PROFIBUS PA VALVE POSITIONER
Series ND800PA rev1.0
USER'S GUIDE
SIMATIC
PDM
EFTA01216870
Table of Contents
Table of Contents
1 Introduction 4
1.1 Abbreviations 4
1.2 Referenced Documents 4
2 Quick start instructions 5
2.1 ND800PA basic setup 5
2.2 Fine tuning 5
3 Installation 6
3.1 GSD file 6
3.2 Simatic PDM driver 8
4 ND800PA GSD modules 11
5 Operation 14
5.1 Identification Group 15
5.1.1 Operation Unit 15
5.1.2 Device 15
5.1.2.1 Positioner 15
5.1.2.1.1 Static Revision No 15
5.1.2.2 Actuator 16
5.1.2.3 Valve 16
5.1.3 Batch Information 16
5.2 Settings Group 17
5.2.1 Assembly Related Configuration 17
5.2.2 Profibus Communication Fail Safe Action 17
5.2.3 Servo Controller 18
5.2.4 Valve Diagnostics 18
5.3 Input Group 19
5.3.1 Input value 19
5.3.2 Working Range 20
5.3.3 Travel Time 20
5.4 Human Interface Group 20
5.4.1 Maintenance 20
5.4.2 Simulation 20
5.5 Certificates and Approvals Group 21
5.6 Device menu 22
5.6.1 Operation 22
5.6.1.1 Page AUTO 22
5.6.1.2 Page Remote Cascade 23
5.6.1.3 Page MAN 24
5.6.1.4 Page Simulation 25
5.6.2 Flow characterization 26
5.6.3 Valve test 30
5.6.4 Write Protection 31
5.6.5 Calibration 33
5.6.5.1 Page Calibration 33
5.6.5.2 Page Position Sensor Temperature Compensation 34
5.6.6 Reset 35
5.6.6.1 Page Factory Reset 35
5.6.6.2 Page Reset Diagnostics 36
5.7 View menu 37
5.7.1 Display 37
5.7.1.1 Page Measured Value 37
5.7.1.2 Page Output 38
2(52)
EFTA01216871
Table of Contents
5.7.2 Device Status 39
5.7.2.1 Page General 39
5.7.2.2 Page Profile 40
5.7.3 Valve Diagnostics 41
5.7.3.1 Page Measurements Trend 41
5.7.3.2 Page Travel Counters 43
5.7.3.3 Page Travel Deviation Trend 44
5.7.3.4 Page Actuator Load Factor Trend 45
5.7.3.5 Page Valve Travel vs. Time Trend 46
5.7.4 Event log 47
6 Appendix A. Parameter table. 48
7 Appendix B. Adding the ND800PA to the PDM project. 52
3(52)
EFTA01216872
Quick start instructions
1 Introduction
ND800PA is a PROFIBUS PA compatible valve positioner made by Metso Automation.
Simatic PDM is a field device configurator software that supports PROFIBUS DP/PA and
HART devices.
The ND800PA documentation is provided in two manuals:
• ND800PA Installation, Maintenance and Operation instructions /1/. This document
describes the physical installation instructions and configuration using the Local User
Interface.
• ND800PA User's Guide. This document describes the functionality of the device in the
Simatic PDM point of view.
This device is designed according to the PROFIBUS-PA Profile for Process Control Devices
Version 3.0 /2/.
1.1 Abbreviations
OLE Object Linking and Embedding (Microsoft technology)
OPC OLE for Process Control (Microsoft technology)
DDE Dynamic Data Exchange (Microsoft technology)
LUI Local User Interface
PDM Process Device Manager
1.2 Referenced Documents
/1/ ND800PA Installation, Maintenance and Operation instructions.
/2/ PROFIBUS Nutzerorganisation, PROFIBUS-PA Profile for Process Control Devices
Version 3.0, October 1999.
4(52)
EFTA01216873
Quick start instructions
2 Quick start instructions
1. Install the PDM driver and the GSD file. See page 6.
2. Add the ND800PA to the Simatic PDM project. See Appendix B.
2.1 ND800PA basic setup
1. Set the Assembly related configuration. See page 17.
2. Set the Profibus Communication Fail Safe Action. See page 17.
3. Run the Automatic travel calibration. See page 33.
4. Set the Bus address from LUI or PDM.
5. Configure the GSD module. See page 11.
2.2 Fine tuning
Some applications may require some of the following adjustments;
• Direction
• Travel Time limiting
• Cutoff
• Limits
• Dead angle compensation
• Flow characterization
Diagnostic warning and alarm limits also may need adjustment as well as the supply pressure
estimate.
5(52)
EFTA01216874
Installation
3 Installation
The ND800PA is shipped with one CD-ROM disc. The CD-ROM disc contents;
• GSD file
• Simatic PDM driver
• Installation, Maintenance and Operation instructions (IMO)
• Users Guide
3.1 GSD file
GSD file is needed for the PROFIBUS master (class 1) to be able to configure the cyclic DP
communication between the master and the slave. The Profibus master could be a DCS or
PLC from any vendor. All of these systems have their own, separate configuration tools. All of
these tools understand the ND800PA GSD file.
The following example (figures 1-5) describes how to add the NEL_052D.GSD file to the
Siemens Step 7 Hardware catalog as well as to the hardware project.
IIW Conk) Conliour IIaide/ate
,Station LW yaw
CakAINE
DIESIciLN
Edt Catalog Prdias
!Iodate Catalog
Install Netiu • GSE Files
Instals new device database Pc in the system and tgdates the co:tents of the catalog
Figure 1. Select "Install New ".GSE Files".
Install Now A.GSE Hot
Locke I A IZ
.21
Filename: INel_052d 9.74 Open
files of hope I• GSE Fies t• gss7) Cancel
Figure 2. Browse to CD-ROM drive and select NEL_052D.GSD.
6(52)
EFTA01216875
Installation
ilw Cook, • ISIMAI1C 300 Station 1Cordiquiolionli• slave_diool MGM
Alta:so Edi Intert PLC View Doom Window Hop
DIta•I2-•I® gol
r-10IUA pRofiguisili tiP m.,3,,, yy.1,,f, i a BAD 'Standee
1 F5307 2A FROFISUS DP
2 ClltI2IS-2 ORB - _j AddoonelFieldOeice:
.1/47 Ao • ,_J I/0
3 __I Soon*
1 a&s128i _J NM% I
5 Unvertal Moduh
6 • J actimix 1 AO
I • —I VS710
8 • —I Gattway
9 - J ClotekoopCcresollin
10 - —I CooknoidSlotan
11 - _J CP 3425.e OP Mesta
DP/inSii
I nP,PA
Figu e 3. Now the ND800PA appears on the hardware catalog. Drag and drop the
ND800PA object to the hardware project.
Selecting the Preset Configuration A
SP,CHECKBACK
SP,READBACKPOS_D,CHECKBACK
RCAS_IN.RCAS_0117
RCAS_INSCAS_OUT,CHECKBACK
SPBB.RC_ISC 0.POS_D.00
(40)SP
(4t 1SP READBACKPOS D
OK Cancel I Help
Figure 4. Select the module for the cyclic communication. In this case the module
contains signals SP, READBACK and
Properties PROEMS Node 140800RA
Genera Panemelets
adckesx 121
Tiansmission Hee 45 45 (31 25)Kbps
Sttoei:
DoPenks—
OK Cancel I Help I
Figure 5. Select the device slave address. This does not change the slave address but
only tells to the S7 project that what the current address is.
7(52)
EFTA01216876
Installation
3.2 Simatic PDM driver
Simatic PDM driver adds the ND800PA device support to the Simatic PDM. This driver is
tested with following PDM versions:
• PDM v. 5.0.1
• PDM v. 5.0.1 SP3
• PDM v. 5.0.2 SP1
The driver installation is described in figures 6-11.
Nd800pa (Z:) SO Ent
File Edit Yew Help
n7nd72en.pdf
Devicelnstall exe
DEVICEINSTALL.HLP
,211ND_HIpM.inc
ND800PAdct
mJ ND800PAddl
ND800PA_Users_Guidepcif
OND800PAB.hlp
ie Nel_052d.gsd
Nel052dn.bmp
j NELES.devices
i PA_9710n.dib
Lai PA139710.gsd
Vobject(s) selected 13260
Figure 6. Browse to CD-ROM drive and start (double click) Devicelnstall.
I Device Install for Simatic PDM E3
Device Install for Simatic PDM
Version R 5.0.0.26-REL
• installs or updates devices
• installs service packs
Copyright SIEMENS AG © 1997 - 1999
Next > Cancel Help
Figure 7. Click Next.
8(52)
EFTA01216877
Installation
Device Install for Simatic PDM: Choose Location
R Supplied devices or service packs
r Diskette
C Search in
sirn_PDM1devices
<Sack Next > Cancel I Help
Figure 8. Select "Supplied devices or service packs" and click Next.
a Device Instill lor Sonol . I >DM P
i6ND800PA (EN
Finish Cancel Help
Figure 9. Click Finish.
9(52)
EFTA01216878
Installation
Device Install fur Simatic PDM. Dune ! El
6 files copied
No update necessary for 2 files
Thank you for using DeviceInstall for Simatic PDM I
Close Help
Figure 1O. Result of successful installation.
SIMATIC PDM Device Selection El
PA-Device Catalogue:139 entries (89 devices)
- Actuators
OK
- Elecio-pneumobc
- Metso Automation
Cancel
Profile 2
SAMSON AG
+ SIEMENS Help
T- SMAR
± Converter
• Discrete Output
+ Other
. Sensors
Catalogue-lmport .. I
Qesciiplion. Electropneumatic valve positioner ND800PA Software Re•. 1.00. PA-Profile 3.0.
Qrder No.: ND8sticcox<
Figure 11. Now the ND8OOPA device should appear in the PA-Device Catalogue window.
This window can be found by selecting the menu Insert / PDM / PFOFIBUS
PA device in the Simatic Manager Process Device Network view.
1O(52)
EFTA01216879
ND800PA GSD modules
4 ND800PA GSD modules
The control communication is basically as follows; PLC/DCS writes the valve position setpoint
to the ND800PA and reads the position measurement from the ND800PA. This
communication is configured by the GSD modules.
GSD module is a set of data, which the ND800PA and DCS/PLC exchanges cyclically until the
end of the world. The GSD modules are listed in the GSD file. The ND800PA GSD file name is
Nel_052d.gsd. During the DCS/PLC configuration, the configuration software, such as
Siemens Simatic Step 7, reads the Nel_052d.gsd file and asks user, which GSD module
should be used.
The ND800PA has following GSD modules;
• SP
• SP,READBACK,
• SP,CHECKBACK
• SP,READBACK, CHECKBACK
• RCAS_IN,RCAS_OUT
• RCAS_IN,RCAS_OUT.CHECKBACK
• SP,RB,RC_I,RC_O, CB
Abbreviations; RB=READBACK, RC_I=RCAS_IN, RC_O=RCAS_OUT, CB=CHECKBACK
For compatibility reasons the modules are represented in both Identifier Byte format and in
Extended Identifier Format.
SP is the valve position setpoint in the AUTO mode. The ND800PA Analog Output Block
default target mode is AUTO. The range is 0-100%.
READBACK is the valve position measurement. The range is 0-100%.
contains the limit switch information. The values are:
1 = closed
2 = opened
3 = intermediate
If the limit switches are not installed, the value is determined from the position
measurement sensor as follows:
1 = closed, Position <= 2%
2 = opened, Position >=98%
3 = intermediate, 2 < Position < 98
RCAS_IN is the valve position setpoint in the Remote Cascade mode. Before this setpoint is
used, the Analog Output Block (AO) actual mode has to be the RCAS mode. This requires as
follows;
• AO block target mode must be RCAS.
• The DCS/PLC has to go through the remote cascade initialization sequence with the
ND800PA. This is done by using the STATUS bytes of the RCAS_IN and RCAS_OUT
signals.
RCAS_OUT feeds back the SP or RCAS_IN, depending on the mode.
CHECKBACK is a diagnostic signal. All control systems has their ways to convert this
standard bit-information to human readable alert messages. See table 1.
11(52)
EFTA01216880
ND800PA GSD modules
Table 1. CHECKBACK signal bit-enumeration.
Byte Bit Description Indication
Class
0 0 Field device in Fail safe active R
1 Request for local Operation R
2 Field device under local control. LOCKED OUT switch is in gear R
3 Emergency override active R
4 Actual position feedback different from expected position R
5 Indicates that the torque limit in OPEN direction is exceeded R
6 Indicates that the torque limit in CLOSE direction is exceeded R
7 Indicates status of travel monitoring equipment, if YES, travel time for actuator has A
exceeded.
1 0 Actuator is moving towards open direction R
1 Actuator is moving towards close direction R
2 The alert generated by any change to the static data (Function and Transducer A
Block).
3 Simulation of process values is enabled R
4 - -
5 Internal control loop disturbed R
6 Positioner inactive (OUT status = BAD) R
7 Device under selftest R
2 0 Indicates that total valve travel limit is exceeded R
1 Indicates that an additional input (i.e. for diagnostics) is activated R
R Indication, remains active as long as the reason for the message exists.
A Indication. will be automatically reset after 10s.
In addition to the actual value (IEEE-754 float), all GSD module signals (except CHECKBACK)
have a status information (See table 2). The status tells the quality of the value. Example;
READBACK status is bad, device failure, if the position measurement sensor is broken.
Table 2. Status byte mapping.
Status byte Quality Additional Limit Meaning
in case that information
the limit bits
are zeros Bits Bits Bits
5 4 3 2
0x00 0 0_ 0 0 0 0 x x bad
0x04 0 0 0 0 0 1 x x bad. configuration error
0x08 0 0 0 0 1 0 x x bad. not connected
0x0C 0 0 0 0 1 1 x x bad. device failure
0x10 0 0 0 1 0 0 x x bad. sensor failure
0x14 0 0 0 1 0 1 x x bad. no communication (last usable value)
0x18 0 0 0 1 1 0 x x bad. no communication (no usable value)
0x1C 0 0 0 1 1 1 x x bad. outer service
0x40 0 1 0 0 0 0 x x uncertain
0x44 0 1 0 0 0 1 x x uncertain, last usable value
0x48 0 1 0 0 1 0 x x uncertain. substituted value
0x4C 0 1 0 0 1 1 x x uncertain. initial value
0x80 1 0 0 0 0 0 x x good
0x84 1 0 0 0 0 1 x x good. Update event (change of parameters)
0xA0 1 0 1 0 0 0 x x good. go into failsafe position (command)
0xA4 1 0 1 0 0 1 x x good. maintenance required
OxC0 1 1 0 0 0 0 x x good (cascade)
0xC4 1 1 0 0 0 1 x x good (cascade). initialization confirmed
0xC8 1 1 0 0 1 0 x x good (cascade). initialization requested
0xCC 1 1 0 0 1 1 x x good (cascade). rcas mode not requested
0xD8 1 1 0 1 1 0 x x good (cascade). local operation has priority
0xE0 1 1 1 0 0 0 x x good (cascade). go into failsafe position (command)
x x x x x x 0 0 value is not limited
x x x x x x 0 1 value is low limited
x x x x x x 1 0 value is high limited
x x x x x x 1 1 value is constant
x = could be any (0 o 1)
12(52)
EFTA01216881
ND800PA GSD modules
In addition to the CHECKBACK, the ND800PA has two more diagnostic signals. These signals
are not included in the GSD modules.
DIAGNOSIS contains standard diagnostic information (See table 3). This parameter is
available to DCS/PLC if it supports a DP service called ddlm_slave_diag. The idea here is
that this parameter is not polled cyclically, but whenever new information is available, the
ND800PA rises a diagnostic flag (in cyclic communication). When DCS/PLC sees that flag, it
reads the DIAGNOSIS parameter by using the ddlm_slave_diag service.
DIAGNOSIS EXTENSION is manufacturer specific extension to the DIAGNOSIS (See table
4). This parameter is included in the ddlm_slave_diag service only if the PROFIBUS Ident
Number is selected to be Manufacturer specific.
Table 3. Dia nosis Darameter bit-enumeration.
Byte Bit Description Indication
Class
1 0 Hardware failure of the electronic R
I Hardware failure mechanics R
2 Motor- temperature too high Ft
3 Electronic temperature too high R
4 Pile mory error R
5 Fa:ure in measurement Ft
6 Device not initialised (No selfcalibralion) Ft
7 Setfcabbration failed Ft
2 0 Zero pord error (limit position) Ft
I Power supply failed (electrical. pneumatic) R
2 Configuration not valid R
3 New-start-up (wamtstart up) carried out. A
4 Re-start-up (coldstart up) carried out. A
5 Maintenance required Ft
6 Characterisation inva►d R
7 Set to 1 (one), if the (dent Number of the running cyclic data transfer and the value of R
Physical Block IDENT_NUMBER SELECTOR parameter are different.
3 0 7 Reserved for use within the PNO
4 0 ... 6 Reserved for use within the PNO
4 7 More diagnoses information is available
R Indication. remains active as long as the reason for the message exists.
A Indication. will be automatically reset after 10s.
Table 4. Dia nosis Extension Darameter bit-enumeration.
Byte Bit Description Indication
Class
1 0 Pneumatic prestage valve 1 control failure R
1 Pneumatic prestage valve 2 control failure R
2 Position feedback ADC low limit failure R
3 Position feedback ADC high limit failure R
4 Pressure sensor failure R
5-7 -
2 0 EEPROM error R
1 RAM error R
2 ROM error R
3 Processor failure R
4 Board to board communication timeout Ft
5 Write was not successful R
6-7 -
3 0 VaNe bil strokes wameig omit exceeded Ft
I Valve reversals warning limit exceeded R
2 Actuator full strokes warning limit exceeded R
3 Actuator reversals warning limit exceeded R
4 Deviation warning limit exceeded Ft
5 Load factor warning Ind exceeded Ft
6 Deviation alarm limit exceeded Ft
7 Load factor alarm limit exceeded R
4 0 Pneumatics problem R
I Friction problem R
2 Travel deviation alert Ft
3 Load factor alert Ft
4-7
5 0-7
6 0-7
R Indication, remains active as long as the reason for the message oasts.
A Indication. will be automatically reset after 10s.
13(52)
EFTA01216882
Operation
5 Operation
The ND800PA Simatic PDM user interface is divided in three main categories.
• Parameter groups. The static configuration parameters are grouped in logical groups. The
parameters in the groups are presented in the parameter table. The parameter table can
be saved to the Hard Disk. The saved parameter table can be compared with the
parameters in the device.
• Device menu. Device menu contains high-level device functions like Calibration.
• View menu. Unlike the Device menu, the View menu contains only passive elements such
as measured value displays.
In the following paragraphs the ND800PA functionality is described in means of Parameter
groups, Device menu and View menu.
The Parameter groups are presented in figure 12.
Pr SLMATIC PDM - Nd800pa
File Device View Options Help
km slal
' P
it Identification
Operation Unit
IS a Device
IS S Positioner
• CI Static Revision No.
11 Actuator
I Valve
ilatch Information
flings
Assembly Related Configuration
Profibus Communication Fait Safe Action
Servo Controller
Valve Diagnostics
Input
Input Value
Working Range
al Travel Time
'-• ' l-lumon Interface
"clo intenance
Simulation
al Certificates and Approvals
Figure 12. ND800PA Parameter Groups in Simatic PDM.
14(52)
EFTA01216883
Operation
5.1 Identification Group
5.1.1 Operation Unit
TAG
Text; can be used in any way. A recommended use is as a unique label for a field device in
the plant.
Descriptor
Text that is associated with the Field Device. This text can be used by the user in any way.
There is no specific recommended use.
Message
Text that is associated with the Field Device. This text can be used by the user in any way.
There is no recommended use.
5.1.2 Device
5.1.2.1 Positioner
Manufacturer
References a specific manufacturer, which is usually a company name, that is responsible for
the manufacture of this Field Device.
Device ID
Uniquely identifies the Field Device when combined with the Manufacturer Identification and
Device Type. Therefore, this variable cannot be modified by the Host user.
Software Revision
Device software revision number.
Hardware Revision
Device hardware (electronics) revision number.
Serial Number
Uniquely identifies the Field Device. Therefore, this variable cannot be modified by the Host.
Device PCB Serial Number
Device Printed Circuit Board serial number.
Installation Date
The Installation date of the device.
Profile Revision
Revision number of the profile relating to the block.
PROFIBUS Ident Number
Each PROFIBUS-DP device shall have an !dent Number provided by the PNO. There are
profile specific Ident Numbers. A device may have a profile specific one and the manufacturer
specific one. The user is able to choose one of both using this parameter. Selections are
• Profile specific (0x9710)
• Manufacturer specific (Ox052D)
NOTE
The Ident Number can be changed only when the cyclic communication is not active.
5.1.2.1.1 Static Revision No
Physical Block, Transducer Block, Function Block
The revision level of the static data associated with the block. The Static Revision No. is
changed by the device each time a static parameter is changed in value.
15(52)
EFTA01216884
Operation
5.1.2.2 Actuator
Manufacturer
References a specific manufacturer, which is usually a company name, that is responsible for
the manufacture of this Field Device.
Actuator Class
Actuator class is electro-pneumatic.
Actuator Type
Actuator type indication. Options are
• Undefined
• Single acting actuator
• Double acting actuator
Actuator Fail Action
Actuator fail safe position during LOSS OF SUPPLY PRESSURE. This parameter is
informational only.
• Not initialised
• Opening (100%)
• Closing (0%)
• None (Double acting actuator)
Serial Number
Actuator serial number can be written here.
5.1.2.3 Valve
Manufacturer
References a specific manufacturer, which is usually a company name, that is responsible for
the manufacture of this Field Device.
Valve Type
Valve type indication. Options are
• Linear moving valve, sliding valve
• Rotary moving valve, part-turn
Serial Number
Valve serial number can be written here.
5.1.3 Batch Information
Batch ID
Identifies a certain batch to allow assignment of equipment-related information (e.g. faults,
alarms ...) to the batch.
Batch Unit
Identifies the active Control Recipe Unit Procedure or the related Unit (e.g. reactor, centrifuge,
drier).
Batch Operation
Identifies the active Control Recipe Operation.
Batch Phase
Identifies the active Control Recipe Phase.
16(52)
EFTA01216885
Operation
5.2 Settings Group
5.2.1 Assembly Related Configuration
NOTE
These parameters are valve assembly related; you should thus check that the control
valve assembly conforms to the setting of these parameters !
Position Sensor Rotation
Defines relationship between the position sensor rotation and the valve action. If the position
sensor rotates clockwise when the valve closes, set Standard: clockwise to close. With
inverse rotation set Nonstandard: counter-clockwise to close. See /1/ for more information of
operation directions and air connections. Options are
• Standard : Clockwise to close
• Non-standard : Counter clockwise to close
Actuator type
Actuator type selection. Options are
• Undefined
• Single acting actuator
• Double acting actuator
Valve Type
Valve type selection. Options are
• Linear moving valve, sliding valve
• Rotary moving valve, part-turn
Positioner Fail Action
Configuration of the action taken during the LOSS OF SUPPLY POWER (supply pressure is
available). This action takes place ALSO when the positioner software notices a fatal device
failure. In these both cases the spool valve feeds C1 (pneumatic connector) and releases C2
pressure. See /1/ how to set this parameter. Options are
• Close
• Open
Actuator Fail Action
Actuator fail safe position during LOSS OF SUPPLY PRESSURE. This parameter is
informational only.
• Not initialised
• Opening (100%)
• Closing (0%)
• None (Double acting actuator)
Dead Angle Compensation
This adjustment is used to change the valve travel from fully closed to a desired travel with a
small change in input signal near the 0% value of the input signal range. This can be used to
compensate dead angle in a ball or segment valve such that it is equal to the ao adjustment in
conventional Neles positioners. The ac, adjustment is used especially with small ball valves
which require a turn of several degrees from the closed position before any flow through the
valve is perceptible. Suitable ac, values for Neles segment and ball valves can be found in /1/.
See figure 13.
Limit switches
This parameter defines either the limit switches are installed or not. Options are;
• Not installed (default)
• Installed
5.2.2 Profibus Communication Fail Safe Action
Fail Safe Mode
Defines reaction of device if communication fault is still detected after fail safe time. Options
17(52)
EFTA01216886
Operation
are
• Fail Safe Value is used as control regulator input
• Storing last valid setpoint
• Positioner does Positioner Fail Action
Fail Safe Time
Time in seconds from detection of failure in output block up to the output action of the block
output if the condition still exists.
Fail Safe Default Value
Default Value for the setpoint input if communication fault is detected.
5.2.3 Servo Controller
Servo controller gain
The servo controller gain value. This parameter is adjusted automatically during the Automatic
Travel Calibration. After travel calibration the value is 1.0. For enhanced control use value 1.2.
Servo controller parameter D
Servo controller tuning parameter D.
• 0.0 for double acting actuators (factory set)
• 1.0 for single acting actuators (factory set)
Servo controller parameter B
Servo controller tuning parameter B. This parameter is adjusted automatically during the
Automatic Travel Calibration. After travel calibration the value is 1.0.
5.2.4 Valve Diagnostics
These settings are used to set limits for different diagnostics information to warn the user
when the limits are exceeded. The limits should first be set to high values such that no
unnecessary warnings are given. After gaining experience, the user can tune the limits to
more accurate levels.
When a particular limit is exceeded, it is reported in corresponding Diagnosis and Diagnosis
extension status messages.
Supply Pressure
Set this parameter to the average value of the positioner supply pressure. Supply pressure is
used to calculate the load factor.
Travel Deviation Warning Limit
Warning limit for the deviation between the setpoint and actual travel.
Travel Deviation Alarm Limit
Travel deviation alarm limit.
Load Factor Warning Limit
Load factor warning limit. In the case of a single acting actuator, the load factor shows the
actuator load with respect to the present spring force, i.e., a load factor of 100% indicates that
the actual load may exceed the spring force. For double acting actuators, the load factor
shows the actuator load with respect to the user-given supply pressure level, i.e., a load factor
of 100% indicates that the actual load may exceed maximum attainable pressure difference
being equal to the supply pressure. A high load factor indicates the presence of high friction or
an undersized actuator if the given supply pressure is equal to actual supply pressure level.
Load Factor Alarm Limit
Load factor alarm limit.
Valve Full Strokes Warning Limit
Warning limit for the distance the valve has traveled in full strokes. One full stroke means
18(52)
EFTA01216887
Operation
valve movement from 0 to 100%. E.g. if valve moves from 40% to 50% full strokes increases
by 0.1.
Valve Reversals Warning Limit
Warning limit for the number of changes in valve movement direction.
Actuator Full Strokes Warning Limit
Warning limit for the distance the actuator has traveled in full strokes.
Actuator Reversals Warning Limit
Warning limit for the number of changes in actuator movement direction.
5.3 Input Group
The input signal modifications accomplished using Dead Angle Compensation, Cut-Off and
Limit functions are presented in figure 13.
100%
OUTPUT
Dead Angle
Compensation
INPUT 100%
14-
Setpoint Cut-Off CLOSE Setpoint Cut-Off OPEN
Lower Limit Valve Position Upper Limit Valve Position
Figure 13. The input signal modifications accomplished using Dead Angle
Compensation, Cut-Off and Limit functions.
Note:
Setpoint Cut-Off function overrides the Limit function. If Setpoint Cut-Off CLOSE is greater
than 0%, the Lower Limit Valve Position is not applied (has value of 0%). Correspondingly, if
Setpoint Cut-Off OPEN is smaller than 100%, the Upper Limit Valve Position is not applied
(has value of 100%).
5.3.1 Input value
Direction
Direction of positioner. Options are
• Rising (increasing of setpoint input results in opening of the valve)
• Falling (increasing of setpoint input results in closing of the valve)
Lower Value
Defines the operational lower range value of the input value (0%) in engineering units.
19(52)
EFTA01216888
Operation
Upper Value
Defines the operational upper range value of the input value (100%) in engineering units.
Unit (Input)
The engineering unit of the input value.
Setpoint Cut•Off CLOSE
When the servo setpoint goes below the defined percent of span, the valve is driven to the
CLOSED position. See figure 13.
Setpoint Cut•Off OPEN
When the servo setpoint goes above the defined percent of span, the valve is driven to the
OPEN position. See figure 13.
5.3.2 Working Range
Lower Value
Lower Value (Output Signal Range): Lower range value of the process variable (0%) in
engineering units.
Upper Value
Upper Value (Output Signal Range): Upper range value of the process variable (100%) in
engineering units.
Unit (Output)
The engineering unit that the output value is reported in.
Lower Limit Valve Position
Lower limit of the valve position in percent of travel span. Travel span corresponds to the
Output Signal Range (Upper Value and Lower Value). See figure 13
Upper Limit Valve Position
Upper limit of the valve position in percent of travel span. Travel span corresponds to the
Output Signal Range (Upper Value and Lower Value). See figure 13.
5.3.3 Travel Time
Travel Time CLOSE
Setpoint for the time in seconds between the change of the state from OPEN to CLOSED.
Travel Time OPEN
Setpoint for the time in seconds between the change of the state from CLOSED to OPEN.
5.4 Human Interface Group
5.4.1 Maintenance
Calibration Date
Date of last calibration of the device.
Configuration Date
Date of last configuration of the device.
Maintenance Date
Date of last valve maintenance.
5.4.2 Simulation
Simulation
Enable or disable the simulation function.
20(52)
EFTA01216889
Operation
Simulation Value
For commissioning and maintenance reasons, it is possible to simulate the Readback by
defining the value and the status. This means that the Transducer Block and the Function
Block will be disconnected.
Quality
Signal quality information. See table 2.
Limit
Signal limit information. See table 2
5.5 Certificates and Approvals Group
Device Certification
Certification of the device.
21(52)
EFTA01216890
Operation
5.6 Device menu
The items in the device menu are presented in figure 14.
Pr SIMATIC PDM - Nd800po
View Qptions H Ip
Set Address...
Load into Device
Load into ?G/PC
Operal ion
Flow characterization
Valve test lo.
Write Protection
Calibration
Reset
I Assembly Related Configuration
- I Prof bus Communication Fail Safe Action
Figure 14. Device menu items.
5.6.1 Operation
5.6.1.1 Page AUTO
The page AUTO in the operation window is presented in figure 15. From this window it is
possible to change the operating mode of the device and change the value of the auto-mode
valve position setpoint (SP).
Operation - r10800 PA (Online)
AUTO I Remote Caned" (RCAS)1145N I Simulesion
Target Mode IAJTO 3
Actual Mode
Setporit
Setpoint 50 Quality
Limit INot limned
Readback Value
Readback Value 50 61893 Ouality I
brag I 11
Setpont Dewation -0.6041745
Check Back Status OK
Transfer
Close
Figure 15. Operation / Auto.
22(52)
EFTA01216891
Operation
5.6.1.2 Page Remote Cascade
The page Remote Cascade in the operation window is presented in figure 16. From this
window it is possible to change the operating mode of the device and change the value of the
RCAS-mode valve position setpoint (RCAS_IN).
OporoNon - NDSOOPA (OaIS)
AUTO Remote Coscode (RCAS) imAN I Simulation'
Target Mode 'Remote Cascade (RCAS)
Actual Mode
RCAS
RCAS IN Quality Good (Cascade) in=sa4zation acknowledged
Limit INot limited
RCAS OUT
RCAS OUT 50 Quaity IGood (Cascade)
Limit INot limited
Readback Value
Readback Value 50 61024 Quay tOood
omit It -it lir
Setpant Deviabon -0 6020203
Check Back Status OK J
Transfer
Close
Figure 16. Operation / RCAS.
23(52)
EFTA01216892
Operation
5.6.1.3 Page MAN
The page MAN in the operation window is presented in figure 17. From this window it is
possible to change the operating mode of the device and change the value of the manual-
mode valve position setpoint (OUT).
• • NO1100tin • IN
I
AUTO Remote Cascade (RCAS) I Simulation I
Target Mode IMAM
Actual Mode
Output
Output Value 50 Quality Gocd
Limit Net kr ted
Readback Value
Readback Value 5058864 Quality
Limit I
Setpoint Donation -0 7462425
Check Back Update Alert
Transfer
Close
Figure 17. Operation / MAN.
24(52)
EFTA01216893
Operation
5.6.1.4 Page Simulation
The page Simulation in the operation window is presented in figure 18. From this window it is
possible to enable/disable the simulation function and simulate the Readback value and
status.
When simulation is enabled, the Analog Output Block and the Tansducer Block are
disconnected. The simulation value and status are copied to the AO Block Readback signal.
Simulation is useful during the device commissioning and maintenance.
Cperotion - NDS00PA (Online)
AUTO I Remote Cascade (RCAS) I MAN Simulation
Simulation lEnabred
Simulation
Simulation Value 10 Quality IGood
Lynn INOt limited
Setpoint Deviation -0.7350807
Check Back Simulation enabled.
Close
Figure 18. Operation / Simulation.
25(52)
EFTA01216894
Operation
5.6.2 Flow characterization
When optimizing process control loop performance a linear relationship between the flow and
valve position setpoint signal should be established. This can be achieved by using this flow
characterization design tool.
Valve inherent flow characteristics curve tells the (normalized) valve capacity (effective flow
cross-section) versus the valve position. This curve is specific to the physical valve design.
Valve installed flow characteristics curve tells the (normalized) flow versus the valve position.
This curve is the result of the inherent flow characteristics curve and the process pressure
behavior.
The flow characterization design tool changes the valve inherent flow characteristics curve to
any desired curve. Current inherent characteristics table tells the flow characteristics
without any signal modifications. Desired inherent characteristics table tells the desired
characteristics. Based on this information, the tool calculates the required signal modification,
Signal modification table, which is as well user editable.
Current inherent characteristics table (Figure 19)
This table tells the inherent flow characteristics without any signal modifications (flow
characterization is off). The table values are the relative flow coefficients at corresponding
valve openings.
Desired inherent characteristics table (Figure 20)
This table tells the desired inherent flow characteristics. The table values are the relative flow
coefficients at corresponding valve openings.
Fill table (Figures 19 & 20)
• User defined - When this option is selected, the table can be entered by user.
• Linear - Fills the table with linear characteristic values.
• Equal percentage 1:25 - Fills the table with Equal percentage characteristic values.
• Equal percentage 1:33 - Fills the table with Equal percentage characteristic values.
• Equal percentage 1:50
• Quick opening (Equal percentage inverse 1:25)
• Quick opening (Equal percentage inverse 1:33)
• Quick opening (Equal percentage inverse 1:50)
• Neles L1-series butterfly valve - Fills the table with Neles specific characteristic values.
• Neles R-series segment valve - Fills the table with Neles specific characteristic values.
• Neles M-series ball valve - Fills the table with Neles specific characteristic values.
• Clear - Clears the table.
Signal modification table (Figure 21)
Signal modification table. The table values are inputs at corresponding outputs.
Characterization (Figure 21)
This parameter controls the characterization. Options are:
• Off - Shows the active state or turns the characterization off.
• On - Shows the active state or turns the characterization on.
• Calculate new Signal mod table from CURRENT and DESIRED tables
• Clear Signal mod table
• Enable new Signal mod table using all table values
• Enable new Signal mod table using every second table value. This option fills the missing
points using linear interpolation.
26(52)
EFTA01216895
Operation
NOTE:
If the installed flow characteristics curve is known, this tool can ALTERNATIVELY be used to
modify the installed characteristics. In this case all the words INHERENT in the tool must be
understood as INSTALLED. The installed curve can be found by a simple process test or it
can be calculated by the Nelprof software.
NOTE:
The dead angle compensation is done before the characterization.
Flow chorootorizotion - 140800e4 (Online)
Curren( inherent characteristic-alai:4e I Dwslredmhoront chanadensics table I Signal modOrention !able I Curse
0% Rel flow 55% 0 177 Rd flow
5% 0 0358 Rd flow 60% 0 2166 Rd flow
10% 0 0127 Rd flow 65% 0 2638 Rd flow
15% 0 0209 Rel flow 70% 0 32 Rel flow
20% 0 03)7 Rd flow 75% 0 3869 Rd flow
25% 0 0423 Rd flow 80% 0 4666 Rel flew
30% 0 0562 Rd flow 85% 0 5616 Rd flow
35% 0 0727 Rel flow 90% 0 6746 Rd flow
40% 0 0924 Rd flow 95% 0 8093 Rd flow
45% 0 1159 Rel flow 100% Rd flow
50% 0 1438 Rd flow Fill table 'Equal percentage 133 B
Transfer
Close
Figure 19. Current inherent characteristics table.
27(52)
EFTA01216896
Operation
Flow characterization - ND800PA Online
Omani inherent chatactneislics tab,* Dewed inherent characienshcs iabie I signal modecabon liable I Curves I
0% 0 Rd flow 55% 0 5500001 Rd flow
5% 005 RN flow 60% 0 6000001 Rel flow
10% 01 Rd flow 65% 0.6500001 Rel flow
15% 0 15 Rel flow 70% 0.7000001 Rel flow
20% 0 Rel flow 75% 0 7500001 Rel flow
25% 0 25 Rd flow 80% 0 8000001 Rel how
30% 03 RN flow 85% 0 8500001 Rel flow
35% 0 35 Rd flow 90% 0 9000002 Rel flow
40% 04 Rd flOw 95% 0 9500002 Rel flow
45% 045 Rd flow 100% Reiman
50% U ,ITAILI1 Rd flow Fill table 'Lineal
Itansfer
Close
Figure 20. Desired inherent characteristics table.
Flan characterization - I4b800PA (Online) El
Curedinherent chreactansbcs table I [Petted inherent thatactensbet table signal mociaicabon table I Calves I
0% % 55% 84 38902
5% 27 76779 % 80% 86 89898
10% 41 61634 % 65% 88 91118
15% 50 93346 % 70% 90 94279
20% 57 90331 % 75% 92 79863
25% 63 5374 % 80% 94 65448
30% 68 22008 % 85% 96 06708
35% 72 24183 % 90% 97 37798
40% 75 82175 % 95% 98 68887
45% 78 95811 % MO% 100
50% 81 75772 % Characterization
Transfer
Close
Figure 21. Signal modification table.
28(52)
EFTA01216897
Operation
The page "Curves" shows the Current. Desired and the signal modification tables in graphical
format.
Flow characterization - FJ0H00PA (Online)
Curzenlinhereal chemaclanslics table Desired inherent chtuacierislics table Signal mcialicabon fable ;Surma
0
-
8I
OO
on
O
O
O
I I 1 1 1 1 1 1 1 1
0 10 20 30 40 50 60 70 80
inpuVvah(e position IN
Close
Figure 22. Curves.
29(52)
EFTA01216898
Operation
5.6.3 Valve test
To ensure that the control valves are working properly they can be tested with the Testing
function. Two control valve performance tests, the Hysteresis loop and Step response, can be
run with the device. The Step response test tells how rapidly the valve reacts to the input sig-
nal, while the Hysteresis loop test tells how large is the dynamic hysteresis + dead band,
which indicates friction quantity. The control valve test results can be used to diagnose the
condition of the control valve, thus showing the need for possible future maintenance work.
Running control valve tests is, therefore, very important predictive maintenance work and en-
sures optimal performance of the control valve in every situation. Note that control valve test-
ing affects process control by driving the control valve independently of the input signal from
the control system !
The valve test control page is presented in figure 23. Before starting the test, adjust the test
settings. Test can be started by pressing the button "Start test". Test can also be cancelled
any time by pressing the button "Cancel test". The dialog "Test state" shows the current sate
of the test procedure.
The graphic window shows the on-line measurements; Positioning value and Feedback value.
The window axis can be adjusted by double clicking the window. The purpose of this window
is just for monitoring the test execution. This window is not intented to be used to examine
the test results, since the sampling time is too long and not constant.
After successful' test, the test results can be found from the pages Step response test results
(fig 24) and Hysteresis test results (fig 25). The data for these graphs is collected by the
device itself. The data size is 50 measurement points.
Shah,. le st I Sep reset-detettretell I11yaereststest meals I
Test tetanal 0 e
Test type Iklysterests loop test :J 0P
Test starbng stout 0
Loop or step size 100 96
Test duratron 100
Test control
Test State
Start test
Cancel test
Figure 23. Valve test.
30(52)
EFTA01216899
Operation
Valve test - HOODOPA (Online) El
V k. k i t Step *sows kS s I Hyoranos IN mar I
Last lost stamps
±Ig
TeS1POS
Teststarting seeponi 20
• oo
Loop or stop we 40 •-• 0
m
E
!so0
Tes1clursOon
£o
• 0
CI
O
00 0.1 02 0.3 04 0.5 06 0.7 0.8 09 10
Time Is) NJ
close
Figure 24. Page Step response test results.
VIMIP I S1gworm 111thrluit HY204*1 teN MUM
LOU lest selling:
ilg
Test Ape
Test staling spooro a
—
at 0
LOOP or am site 100
£O
si F-
Test cluralm 100 mop
0
E0
a co
o
ole N
O
O
0 10 20 30 40 50 60 70 80 90 100
Position setpon [96)
close Help
Figure 25. Page Hysteresis test results.
5.6.4 Write Protection
The window Write Protection is presented in figure 26. From this window it is possible to
configure three different write protection options
• HW Write Protection. Indicates the position of a hardware jumper which protects all acyclic
write access to all writeable parameters of a device.
• SW Write Locking. Protects all acyclic write access to all writeable parameters of a device
except this SW Write Locking one. Selections are On and Off.
• Local Operation. Enables/Disables the local operation of the device. The operation of the
host has higher priority then the local terminal one. If communication fails for a time greater
30 sec, local operation will be enabled automatically. Communication failure is defined here
as absence of cyclic and acyclic communication for the specified time period. If Local
Operation parameter is disabled and the communication is working again, then the device
switch back to remote operation.
31(52)
EFTA01216900
Operation
Write Protection - NbS00PA (Online) El
Write Protection
HW Write Protection'
SW Write Locking IOff
Local Operation 'Enable°
Transfer
Close
Figure 26. Write Protection.
32(52)
EFTA01216901
Operation
5.6.5 Calibration
5.6.5.1 Page Calibration
The page Calibration in the Calibration window is presented in figure 27. From this window it is
possible to run following calibration routines
• Automatic Travel Calibration. This calibration calibrates the position sensor range and
tunes the servo control tuning parameters. This calibration must be done during the device
commissioning.
• Position Sensor Calibration. This calibration is needed only when the position sensor
module is replaced. Position sensor is factory calibrated.
• Pressure Sensor Calibration. This calibration is needed only when the pressure sensor
module is replaced. Pressure sensor is factory calibrated.
• Temperature Measurement Calibration. This calibration calibrates the on-board
temperature measurement. Temperature measurement is factory calibrated.
Each calibration routine prompts and advises the user via dialog boxes.
Calibnrtion - NDB00PA (Online)
User delined table, pad 1 User defined table, part 2
Calibration Position Sensor Temperature Compensation
Automatic Travel Calibration
Operation Status
Cancel
Module Calibration
Start Position Sensor Calibration
Start Pressure Sensor Calibration
Start Temperature Measurement Calibration
Close
Figure 27. Calibration.
33(52)
EFTA01216902
Operation
5.6.5.2 Page Position Sensor Temperature Compensation
The page Position Sensor Temperature Compensation in the Calibration window is presented
in figure 28. From this window it is possible to configure the position sensor temperature
compensation. Options are
• Compensation off. This selection turns the compensation off.
• Compensation on, User defined table. This selection turns the compensation on and uses
the User defined table. User defined table (part 1 of 2) is presented in figure 29.
• Compensation on, Default table. This selection turns the compensation on and uses the
default compensation table stored in the device memory (permanently).
The position sensor temperature compensation is factory configured. The configuration is
needed only when the position sensor module is replaced.
Calibration - Nb800PA (Online) El
User defined table, part 1 User defined table, part 2
!I-- Calibration Position Sensor Temperature Compensation
Position Sensor Serial Number 1 1
Temperature Compensation Compensation on; Default table
Compensation off
Compensation on. User defined table
Compensation on Default tat:I:
Transfer
Close
Figure 28. Position Sensor Temperature Compensation.
34(52)
EFTA01216903
Operation
Calibration - NDSOOPA (Online)
Calibration Position Sensor Temperature Compensation
User defined table, patt 1 User defined table, part 2
Min -40°C 43 4576 % Max -40°C 522259
Min -35°C 43 4576 % Max -35°C 52.6243
Min -30°C 43 4576 % Max -30°C 52.9817
Min -25°C 43 4576 % Max -25°C 53.2993
Min -20°C 43 4576 % Max -20°C 53.5789
Min -15°C 43 4576 % Max -15°C 53.8219
Min -10°C 43 4576 % Max -10°C 54.0307
Min -5°C 43 4576 % Max -5°C 54.2074
Min 0°C 43 4576 % Max 0°C 54.354
Min 5°C 43 4576 % Max 5°C 54.4728
Min 10°C 43 4576 % Max 10°C 54.5659
Min 15°C 43 4576 % Max 15°C 54.6353
Min 20°C 43 4576 % Max 20°C 54.6828 %
Transfer
Close
Figure 29. User defined temperature compensation table, part 1.
5.6.6 Reset
5.6.6.1 Page Factory Reset
The page Factory Reset in the Reset window is presented in figure 30. From this window it is
possible to carry out three different reset functions
• Factory Reset resets device parameters to default values. The bus address remains the
same.
• Warmstart of the device. All parametrisation remains unchanged.
• Reset the bus address to value 126.
35(52)
EFTA01216904
Operation
Reset - N0800P A (Online)
Factory Reset I Reset Diagnostics
Factory Reset Factory Reset
No function
Check Back Factor/ Reset
Warmstart
Reset Address to '126'
Diagnosis Power supply failed. J
More information available.
-I
Diagnosis Extension Pneumatics problem
Transfer
close
Figure 30. Factory Reset.
5.6.6.2 Page Reset Diagnostics
The page Reset Diagnostics in the Reset window is presented in figure 31. From this window
it is possible reset following diagnostic trends
• Event history
• Travel Deviation trend
• Valve travel vs. time trend
• Load Factor trend
• Valve travel counters
• Actuator travel counters
Factory Reset Reset Diagnostics I
Reset Diagnostics Valve travel counters
None
Event history
Travel deviation trend
Valve travel vs time trend
Load factor trend
Actuator travel counters
Transfer
Close
Figure 31. Reset Diagnostics.
36(52)
EFTA01216905
Operation
5.7 View menu
The items in the view menu are presented in the figure 32.
F' SIMATIC PDM - Nd800po
elle Device Qptions yelp
lid id ti_14 Display
Device Status
'dent Valve Diagnostics
of Event Log
R D.
Ioolbar
A fa
atatus bar
Update F5
I e
- I Batch Information
Figure 32. View menu.
5.7.1 Display
5.7.1.1 Page Measured Value
The page Measured Value of the window Display is presented in the figure 33. This window
monitors the Setpoint, Readback value and related information.
toispkoy - t4P800Pe (Online)
Measured Value I Output I
Readback value 50.49236 %
0% 60% 100%
Readback Value
Readback Value 6049236 Quality I J
Limit I 'ite
Segura
Setpoint sci ouamy
Limit ►'
Valve Position
Selpoint De Cation 30 28838
Check Back Status OK
Close
Figure 33. Display I Measured Value.
37(52)
EFTA01216906
Operation
5.7.1.2 Page Output
The page Output of the window Display is presented in the figure 33. This window monitors
the AO Block Output and Positioning value. The signal modifications presented in figure 13
and characterization impact between these two signals. Positioning value is the final servo
control setpoint after all signal modifications.
Display - ell)800PA (Online)
MeoswedVdue °ItPul
Output Wet* 50 %
0% 60% 100 %
Output Value
Output Value 50 A% Quaky I
Limit I ted
Positioning Value 80.80146 %
0% 60% 100%
Positioning Value
Postponing Value 80 80146 % Ouatity IbuuJ
Limit
Check Back Status OK
Close I HO) I
Figure 34. Display I Output.
38(52)
EFTA01216907
Operation
5.7.2 Device Status
5.7.2.1 Page General
The page General of the window Device Status is presented in the figure 35. This window has
first some identification parameters and the last three ones are diagnostic parameters.
Device Status - Nb800PA (Online) a
General I profile I
TAG NDBOOPA
Manufacturer
Device ID NDBOOPA
Serial Number 2000390016
Software Revision 1.00
Hardware Revision 0.20
Installation Date 01.01.2000
Check Back Status OK
Diagnosis Power supply failed.
More inforrnabon available.
Diagnosis Extension Pneumatcs problem
Close Help
Figure 35. Device Status \ General.
Parameters Checkback, Diagnosis and Diagnosis Extension report the device diagnostic
status messages. These parameters are explained in tables 1, 3 and 4, correspondingly.
39(52)
EFTA01216908
Operation
5.7.2.2 Page Profile
The page Profile of the window Device Status is presented in the figure 36. This window
monitors the revision level of the static data associated with the three blocks. The Static
Revision No. is changed by the device each time a static parameter has changed in value.
Device Status - N0800PA Online
General Profile
Profile
Profile Revision I
—Static Revision No.
Physical Block 11
Transducer Block 4
Function Block 23
Close I Help I
Figure 36. Device Status 1Profile.
40(52)
EFTA01216909
Operation
5.7.3 Valve Diagnostics
The ND800PA valve controller continuously monitors control valve behavior. It records valve
travel trends, histograms and possible alerts. Trends and histograms show how the valve has
operated over a long time period. Alerts tell about the latest problems in control valve
operation including control behavior and ND800PA valve controller faults. Valve and actuator
travel distances and reversals are also counted to inform the user of the need for
maintenance.
All the diagnostics information is very important for the process control and maintenance
needs. Diagnostics information is on-line data which allows the process automation people to
check the condition of the control valves anytime needed. This checking is done in real-time
and it does not disturb the process. With these trends, histograms, travel distance and
reversal counters and alert reports user can schedule the maintenance needs for the control
valves. This is highly important predictive maintenance and it allows control valves and
therefore the whole process to work more accurate and more reliably.
5.7.3.1 Page Measurements Trend
The page Measurements Trend of the window Valve Diagnostics is presented in the figure 37.
This window trends following measurements
• The Actuator Pressure Difference graph can be used to check that the control valve is
working properly. With the aid of pressure information, possible friction and actuator
leakages can be discovered by comparing prevailing and previous pressure curves.
Actuator pressure is the pressure difference in double-acting actuators and the pressure
opposed to the spring in single-acting actuators.
• The Device Temperature graph shows the temperature inside the ND800PA valve
controller on the PCB (Printed Circuit Board). The temperature information can be used for
checking that the environmental temperature is within specified ambient temperature limits.
This ensures reliability of the ND800PA valve controller.
• Device operation time. This comprises the total time during which the valve controller has
been operating, and is displayed in hours. Resetting the diagnostics does not affect the
total time.
41(52)
EFTA01216910
Operation
Valve Diagnostics - ND800PA (Online)
Travel Deviation Tread Valve Travel vs. Tine Trend
Measizements trend Travel Counters Actuator Load Facto' Trend
a
Jo
evice temperature [°
16:30 16:35 16:40 16:45
11/9/0 Time 11/910 Ri
Device temperature 24.90566 IC
Actuator Pressure Difference 0 2788844 bar
Device Operation time 0.72897
Close I Help
Figure 37. Valve Diagnostics 1 Measurements Trend.
42(52)
EFTA01216911
Operation
5.7.3.2 Page Travel Counters
The page Travel Counters of the window Valve Diagnostics is presented in the figure 38. This
window monitors following parameters
• Valve number of full strokes. The distance the valve has traveled in full strokes. One full
stroke means valve movement from 0 to 100%. E.g. if valve moves from 40% to 50% full
strokes increases by 0.1.
• Valve number of reversals. The number of changes in valve movement direction.
• Actuator number of full strokes. The distance the actuator has traveled in full strokes.
• Actuator number of reversals. The number of changes in actuator movement direction.
Valve Diagnostics - N0800PA (Online)
Actuator Load Factor Trend I Travel Deviation Trend I Vette Travel vs. Time Trend
Measurements trend Travel Counters
Valve
Full Strokes 39 04157 Warning limit 250000
Reversals 2667 Warning limit 1000000
—Actuator
Full Strokes 39.04157 Warning limit 250000
I
Reversals 2667 Warning limit 1000000
IN
Close Help
Figure 38. Valve Diagnostics 1 Travel Counters.
43(52)
EFTA01216912
Operation
5.7.3.3 Page Travel Deviation Trend
This trend shows the deviation between the setpoint and actual travel during total valve
operation time. The travel deviation trend can be used to analyse present and predict future
behaviour of the control valve. The travel deviation is not updated when the valve is
appropriately fully open or closed.
Valve Diagnostics - ND800P A (Online) El
Measurements trend Travel Counters
Actuator Load Factor Trend Travel Deviation Trend Valve Travel vs. Time Trend
Jo
co _
r--
O <0
i
a) to -
TD
>
cn
O
I I I I I I I I I
-500 -400 -300 -200 -100 0
Time [h]
Travel Deviation Warning Limit 2
Travel Deviation Alarm Limit 10
Close Help
Figure 39. Valve Diagnostics I Travel Deviation Trend
44(52)
EFTA01216913
Operation
5.7.3.4 Page Actuator Load Factor Trend
This trend shows the load factor of the actuator as a percentage. In the case of a single acting
actuator, the load factor shows the actuator load with respect to the present spring force, i.e.,
a load factor of 100% indicates that the actual load may exceed the spring force. For double
acting actuators, the load factor shows the actuator load with respect to the user-given supply
pressure level, i.e., a load factor of 100% indicates that the actual load may exceed maximum
attainable pressure difference being equal to the supply pressure. The trend can be used for
analysing the condition of the control valve. A high load factor indicates the presence of high
friction or an undersized actuator if the given supply pressure is equal to actual supply
pressure level. The load factor is not updated when the valve is appropriately fully open or
closed.
Valve Diagnostics - NDS00PA. (Online)
Measurements trend Travel Counters
Actuator Load Factor Trend I Travel Deviation Trend Valve Travel vs. Time Trend
Jo
_
00 —_
o
—r--
0 _
.es (.0 —
to:
in
0
0 ‘ r
07-
O
C•I
O
I I I
-500 -400 -300 -200 -100 0
Ti me Ill
Load Factor Warning Limit 50
Load Factor Alarm Limit 85
Close I Help I
Figure 40. Valve Diagnostics 1 Actuator Load Factor Trend
45i:52)
EFTA01216914
Operation
5.7.3.5 Page Valve Travel vs. Time Trend
The histogram illustrates the valves opening history as percentages of total valve operation
time. Valve opening is on the horizontal axis and percentages of operation time on the vertical
axis. This histogram can be used to check valve sizing. If the valve operates mostly in small
openings, this indicates that the valve is oversized for the application.
Elapsed trend time reports the time during which the data for the statistics displayed have
been collected, and is displayed in hours.
Valve Diagnostics - N0800P A (Online)
Measurements trend Travel Counters
Actuator Load Fedor Trend I Travel Deviation Trend Valve Travel vs. Time Trend
±4 I
o
00
E r--
ID
c0
20
-0 in —
a> 0 .1
ay —4
(c)
a)
0
e
a0
0
0 10 20 30 40 50 60 70 80 90 100
Valve travel [%]
Elapsed trend time 0.1491667 h
Close I Help
Figure 41. Valve Diagnostics I Valve Travel vs. Time Trend
46(52)
EFTA01216915
Operation
5.7.4 Event log
Event log holds 20 latest events and failures stored in the ND800PA memory.
• Event - Event description.
• Count - Number of consecutively occurred events.
• Time stamp - Event time stamps represented in device operating hours. If there are
consecutively occurred events, the time stamp reports the last event occurrence time.
Figure 42. Event Log, part 1.
47(52)
EFTA01216916
Appendix A. Parameter table
6 Appendix A. Parameter table.
The ND800PA parameters can be accessed by using an OPC or DDE server from any
vendor. The parameters are listed in the following table.
Table 5. ND800PA Parameter table.
mot Met Ele- Default Obied Parameter Delia101011 Deta it Of Can reed
merit Value Type ele- vats
— - — manta —
Device ManagemeM
1 0 HEADER unagria016 6 r
1 04003 Dir ID Directory ID (reserved)
2 Oxi)301 Nin_Dir_Rev Directory Revision Number
3 Ox0001 Num_Dir Obj Number of Directory Object (Directories)
0 WON Num_Dir Entries Total Number of Directory EntrieS
5 OxIXODI Fing_Corrp_Dir_EntrY Entry number of first Composite Lot Dr
Entry
6 OnC003 Num Comp_DirEntry Runner of COrrpteite liat Directory EnMea
1 1 COMPOSITE_LIST_DIRECTORY_EN unsigned18 12 r
TRY
1 Onl)104 Slart_PS_Ref Directory Index Physical BIM* (Resource
Mock)
OXCODI Num_PB Number of Physical Blocks (1)
2 Oxi)105 Mart_First_IttRef Directory Index tor Met Transducer Block
Oxi1001 Nurn_TEI Number of Transducer Blocks
3 NOM Mart_FirstiltRef Directory Index for eru Function Block
Oxi1001 Num FEI Number of Function Mocks
4 WAGE Slot_Inclex_PS COmmuniteliOn relMed address index 00 PB
Oxi)022 Num PO Panto (Ind. reserved cells)
5 NOM Slot_Index_TB (Abaolote index)
0x00C9 Num TEt_Param (Ind. rezoned cells)
8 043110 Slot Index Fe (Absolute index)
OnC032 Num; Ftisarem (Ind reserved cells)
Phyikel Block
1 14 BLOCK OBJECT Mock characteristic ds32 1 r
1 0 reserved
2 WI Block Object Mock type (physical)
3 OWT2 Parent Class
4 0 Class
5 exC00000110 00-Reference (reserved)
6 MOW 00-RevieiOn (reserved)
7 014002 Profile PA profile number assigned by PNO for
PROFIBUS - PA a 64. Compact CMS* B
8 Ox03110 Profile Revision
9 NCO Execttlon Time for Mute use
10 Oxi:022 Number of Parameters
11 Oxi:040 Index of VIEW 1
12 NW Number of View Lists
1 15 0 ST_REV Counter that is incremented on every unsignedIS 1 r
Charge of antiguration parameters
1 18 TAGDESC Ursque lag in the system that the user can visible shin 32
SPOOKY 9
1 17 0 STRATEGY Strategy Value can be mitten to by user for unsgred115 1
alarm processing
1 16 0 ALERT KEY unsgred8 1
1 19 048 TARGET MODE Target mode of the PB • Auto unagned8 1
1 20 MODE_BIK Block mode d537 1 r
1 Ox08 Actual Auto
2 048 Permitted Auto
3 048 Normal Auto
1 21 ALARKI_SUNI Alarm status d542 1 r
1 Oxi)000 Current Marro
2 MOW UnactooMedged
3 MOW Unreported
4 OxiXID3 Disabled
22 10 SOF TWARE_REVISION Software Revision OCR/liana 16 r
23 0.2 HARDWARE RELOSICN Hardware Ronson collet string 18 r
24 Melee DEVICE_MAICID Manufacturer iflonoticabco unsIned16 1 r
Autornation
25 1.0800PA DEVICE-ID visitre_strin le r
g
26 DEVICE_SER_NUM Deice serial number visble_strin 16 r
9
27 DIAGNOSIS Diagnostic infcemaficn (bit-ceded) octet song 4 r
28 DIAGNOSIS_EXTENSION Manufacturer Specie extension to ottet_elring 6 r
DIAGNOSIS
29 OxFFFF0080 DIAGNOSIS_MASK BEN Sul/POMO by DIAGNOSIS OCIet_etring 4 r
30 Ox3F3FFFOF DIAGNOSIS_MASK_EXTENSICN Ens supported by octet sling 8 r
0000 DIAGNOSIS_EXTENSION
31 4. DEVICE CERTIFICATION meet string 32 r
32 2457 WRITE IOCKING Write Prealsainn selection unsined16 1 Lw
33 0 FACTORY RESET Reset device to default values untagned16 1 w
34 4. DESCRIPTOR octet siring 32
35 -1- DEVICE_MESSAGE Ottet_etrOg 32
36 1.1.2000 DEVICE INSTAL DATE Date of device installation octet string 18
37 1 LOCAL -CP_ENA- Enable I Made local operation unsinece3 1
38 I ICENT_NUMBER_SELECTOR Switch: Profile ID/ Manufacturer ID unsigned8 1
39 0 NW_WRITE_PROTECTION InIcates the state of the wee protection
DIP snatch
47 0 DEVICEPCS_SN
_ r
78 VIEW_I struct 4 r
1 1 ST REV
2 6 AKIDE_FILK
3 7 ALARIA SUIA
4 13 DIAGNOSIS
Transducer Block
48(52)
EFTA01216917
Appendix A. Parameter table
901 lodes En, (1.3faffli Parameter Qin)CrOlJon Data 4 01 Co:tic feel
rent Value Type els- unite
mrits
e
2 0 BLOCK_OBJECT BIOCk CharaCtertallc r
1 010 reserved
2 Ox1:0 13100 Object Block type IttanaduCel
3 045 Parent Class
4 Ox02 Class
5 0480000000 DO-Reference (reserved)
6 018000 0O-Revan (reserved)
7 014002 Profile PA profile number assigned by PNO for
PROFIBUS - PA • 64. Compact Class B
8 018300 Profile Revision
9 &CO Exec./Jon Tine for figure use
10 01O3O9 Number a Parameter*
11 O400D2 Index of VIEW 1
12 01D1 Number of Mew LIM
2 1 0 ST_REV Counter that is incremented on every unsignedIS 1 r
change of configuration paratnecers
2 2 TAG_DESC Unique lag In Ile system that the user Can vis•Dle_strin 32
aPecifY 9
2 3 0 STRATEGY Strategy Value can be mitten to by use lot unsignedIS 1
abut+ Processing
2 4 0 ALERT KEY unsignect9 1
2 5 0408 TARGET MODE Target mode of the TRANSDUCER • Auto unsigned8 1
2 6 MOOE_BIK Block mode cle37 1 r
1 0108 Actual Auto
2 0108 Permitted Auto
3 0108 Normal Auto
2 7 ALARM SUM Marro status ds42 I r
1 MOW Commt_Nann
2 &DM Unacknowledged
3 010000 Unreported
4 &DM Disabled
2 23 1 12000 DEVICE_CALIB_DATE Calibration date or bit device OctelSffing
2 24 1.1.2000 DEVICE CONFIG DATE Configuration date of he device OctelSting
2 25 0 LIN TYPE Linearization type Unsigned8
2 32 100 RATED_TRAVEL Rated travel or the valve Fiord
2 33 0 SELF_CALIB_CMD Calibration Man Unsigned8
2 34 0 SELF_CALIB_STATUS SWAN of caibrabon Unsigned8 r
2 35 1.0 SERVO GAIN I Servo controller gain Flea
2 38 2 SETP_CUTOFi_DEC RetpOint CutOrl Fleet
2 39 100 SETP CUTOFF INC Selpoint ousaft Float
2 47 0 TRAVIL_LOAT:LOW Valve OOSitiOn lirnItalion Float
2 48 100 TRAVEL Liken' UP Valve position limitation Flea
2 49 0 TRAVEL RATCCEC Travel rate limitation Flea
2 50 0 TRAVEL_RATE_INC Travel rate limtation Float
2 51 1.1.2000 VALVE MANI DATE Date of valve maintenance OctelSting
2 57 POSITIONINGVALUE Valve positon selp0int alter all signal DS_33 r
modifications
1 0 Value IEEE-754 4
goat
2 Status unsignecIS I
2 58 FEEDBACK VALUE Measured valve position DS 33 r
1 0 Value IEEE-754 4
float
2 Status unsgred8 I
2 59 IMMO VALVE_MAN Valve mitnutadurer 0001501no
Automation
2 60 Mele0 ACTIJATORJAAN Attalla manufacturer OcteiSting
Automation
2 61 1 VALVE_TYPE Valve type Unsigned8
2 82 0 ACTUATOR CLASS Actuator class (always electropnewmatc) Unsigned8
2 63 0 ACTUATOR FAIL_ACTION Actuator fail safe position Sang LOSS OF Unsigned8
SUPPLY PRESSURE. INS parameter is
informational orly.
2 64 VALVE_SER_NUM Valve semi number OCI0150ing
2 65 ACTUATOR SER_NUAI Actuator social number OctelSting
2 66 4- ADDJ3EAR_SER_NUM Serial No or the gearing OO•1501n2
2 87 4- ADD_GEAR_MAN Goading rnanufactwer OctelSting
2 68 4- ACO_GEAR_ID Gearing identraCetiOn OO•1501n2
2 69 1 1.2000 ACO_GEAR_INST_DATE Dace or installation of gearing OCIMS01n2
2 100 00 Servo controller tuning paranoia D foal
2 102 10 SERVO PARAMJ3 Servo controller twins par Meer B float
2 104 0 ACT TYPE Actuator type Unsigned8
2 105 0 LIMITSV/ITCHES Lent *meth pmsen0e Selection Unsig1808
2 106 5 SUPPLY PRESSURE Supply pressure estimate Owl
2 108 0 POSITIONER_FAIL_ACTION Confgurat0n or tne action taken during the Unsigned8
LOSS OF SUPPLY POWER (supply
preface a available). Rob eCtlOn takes
pace ALSO Men the postloner software
notices a fatal device faiure.
2 110 1 POS_SENSCR_ROT Position sensor notation Unsigned8
2 112 0 DEAD ANGLE_COMP Dead ngle compensation float
2 114 0 SOVRCE_CHARACTERISTICS_TAB 500r03 theraCtibiSaCSIable snug
LE
11021 lable_valoe Relative law afenKieneS float
22 none FILL_TABLE Fill table Unsigned 8
2 116 0 TARGET_CHARACTERISTICS_TABL Target Characteristics table snug Lw
E
1 to 21 tabla_valua Relative Sow coefficients foal
22 none FILL_TABLE Fill table Unsigned 8
2 118 0 SIGNAL_MOD_TABLE stud
11021 table_value Output values fl0at
49(52)
EFTA01216918
Appendix A. Parameter table
Bbl Index Ele- Default Oq Para/rater Data N of Oatao read
mart Value _ WON ale- wilts
ments r.
2 of, CHARACTERIZATION ChareCteniation wnb01 Unsigned a
2 120 ACT PRESSURE Actualeor pressure difference measurement foal r
2 122 OEV_TEMPERATURE 00.+00 temperature messuremeni iloal r
2 124 OPERATION TIME Device operation lime foal r
2 126 EVENT_LOG_EVENT_TABLE Event 109 filnift r
1 to 20 table valise Unsigned16
2 128 EVENT_LOC_COVNT_TA131E Event tog filnift r
1 10 20 table_value tOnsIgne016
2 130 EVENT_LOG TIME_TABLE EveN log slruct r
1 10 20 table_value float
2 132 TRAVEL_DEVIATION_TRENCI_TIME Travel deviation trend duct r
TABLE
1 to 20 Estate valise noel
2 134 TRAVEL_DEVIATICOLTRENO_ERRO Travel deviation Rend Sired r
R TABLE
1 10 20 tablevalue float
2 135 2 TRAVEL_DEVTATION_WARNING_LI Travel deviation nand flOal
MIT
2 136 10 TRAVEL_DEV1ATION_ALARM_LPAIT float
2 138 VALVE_TRAVEL_VS_TIAIE_TRENO stud r
110 10 table_valua float
2 11 ELARSED_TFtENO_TIME float r
2 140 LOAO_FACTOR_TRENO_TIME_TAB Sired r
LE
1 10 20 labie_velve float
2 142 LOAO_FACTOR_IRENO_FACTOR_T Sired r
ABLE
1 10 20 tabse_value float
2 103 50 LOAD_FACTOR_WARNING_LIAUT foal
2 144 85 LOAD_FACTOR_ALARM_LIMIT float Lw
2 148 VALVE_TRAVEL_COUNTERS duct r
2 1 FULL_STROKES float r
2 2 250 000 FULL_STROKES_WARNING_LIAIIT Unsigned32
2 3 REVERSALS tOnsIgne032 r
2 4 1 066 D30 REVERSALS_WARNING_LIMIT tOnsIgne032
2 108 ACT_TRAVEL_COUNTERS struct r
2 1 FULL_STROKES float r
2 2 250 000 FULL_STROKES_WARNING_LIAIIT Unsigned32
2 3 REVERSALS tOnsIgne032 r
2 4 1 003 000 REVERSALS_WARNING_LIMIT Unsigned32
2 150 0 RESET_CHAONOSTICS tOnsIgneatt
2 152 VALVE TEST stud
2 1 Step TEST TYPE tOnsIgne016
2 2 20 TEST_STARTING_SETPOINT float
2 3 20 TEST_LOOR_Cft_STER SIZE float
2 4 10 TEST DURATION float
2 5 idle TEST START Unsigned8
2 154 LAST_VALVE_TEST_SETTINGS filnift r
2 1 TEST TYPE Unsigned16 r
2 2 TEST_STARTING_SETPOINT float r
2 3 TEST_LOOR_CA_STER SIZE float r
2 4 TEST DURATION float r
2 156 LAST_VALVE_TEST_SP_OR_TIME_ Sired r
TABLE 1
1 10 25 tebtvalue float
2 158 LAST VALVE_TEST_SP OR_TILIE_ sauct r
TABLi_2
1 to 25 table valor float
2 160 LAST_VALVE_TEST_POSITICN_TAB Sired r
LE 1
1 10 25 taae_valve float
2 162 LAST_VALVE_TEST_POSITION_TAB Sired r
LE 2
1 10 25 latiTa_value float
2 164 0 POS_SENSCII_SN Position sensor serial number Unsigned32
2 168 POS_SENSCW_TEMP_COMP POSItice sensor lemeperature UnSigned8
compensation
2 170 POS_SENSOR_TEMP_COMPJAN_ Poster, sensor lemeperature Met
TABLE compensation lade
1 to 26 table valise float
2 172 POS_SENSOR_TEI/P_COMP_WVC_ POSIke sensor lemeperature Met
TABLE compensation table
1 10 26 tabtvalue float
2 210 VIEW_1 stud 3
1 ST REV
6 616DE BLK
7 ALARM SW
Analog Output Block
3 0 BLOCK OBJECT Week characteristic ds32 1 r
50(52)
EFTA01216919
Appendix A. Parameter table
siot Index Els- Default Defect Parameter Dela Data N of 0/Cie reed
mart Value boa S vale
mans
1 0 reserved
2 0x02 Block Object Rock type (Waco)
3 0102 Parent Class Output
a 0101 Class Analog output
5 0100000000 00-ROferOnCe preserved)
8 010000 DO-Revision (reserved)
7 014002 Profile PA profile number assigned by ENO la
PROFIBUS - PA . 64. COMpeCt Clete B
8 04300 Profile Revision
9 NCO Erecttion Time for Mure use
10 01332 Number of Parameters
II 010040 Index of VIEW 1
12 0101 Number of View Lists
3 I 0 ST_REV COMO, that * Incremented on every unS8inedIS 1 r
change of configuration parameters
3 2 TAG_DESC Lingo) lag In the system that the user Can wsible_strin 32
specify 9
3 3 0 STRATEGY Strategy Value can be witten to by user for unsgredl 6 1
arm oroceseng
3 4 0 ALERT KEY unsignedS 1
3 5 048 TARGE-T_MODE Target mode of the AO a Alio unsignedS 1
3 8 AlOCIE_BLX Rock mode ds37 1
1 Ox08 Actual Auto
2 048 Pernitled Auto
3 0108 Normal Auto
3 7 ALARM_SUM Alarm status 0542 1 r
1 04000 Current Alarm
2 OXCOCO Unacknowledged
3 Ox0000 Unreported
4 MOM Disabled
a BATCH INFORMATION Stored information for batch processes record 4
1 0 BetCh_15 unstene032
2 0 Equipment unsignedIS
3 0 Operation unsignedIS
4 0 mese unsigned16
3 9 SP Selpoir4 in per cent. wth rat to PV_SCALE d533 1
1 0 Value IEEE-754 4
float
2 0118 Status unsignedS I
3 11 eV SCALE Scaling of the selpoiM 0536 1
1 100 EU-St 100%
2 0 EU at 0%
3 1342 Lime Index
4 2 DOCImei Pant
3 12 READBACK Readbadt in per cent. with ref. to d533 1 x r
PV_SCALE
1 0 Value IEEE-754 4
float
2 Status unsgred8 1
3 14 FICAS_IN Setpoinc In Remote Cascade mode d533 1
1 0 Value IEEE-754 4
float
2 0118 Status unsigned:9 1
3 21 1 1N_CHANNEL Asszgnrnent to the transducer block unsignedIS 1
(feedbadi)
3 22 1 OUT_CHANNEL Assignment to thetransducer dock unsignedIS 1
(COMICOIng)
3 23 30 FSAFE TIME Respcnse limn after commun.:alien failure float 1
3 24 2 FSAFE_TYPE Type 04 resealse to communication failure unstenedS 1
3 25 0 FSAFE VALUE SelpoiM on communication failure float 1
3 27 RCAS -OUT Readback in Remote Cascade mode ds33 1
1 0 Value IEEE-754 4
float
2 Status unsigned:9 1
3 31 Mil Discrete pose*, d534 x r
I Value unsigned:9 1
2 Status unsgred8 1
3 32 SE TP_DEVIAT1ON Difference between position setpoint and float 1 r
measurement
3 33 CHECK BACK Device informaticn octel_string 3 x r
3 34 OX9E7603 CHECK_BACK_MASK Mask for device informaton oclet_sirng 3 r
3 35 SIMULATE of
Simulation the roadbed,. ds50 1
Sirnulate_St8WS
Smulate_Value
0 Simulate_En f NSW/
3 38 0 INCREASE CLOSE Positioning &action unsigned8 1
3 37 OUT SielpOiM in per cent. WM rel. to 0533 1 r
OUT_SCALE
1 0 Value IEEE-754 4
float
2 Status unsgred8 1
3 38 OUT_SCALE 5C-tiling c the output value 0536 1 r. w
I 100 EU at 100%
2 0 EU et 0%
3 1342 Unds Index
4 2 Decimal Pont
3 64 VIEW_1 alma 6
1 ST_REV
6 MODE BLK
7 ataatai sum
12 READBAO(
31
33 CHECK_BACK
51(52)
EFTA01216920
Appendix B. Adding the ND800PA to the PDM project.
7 Appendix B. Adding the ND800PA to the PDM project.
The following table is a copy from Siemens document "Using SIMATIC PDM to connect a
PROFIBUS PA device to a PROFIBUS interface (Standalone-Version)"
(simaticpdm_pa_e.pdf).
Table 6. Adding the ND800PA to the Simatic PDM project.
Action Mouse action Input Remark
Start SIMATIC PDM Th. lions the SMATIC,Mantoet
• Double dick on the .simAtic- Tr. SILIATe-lAsnego. it wedw to!
Manager vo the conmutycsboto o tiys, ebtch
are toed by SIMATIC CCM
Select the Process Device ..• Options .> Customize -> View .>
Network View as default .Process Device Network View"
view
in, es /
Set the PC/PG-Interface • Options -> Set POPC-Interface' 110 •
"
s' Click on e.g. CP5511(Profibus) adepts. TOO sure the yp°
°0000+4 COMO/Jed lo th. I
, Click on .Properties* corn
. Make following settings:
- Profile: OP
- Transmission Rate: 45.45kbps
• Deselect .Not the Only
Master Active"
Create a new project . File •,. New Enter the project name
+ Click on „OK'
insert a PROFIBUS DP • Double click on .networks' in the
network right window
• Click on .nehverks" in the left
window
• Right mouse button -> Insert new
object -> PROFIBVS DP network
Insert a PC
• Pick on .Networks" in the left
window
• Right mouse button -> Insert new
object -> PC
Define the now PC to the . Click on .PC' in the left window ar selecting 'Dein, currert Pt. or.
PC object you psi inserted wmo ne
active PC • Right mouse button -> Options -> Poled 4 WSW 10 eticale in. it ,
Define current PC tine OS OW aanii,C
Insert e interface in the '• Click on .(x)PC' in the right window
active PC • Right mouse button -> Insert new
object -> PROFIBUS DP interface
Select the correct network • Double dick on .(x)PC" in the right
for the PROFIBUS DP window
interface • Click on PROFIBUS DP interface"
in the nght window
• Right mouse button .> Object
properties
• Select Page .Network*
• Select PROFIBUS DP network
about the arrow
• Click on .OK'
I risen a PA device • Click in the left window on Enter the device name
.PROFIBUS DP network" ->Click on .OK"
• Right mouse button -> Insert new
object -> PROFIBUS PA device
Sot the device address • Click on the new PA device in the Enter the PA address no "ThsIT" tr "Paid t° th.
right window ->Click on -OK" PA address of the onwcIrJ&Mc,
Default oaths: •26
• Right mouse button -> Object
properties
• Select Page _Connection*
The parametenng of the • Double dick on the now PA device
device is within SIMATIC in the nght window
PDM • Select the right device about the
menu tree (This menu comes only
by the first selection )
• The parametenng of the device is
within SIMATIC PDM
52(52)
EFTA01216921