Panel is configured with the most Yes No N/A
required. current Flashlile. Update as reqUred.
3 Confirm B+ Wiring is correct. (i.e. Polarity. secured) for Yes No NIA 11 Confirm that meters are wired properly and Yes No NIA
the Control Panel and all ancillary devices. conductor terminations are secured.
4 Energize set & system controls. Confirm devices Yes No NIA 12 Confirm that meters function properly Yes No NA
energize properly.
5 Verify operation of annunciator device Yes No NIA 13 Confirm that the all Emergency E-Stops (local & Yes No NIA
remote) are wired properly and function correctly
6 Confirm operation of Auto, Manual and Stop functions. Yes No NIA 14 Confirm all interconnect wiring is correct and Yes No NA
properly secured
7 Check generator local controls Yes No NIA 15 Commissioned: Electronic copy of the ECM Yes !No
replacement configuration file downloaded and
saved.
8 Check generator remote controls Yes No NA 16 Generate and Save a PSRP Yes No NA
15. Generator Set System - Mechanical
1 Check for loose or missing hardware Yes No N/A
16. Generator Set System - Circuit Breakers
1 Test any alarms shunt trp
2 Set circuit breaker trp unit for site conditions
Yes No N/A
Yes No N/A
■Yes No NIA
17. Generator Set System - Integrated Voltage Regulator
1 Confirm Integrated Voltage Regulator (IVR) Type EM10. EM15 4 Conlin IVR Fuses are installed and secure. Yes No NA
2 Confirm IVR Interlace Harness is correctly installed Yes No NiA 5 Confirm IVR Parameters have been Set. Use ET to Yes No NIA
view parameters.
3 Confirm IVR Over-Excitation Protection LED is GREEN. Yes No NA For Technical reference use LEBE0006 A&I
LED is Green for Normal Concitions. Manual. Section -Integrated Voltage Regulator
18. Automatic Transfer Switch
1 Verily voltageamperage Yes No NA 4 Confirm proper phase rotation Yes No WA
2 Confirm No Damage is present (Mechanical. Structural. Yes No NA 5 Set Exercise Timer Yes No WA
Electrical)
3 Confirm all conductors are terminated property and Yes No NA Exercise Timer Frequency Setting
secured.
Start Up Details:
Page 4 Start Up Action Items
EFTA00798866
Page 5 Start Up Action Items
EFTA00798867
Page 6 Start Up Action Items
EFTA00798868
Page 7 Start Up Action Items
EFTA00798869
Page 8 Start Up Action Items
EFTA00798870
Warren CAT
WARREN CAT 15 North Meridian Avenue
Oklahoma City, Oklahoma 73127
SECTION VIII
WARRANTY
•
• 0
• •
I I
Photographs included in this document are for page break purpose only
and do not necessarily represent the equipment supplied.
EFTA00798871
re
Effective Mth sales to the first user on or after August 7 2,7, 7 .1
CATERPILLAR LIMITED WARRANTY
Industrial, Petroleum, Locomotive, and Agriculture Engine Products and
Electric Power Generation Products
Worldwide
Caterpillar Inc. or any of its subsidiaries ("Caterpillar") For electric power generation products other than manufacturers packaged and sold by Caterpillar):
warrants new and remanufactured engines and electric CG132. CG170 and CG260 series in prime or
Provide travel labor. up to four hours round trip. if in the
power generation products sold by it (including any products continuous applications the warranty period is
opinion of Caterpillar, the product cannot reasonably
of other manufacturers packaged and sold by Caterpillar), to 12 months. For standby applications the warranty period
be transported to a place of business of a Cat dealer
be free from defects in material and workmanship. is 24 months/1000 hours. For emergency standby
or other source approved by Caterpillar (travel labor
applications the warranty period is 24 months/400 hours.
This warranty does not apply engines sold for use in in excess of four hours round trip. and any meals.
All terms begin after date of delivery to the first user.
on-highway vehicle or marine applications: engines in mileage, lodging. etc. is the user's responsibility).
machines manufactured by or for Caterpillar; C175. 3500 For all other applications the warranty period is For all other products:
and 3600 series engines used in locomotive applications: 12 months after date of delivery to the first user.
3000 Family engines. CO.5 through C4.4 and ACERT'" Provide reasonable travel expenses for authorized
Caterpillar Responsibilities
(C6.6. C7. C7.1. C9. C9.3. C11. C13. C15. C18. C27. and mechanics, including meals, mileage, and lodging,
C32) engines used in industrial, mobile agriculture and If a defect in material or workmanship is found during the when Caterpillar chooses to make the repair on-site.
locomotive applications: or Cari batteries. These products warranty period. Caterpillar will. during normal working
User Responsibilities
are covered by other Caterpillar warranties. hours and at a place of business of a Cat dealer or other
source approved by Caterpillar: The user is responsible for:
This warranty is subject to the following:
Provide (at Caterpillar's choice) new. Remanufactured. • Providing proof of the delivery date to the first user.
Warranty Period
or Caterpillar approved repaired parts or assembled • Labor costs, except as stated under "Caterpillar
• For industrial engines. engines in a petroleum components needed to correct the defect. Responsibilities," including costs beyond those
applications or Petroleum Power Systems (excluding required to disconnect the product from and reconnect
Note: New, remanufactured. or Caterpillar approved
petroleum fire pump application), or engines in a the product to its attached equipment. mounting, and
repaired parts or assembled components provided
Locomotive application, or Uninterruptible Power support systems.
under the terms of this warranty are warranted for
Supply (UPS) systems. the warranty period is
the remainder of the warranty period applicable • Travel or transporting costs, except as stated under
12 months after date of delivery to the first user.
to the product in which installed as if such parts "Caterpillar Responsibilities.'
• For engines used in petroleum fire pump and mobile were original components of that product. Items
agriculture applications the warranty period is replaced under this warranty become the property • Premium or overtime labor costs.
24 months after date of delivery to the first user. of Caterpillar. • Parts shipping charges in excess of those that are
• For controls only (EPIC), configurable and custom Replace lubricating oil, filters. coolant, and other usual and customary.
switchgear products. and automatic transfer switch service items made unusable by the defect. • Local taxes, if applicable.
products, the warranty period is 24 months after date Provide reasonable and customary labor needed to
of delivery to the first user. • Costs to investigate complaints, unless the problem
correct the defect, including labor to disconnect the is caused by a defect in Caterpillar material or
• For new CG132. CG170 and CG260 series product from and reconnect the product to its attached workmanship.
power generation products the warranty period is equipment, mounting, and support systems, if required.
24 months/16.000 hours, whichever comes first, after • Giving timely notice of a warrantable failure and
For new 3114, 3116, and 3126 engines and electric power promptly making the product available for repair.
date of delivery to first user.
generation products (including any new products of other
(Continued on reverse side.. )
SELF5611
EFTA00798872
• Performance of the required maintenance (including • Failures resulting from attachments, accessory items. • Damage to pads, fixtures, housings, attachments, and
use of proper fuel, oil, lubricants, and coolant) and items and parts not sold or approved by Caterpillar. accessory items that are not part of the engine. Cat
replaced due to normal wear and tear. • Selective Catalytic Reduction System or electric power
Failures resulting from abuse, neglect, and/or improper
• repair. generation product (including any products of other
Allowing Caterpillar access to all electronically stored
manufacturers packaged and sold by Caterpillar).
data.
• Failures resulting from user's delay in making the
• Repair of components sold by Caterpillar that is
Limitations product available after being notified of a potential
warranted directly to the user by their respective
Caterpillar is not responsible for. product problem.
manufacturer. Depending on type of application, certain
• Failures resulting from unauthorized repairs or exclusions may apply. Consult your Cat dealer for more
• Failures resulting from any use or installation that
adjustments, and unauthorized fuel setting changes. information.
Caterpillar judges improper.
This warranty covers every major component of the products. Claims under this warranty should be For products operating in Australia, Fiji, Nauru, New Caledonia, New Zealand, Papua New
submitted to a place of business of a Cat dealer or other source approved by Caterpillar. For further Guinea. the Solomon Islands and Tahiti, the following is applicable:
information concerning either the location to submit claims or Caterpillar as the issuer of this warranty,
THIS WARRANTY IS IN ADDITION TO WARRANTIES AND CONDITIONS IMPLIED
write Caterpillar Inc., 100 N. E. Adams St.. Peoria, IL USA 61629.
BY STATUTE AND OTHER STATUTORY RIGHTS AND OBLIGATIONS THAT BY ANY
Caterpillar's obligations under this Limited Wairanlyare subject to. and shall not apply in contravention APPLICABLE LAW CANNOT BE EXCLUDED. RESTRICTED OR MODIFIED ("MANDATORY
of, the laws, rules, regulations. directives. ordinances. orders, or statutes of the United States. or of RIGHTS"). ALL OTHER WARRANTIES OR CONDITIONS. EXPRESS OR IMPLIED (BY
any other applicable jurisdiction, without recourse or liability with respect to Caterpillar. STATUTE OR OTHERWISE), ARE EXCLUDED.
For products operating outside of Australia. Fp, Nauru, New Caledonia. New Zealand, Papua New NEITHER THIS WARRANTY NOR ANY OTHER CONDITION OR WARRANTY BY
Guinea. the Solomon islands and Tahiti, the following Is applicable: CATERPILLAR. EXPRESS OR IMPLIED (SUBJECT ONLY TO THE MANDATORY RIGHTS).
IS APPLICABLE TO ANY ITEM CATERPILLAR SELLS THAT IS WARRANTED DIRECTLY
NEITHER THE FOREGOING EXPRESS WARRANTY NOR ANY OTHER WARRANTY BY TO THE USER BY ITS MANUFACTURER.
CATERPILLAR, EXPRESS OR IMPLIED, IS APPLICABLE TO ANY ITEM CATERPILLAR SELLS
THAT IS WARRANTED DIRECTLY TO THE USER BY ITS MANUFACTURER. TO THE EXTENT PERMITTED UNDER THE MANDATORY RIGHTS, IF CATERPILLAR IS
THE SUPPLIER TO THE USER, CATERPILLAR'S LIABILITY SHALL BE LIMITED AT ITS
THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER WARRANTIES. EXPRESS OPTION TO (a) IN THE CASE OF SERVICES, THE SUPPLY OF THE SERVICES AGAIN
OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A OR THE PAYMENT OF THE COST OF HAVING THE SERVICES SUPPLIED AGAIN, AND
PARTICULAR PURPOSE, EXCEPT CATERPILLAR EMISSION-RELATED COMPONENTS (b) IN THE CASE OF GOODS, THE REPAIR OR REPLACEMENT OF THE GOODS, THE
WARRANTIES FOR NEW ENGINES. WHERE APPLICABLE. REMEDIES UNDER THIS SUPPLY OF EQUIVALENT GOODS, THE PAYMENT OF THE COST OF SUCH REPAIR OR
WARRANTY ARE LIMITED TO THE PROVISION OF MATERIAL AND SERVICES, AS SPECIFIED REPLACEMENT OR THE ACQUISITION OF EQUIVALENT GOODS.
HEREIN.
CATERPILLAR EXCLUDES ALL LIABILITY FOR OR ARISING FROM ANY NEGLIGENCE
CATERPILLAR IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.
ON ITS PART OR ON THE PART OF ANY OF ITS EMPLOYEES. AGENTS OR
CATERPILLAR EXCLUDES ALL LIABILITY FOR OR ARISING FROM ANY NEGLIGENCE ON REPRESENTATIVES IN RESPECT OF THE MANUFACTURE OR SUPPLY OF GOODS OR
ITS PART OR ON THE PART OF ANY OF ITS EMPLOYEES, AGENTS OR REPRESENTATIVES THE PROVISION OF SERVICES RELATING TO THE GOODS.
IN RESPECT OF THE MANUFACTURE OR SUPPLY OF GOODS OR THE PROVISION OF
CATERPILLAR IS NOT LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES
SERVICES RELATING TO THE GOODS.
UNLESS IMPOSED UNDER MANDATORY RIGHTS.
IF OTHERWISE APPLICABLE, THE VIENNA CONVENTION ON CONTRACTS FOR THE IF OTHERWISE APPLICABLE, THE VIENNA CONVENTION ON CONTRACTS FOR THE
INTERNATIONAL SALE OF GOODS IS EXCLUDED IN ITS ENTIRETY.
INTERNATIONAL SALE OF GOODS IS EXCLUDED IN ITS ENTIRETY.
For personal or family use engines or electric power generation products, operating in the USA. its (02014 Caterpillar All Rights Reserved.
territories and possessions, some states do not allow limitations on how long an implied warranty CAT, CATERPILLAR, their respective logos. 'Caterpillar Yellow," the "Power Edge" trade dress
may last nor allow the exclusion or limitation of incidental or consequential damages. Therefore, the as well as corporate and product identity used herein, are trademarks of Caterpillar and may
previously expressed exclusion may not apply to you. This warranty gives you specific legal rights not be used without permission.
and you may also have other rights. wnich vary by Jufisdiction. To find the location of the nearest Cat
dealer or other authorized repair facility. cal (800) 447-4986. If you have questions ooncerning this
warranty or Its applications. call or write:
In USA and Canada: Caterpillar Inc., Engine Division, P. 0. Box 610, Mossville. IL 61552-0610,
Mention: Customer Service Manager. Telephone (800) 447-4986. Outside the USA and Canada:
Contact your Cat dealer.
SELF5611