Hi Rich,
This visit focused on the island grid layout and 3-phase distribution design. The grid has historically had a
major power draw around 2am. We found several easy changes that need to be made my Danny Vickers that
might solve this problem. Some of the distribution panels on the grid have neutral and grounds bonded
together which can cause a "voltage loop" and send power directly to ground when power consumption takes
place. The ground and the neutral should only bond in one place and that is the multi-cluster box in the
battery room.
We also thermal imaged all the main electrical connections on the island. We found a few chaired wires that
were trimmed and re-seated to eliminate fire hazard.
Danny and I concluded that he could easily upgrade the main panel under the main house to a 200A 3-phase
panel instead of the current situation which is 3-phase distribution but single phase energy usage. This creates
an imbalance and leads to a major loss of efficiency.
We will continue to watch the systems performance and once these changes are made we will check to see if
we are still experiencing the 2am battery drain.
The attached pictures show heat signatures we are addressing. Some of them have been rectified already.
EFTA01038264
please note
The information contained in this communication is
confidential, may be attorney-client privileged, may
constitute inside information, and is intended only for
the use of the addressee. It is the property of
JEE
Unauthorized use, disclosure or copying of this
communication or any part thereof is strictly prohibited
and may be unlawful. If you have received this
communication in error, please notify us immediately by
return e-mail or by e-mail to jeevacation@gmail.com, and
destroy this communication and all copies thereof,
including all attachments. copyright -all rights reserved
EFTA01038265